Table 9 R1C test modes
(in test mode the green LED flashes every half a second):
SW1
SW2
Mode
1
1
2
Trap monitor mode - the R1C’s trap leaking steam detection period
filters turns off and the outputs show if there is steam or condensate
ON
OFF
OFF
present in the trap. In this mode, the switches controlling the temperature
and conductivity thresholds still operate as described in the Tables
on pages 8 and 9.
ON
OFF
ON
BEMS /EMS set-up mode - the R1C will cyclically change it’s outputs,
one step every 8 seconds.
An analogue output is available from the R1C as standard for use with BEMS /EMS’s that
operate on an analogue input signal. Recommended BEMS /EMS setting details are given
below:
Table 10 BEMS / EMS recommended analogue settings
Trap status
Nominal output
Recommended BEMS / EMS
current from R1C
alarm threshold settings
Trap operating correctly
20 mA
23.0 mA > setpoint > 17.5 mA
Trap leaking steam
15 mA
17.5 mA > setpoint > 12.5 mA
Trap blocked or waterlogged
10 mA
12.5 mA > setpoint > 7.5 mA
Trap cold, but free of
4 mA
7.5 mA
> setpoint > 0 mA
condensate (or R1C failure)
Two digital outputs are also available from the R1C as standard.
a. PNP open collector outputs
b. NPN open collector outputs
R1C digital outputs
Trap status
Waterlogged
Leaking steam
Trap operating correctly
ON
ON
Trap leaking steam
ON
OFF
Trap blocked or waterlogged
OFF
ON
Trap cold, but free of condensate
(or R1C failure)
OFF
OFF
5. BEMS/EMS commissioning