INSTALLATION AND OPERATING INSTRUCTIONS
INSTALLATION (All Models)
1.
Identify your unit from the model description on the serial number label affixed to the heater and the exploded views contained in this manual.
2.
Where necessary. Fit wheels on axle using the clips and cover supplied. Fit axle assembly and support to the tank using the bolts supplied.
3.
Fill the Fuel Tank using clean filtered fuel.
4.
Connect Power Plug to Mains Power Outlet
5.
Have your chimney installation checked by local authorities.
OPERATING INSTRUCTIONS
TO START & USE
1.
WHERE FITTED. This unit can be fitted with a thermostat. If required please contact your service agent for further information. Set operating
temperature to the desired position on the thermostat.
2.
Turn power switch to the On (I) position. This will start the ignition cycle.
TO STOP (NORMAL OPERATION)
1.
Turn power switch to the Off position. The fan will continue to run until the cooling cycle is complete, DO NOT REMOVE THE PLUG FROM
THE ELECTRICAL SUPPLY UNTIL THE FAN HAS STOPPED RUNNING AS THIS WILL CAUSE DAMAGE TO THE UNIT.
2.
After the fan has stopped running remove the plug from the electrical outlet
MAINTENANCE AND FAULT FINDING PROCEDURES
WARNING: ALWAYS ISOLATE UNIT FROM THE ELECTRICAL SUPPLY BEFORE ATTEMPTING ANY REPAIRS OR MAINTENANCE.
TROUBLESHOOTING GUIDE
FAULT
CAUSE
A
The fan motor never starts
1-2-3-4-5-6-7-14
B
The fan motor starts but unit goes into lockout
8-9-10-11-12-13-14-15-17
C
Heater runs but excessive smoke/smell is emitted
4-8-11-15-16-17
D
Heater runs but flames exit from front guard
15-16-17
ALL REPAIRS / MAINTENANCE WORK SHOULD BE CARRIED OUT BY A QUALIFIED TECHNICIAN.
CAUSE
REMEDY
1.
Electricity Supply is faulty
Check the power plug is plugged in.
Check that electricity supply is available and wiring connections are secure
2.
The motor is blocked/faulty
Check and replace as necessary
3.
The fan is blocked/damaged
Check and replace as necessary
4.
The compressor assembly is blocked/damaged
Check and adjust or replace as necessary
5.
Switch/switch connections is/are faulty/loose
Check and replace as necessary
6.
If fitted:
The thermostat setting is incorrect
The thermostat plug is not plugged in
The thermostat/thermostat connection is loose/faulty
Adjust thermostat accordingly
Plug the thermostat plug into the appropriate socket
Check and replace as necessary
7.
Limit thermostat is faulty
Check for continuity in Limit thermostat connection
8.
Diesel flow absent /low
Check that the fuel tank is full. Fill if necessary.
Check fuel filter for blockages. Clean/replace as necessary.
Check fuel line for blockages. Clean or replace as necessary.
Check air line for blockages/leaks. Tighten/clean or replace as necessary.
Check air filters. Clean and replace as necessary
Check the compressor assembly for correct operation. Adjust and replace as
necessary.
9.
Diesel nozzle Blocked /faulty
Check and clean/replace as necessary
10.
Photocell flame detection unit dirty or not working properly
Check, clean and adjust or replace as necessary
11.
Inlet/outlet grill or inside of heater is dirty or partially blocked
Check and clean as necessary
12.
Limit thermostat cuts in interrupting the heater
Check if the inlet/outlet grill are dirty or blocked, clean as necessary
Check that airflow in and out of the heater is not impeded
13.
Diesel is not igniting
Check Transformer and replace if necessary
Check High Tension leads and adjust/replace as necessary
Check electrodes and adjust and replace as necessary
14.
Burner Control box faulty
Check and replace if necessary
15.
Pressure adjustment is incorrect
Check and adjust/clean compressor regulating valve as necessary (Follow
pressures listed in the technical specifications an see maintenance instructions)
Check compressor for correct operation and wear. Adjust/replace as necessary.
Check air line for blockages/leaks. Tighten/clean or replace as necessary.
16.
Nozzle O’Ring is damaged
Check and replace as necessary
17.
Fuel is contaminated/bad quality
Drain tank and replace fuel