Spirent A2-400 Appliance Installation Instructions
Site Selection
Spirent A2-400 Appliance Installation Instructions
|
7
PN 71-009456 Rev A October 2022
Site Selection
The Spirent A2-400 appliance is a high-end network testing device that must be installed
in a dust free and dry environment with adequate airflow, power, and cooling.
•
The appliance is designed with front to rear airflow and both ventilation locations
must remain unobstructed for proper operation. Inadequate cooling or airflow can
result in an over-temperature situation that will cause an automatic system shutdown.
•
The appliance is designed to be mounted in a telecom-style 19" 4-post open rack.
•
The rack must be designed, and adequately secured, to accommodate the fully
loaded weight of the appliance and any other installed equipment.
•
It is not recommended to install the appliance in an enclosure unless it is
specifically designed to handle the airflow and cooling requirements.
Refer to
for temperature and power requirements.
Refer to
“Rack Mounting Considerations” on page 8
Technical Specifications
•
Environmental
•
Operating requirements:
–
50° to 95° F (10° to 35° C) when using QSFP-DD transceivers rated up to
15W. When using QSFP-DD transceivers s exceeding 15W, the maximum
operating temperature is 86° F (30° C); 10% to 80% relative humidity (non-
condensing). The minimum operating temperature is 41 ° F (5° C).
Warning:
Always use appropriate ear protection when working in proximity to an
operating appliance.
•
Appliance Design and Form Factor
•
EIA 19" rack compatible, 2RU high
•
Front to back airflow
•
Physical
•
Dimensions: 17.1"W x 3.5"H x 29.5"D (43.4 cm x 8.9 cm x 74.9 cm)
•
Unit installed weight: 62 lb. (28.2 kg)
•
Shipping weight: 86 lb. (39.1 kg)