background image

Liquid Controls 
Sponsler, Inc.

 

IT400 Remote Totalizer & Rate Indicator

 

Page: 12 

DOC#: 

MN-IT400-R2c.doc 

 

 

 

 

 

Signal

 input from practically any frequency generating device producing a sinusoidal signal, a 

square wave pulse or can be connected to a modulated carrier pickup coil. 

Sinusoidal signal:

 low amplitude crossing signal that doesn’t exceed the 

IT400

’s input 

specification.  This signal can come directly from the pickup coil sensing rotation of the 
attached Sponsler, Inc. turbine flowmeter or other flowmeter device. 

Square signal:

 any zero referenced pulse that doesn’t exceed the 

IT400

’s input 

specification. 

Modulated carrier:

 derived by modulating a carrier signal of the pickup coil caused by 

the change in impedance resulting from the rotor blades passing in proximity to the coil.  
This is an inductive coil therefore there is no drag on the rotor.  MC coil operation is 
factory enabled only.  MC coil operation requires DC or loop power. 

Note:

 SW5-3 must be “

On

” for MC coil operation when externally DC powered. 

Backlight 

The backlight is controlled by a combination of system parameters.  The following table lists the 
operation of the backlight and how it is controlled by these various system parameters: 

DC 

Powered 

4-20mA 

Powered* 

Battery 

Condition 

 

value 

Backlight 

in 

 

Backlight 

in Menu 

Yes 

Don’t Care  Don’t Care 

Non-Zero 

ON 

ON 

No 

No 

Good 

Non-Zero 

Timer 

ON 

No 

No 

Low 

Don’t Care  Manual 

OFF 

No 

Yes** 

Good 

Non-Zero 

Timer 

ON 

No 

Yes 

Don’t Care 

Don’t Care  Manual 

OFF 

Don’t Care  Don’t Care  Don’t Care 

 

Manual 

OFF 

Don’t Care  No 

Good 

ON 

ON 

* SW5-1, SW5-2, & SW5-3 “

On

”. 

** SW5-3 “

Off

” (4-20mA loop to power modulated input and battery to power main circuit). 

*** If the timer is set to 

, the battery will last about two months when not DC powered. 

The front panel magnetic reed switch activates the backlight regardless of anything (as long as power 
is applied).  Backlight activation may increment one additional input pulse and will cause 4-20mA 
errors. 

Power 

The 

IT400

 may be powered externally by any 5-48VDC source, 4-20mA loop, internally by battery, or 

by a combination of these.  Power consumption is affected by programmed options, input signal 
frequency, and the programmed power mode. 

 

External Power 

o

 

DC:

 5-48VDC 

o

 

4-20mA Loop:

 used to power the 

IT400

 or just the modulated carrier circuit (which 

requires more voltage than is available from the battery).  The 

IT400

 requires 7VDC of 

the loop supply. 

Содержание IT400

Страница 1: ...INSTALLATION OPERATION MANUAL IT400 Remote Totalizer Rate Indicator Document MN IT400 R2c doc...

Страница 2: ...Every effort has been made to design and manufacture this instrument to be safe for its intended use A hazardous situation may occur if this instrument is not used for its intended purpose or is used...

Страница 3: ...l Overview 7 Calibration 7 Temperature Compensation 7 Linearization 7 LCD Display 8 User Controls 9 Non User interfaces 9 Inputs 11 Backlight 12 Power 12 Enclosure 13 Menu System 14 Button functions 1...

Страница 4: ...tputs are fully opto isolated not RS 232 RS 232 port available Temperature compensation RTD probe available Backlight and backlight timer for low light display viewing Autoranging Rate display decimal...

Страница 5: ...e separate unit displays Decimal Locations Total Two places and x10 x100 Rate Three places and x10 x100 autorange Time Base Rates can be displayed in units per second minute hour day and custom in sec...

Страница 6: ...nected to an earth ground via the screw attached to the outside of the unit At least a 12 AWG preferably green wire is recommended All connections are to be made to the unit via rigid conduit All conn...

Страница 7: ...Liquid Controls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 4 DOC MN IT400 R2c doc Diagrams Figure 1 IT400 Connections...

Страница 8: ...ls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 5 DOC MN IT400 R2c doc TB5 TB6 J1 J3 TB2 TB3 TB4 JP3 TB5 1 2 3 4 1 2 3 4 1 1 2 1 2 1 1 2 3 2 1 TB1 Figure 2 IT400 Board Stack Assembly and Ba...

Страница 9: ...Liquid Controls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 6 DOC MN IT400 R2c doc Figure 3 Meter Mounting and Dimensional...

Страница 10: ...re is out of a programmable range Optionally an alarm output as well as a totalizer inhibit function can also be tied to this temperature warning Various Coefficient of Thermal Expansions and their re...

Страница 11: ...e display also show the engineering units of volume time and decimal place used to compute the rate value Note When the Grand Total magnetic reed switch is activated and GRAND is displayed on the scre...

Страница 12: ...of the IT400 indicated on the front panel with yellow text These switches allow external activation of the following functions Grand The following actions are taken when the grand reed switch is acti...

Страница 13: ...se divider to 1 The 15 pulses would take 1 5 seconds 15x100ms only 10 pulses would be outputted Either the pulse width must be reduced or if acceptable the divider increased Guideline calculate the ma...

Страница 14: ...hows the engineering units of each value The date time is adjusted for local time zone as set in the menu DST is not included as this would allow duplicate time stamps Example Date Time Mon Jan 18 203...

