Body design conditions
M70i
PN63
M80i
720 psi g
PMA Maximum allowable
pressure
M70i
62 bar g @ 20 °C (899 psi g @ 68 °F)
M80i
50 bar g @ 109 °C (720 psi g @ 228 °F)
TMA Maximum allowable
temperature
M70i
200 °C @ 0 bar g (392 °F @ 0 psi g )
M80i
180 °C @ 0 bar g
(356 °F @ 0 psi g)
Minimum allowable
temperature
M70i
-29 °C
(-20 °F)
M80i
-20 °C
(-4 °F)
PMO
Maximum
operating
pressure for
saturated
steam
service
*
M70i ISO
Virgin PTFE TFM 1600
7.0 bar g
(101 psi g)
Mineral filled PTFE
8.5 bar g
(123 psi g)
M80i ISO
Virgin PTFE TFM 1600
7.0 bar g
(101 psi g)
TMO Maximum operating
temperature
M70i
200 °C @ 0 bar g (392 °F @ 0 psi g )
M80i
180 °C @ 0 bar g
(356 °F @ 0 psi g)
Minimum operating temperature
M70i
-29 °C
(-20 °F)
M80i
-20 °C
(-4 °F)
Note:
For lower operating temperatures consult Spirax Sarco.
D
PMX
Maximum differential pressure is limited to the PMO
Designed for a maximum cold
hydraulic test pressure of:
M70i
93 bar g
(1348 psi g)
M80i
75 bar g
(1 087 psi g)