Страница 15: ...The following table lists the operation of the backlight and how it is controlled by these various system parameters DC Powered 4 20mA Powered Battery Condition value Backlight in Backlight in Menu Y...

Страница 16: ...loop isolation switches SW5 1 2 must be Off isolated Loop powered operation the loop isolation switches SW5 1 2 must be On non isolated Power Mode controls the refresh rate of both the display and out...

Страница 17: ...mber will change according to the number dial When editing decimal placement of a number the decimal point will change according to the number dial Editing numbers Some menu items require the editing...

Страница 18: ...re degrees Fahrenheit and must match the Coefficient of Thermal Expansion used in the next item and is listed in the Appendix 2 2 Coefficient of Thermal Expansion The Coefficient of Thermal Expansion...

Страница 19: ...e conversion 5 Totalizer Units Set by turning the Number dial to the desired position The dial positions allow several standard conversions as well as three customizable settings The conversion from g...

Страница 20: ...ut is enabled or disabled in this menu If the 4 20mA output is the next two sub menu items are skipped 10 1 4 20mA Output Low Setting Used by the 4 20mA output as the low setpoint Edit the number to r...

Страница 21: ...t Timer Determines the length of time the backlight remains On when activated Set by turning the Number dial to the desired position The dial positions allow several standard timer values in seconds a...

Страница 22: ...the is set to The totalizer will not count any gassing of the meter it will not totalize when the detected temperature is outside the liquid temperature range To set an alarm press Select A prompt to...

Страница 23: ...ivation and Output Settings 16 2 Datalogger Activation and Output Settings Setting the datalogger activation and output settings flows seamlessly from the previous menu listing The same procedure as i...

Страница 24: ...s the setting of the time portion of the real time clock The current time is set by holding Select for more than 3 seconds Prompts for time zone 4 hour 5 minute and second are displayed The internal t...

Страница 25: ...by the flowmeter input The value is in Hz Pressing Select displays the max frequency received by the flowmeter input 2 2 The displayed value is the raw resistance value of the RTD in ohms The value i...

Страница 26: ...Liquid Controls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 23 DOC MN IT400 R2c doc Appendix...

Страница 27: ...se Width 0 Frequency 1 1 ms 2 2 ms 3 5 ms 4 10 ms 5 50 ms 6 100ms 7 Custom Pulse Output Divider 0 1 1 2 2 5 3 10 4 50 5 100 6 1000 7 Custom 12 Backlight Timer 0 Disabled 1 2s 2 5s 3 10s 4 30s 5 1m 6 3...

Страница 28: ...Temperature F Coefficient of Thermal Expansion Air 7 294 317 8 0 0016262 Ammonia 5 699 28 2 0 0005704 Argon 11 616 302 6 0 0014861 CO2 8 733 10 0 0 0012609 Methane 3 540 258 7 0 0010523 Natural Gas 3...

Страница 29: ...es No 0000 C oD E Number Entry Lockout Correct R ST YES ToTAL Feature C Purchased oF 60 000 R EF T Number Entry 0 0001015 TC oEF Number Entry No Yes EN ABLED TC oM P Temperature Compensator Enabled Ye...

Страница 30: ...te Set FY to zero after last valid entry Yes 1 0000000 UNI TT 60 000000 FCt or Set with Dial Number Entry DEC T Set with Dial Linearizer Enabled No Yes 8 3359000 LBS 3 7810000 KG 1 2000000 Custom Sele...

Страница 31: ...ith Dial 4 20mA Enabled No Yes 0 0000000 oU TLo Number Entry 99999 000 oU ThI Number Entry 604800 00 Custom 8 3359000 LBS 3 7810000 KG 1 2000000 Custom GAL LIT LBS FT3 M3 BBL KG Custom 0 001 0 01 0 1...

Страница 32: ...Menu Enter Menu Enter Menu Enter Menu Enter FREQUENCY 2 5 10 50 100 75 Custom 1 2 5 10 30 100 1000 75 Custom DI SABLED 2 5 10 30 60 180 300 600 75 Custom Menu Enter Select Digit PM oDE Set with Dial...

Страница 33: ...Enable Disable Enable Disable Enable Disable DI SABLED AW AR N DI SABLED AG R N D DI SABLED ATI M E DI SABLED SER D B Enable Disable Enable Disable Enable Disable Enable Disable DI SABLED A R ST Enab...

Страница 34: ...ect Digit Menu Enter Menu Enter Set with Dial 0 10 50 75 100 Menu Enter VERSI O N 1 10 P6 1 0 0000000 FLoLo Number Entry 9999999 2 FLohI Number Entry Select Digit Select Digit 10 DELAY Set with Dial 7...

Страница 35: ...NFI G SAVED R U N Number Entry NEG TM P Lo Continue Can the value be negative PoS TM P Lo 35000000 TM P Lo No Is the value positive Yes No Yes Can the value have a decimal point Menu Enter Set with Di...

Страница 36: ...ities to LB Gal 22 Added Version to test mode 28 Revision history added 29 Various formatting and editorial markups R2 1 17 2006 Added Datalogger and Real Time Clock sections to Operational Overview M...

Страница 37: ...Liquid Controls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 34 DOC MN IT400 R2c doc...

Страница 38: ...Liquid Controls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 35 DOC MN IT400 R2c doc...

Страница 39: ...Liquid Controls Sponsler Inc IT400 Remote Totalizer Rate Indicator Page 36 DOC MN IT400 R2c doc...

Страница 40: ...2009 Pub No MN IT400 R2c 1 2011...

Отзывы: