
IM-IBR17-49IN
Issue 1
9
0
0
50
100
150
200
220
2
4
6
8
10
12
14
13
16
Pressure bar g
D
B
A
C
Steam
saturation
curve
The product
must not
be used in this region.
A - B - D
Flanged EN 1092 PN16.
A
-
C
-
D
Flanged ASME 125.
Body design conditions
PN16 (For PN16 Flange)
PMA Maximum allowable pressure
13 bar g @ 195 °C
TMA
Maximum allowable temperature
220 °C @ 12.1 bar g
Minimum allowable temperature
0
°C
PMO Maximum operating pressure for saturated steam service
13 bar g @ 195 °C
Note: The DN40 and DN50 traps are limited to a PMO equal to PMX
TMO Maximum operating temperature
220 °C @ 12.1 bar g
Minimum operating temperature
0
°C
Note:
For lower operating temperatures consult Spirax Sarco
D
PMX Maximum differential pressure
FT43-4.5
4.5 bar
FT43-10
10 bar
FT43-14
13 bar
Body design conditions
PN16 (For ASME 125 Flange)
PMA Maximum allowable pressure
13 bar g @ 90 °C
TMA
Maximum allowable temperature
220 °C @ 9 bar g
Minimum allowable temperature
0
°C
PMO Maximum operating pressure for saturated steam service
10 bar g @ 184 °C
Note: The DN40 and DN50 traps are limited to a PMO equal to PMX
TMO Maximum operating temperature
220 °C @ 9 bar g
Minimum operating temperature
0
°C
Note:
For lower operating temperatures consult Spirax Sarco
D
PMX Maximum differential pressure
FT43-4.5
4.5 bar
FT43-10
10 bar
Designed for a maximum cold hydraulic test pressure of
19.5 bar g
Note: With internals fitted, test pressure must not exceed PMX
Pressure / temperature limits
Te
m
pe
rat
ur
e °C
Содержание FT 43 Series
Страница 26: ...IM IBR17 49IN Issue 1 26...
Страница 27: ...IM IBR17 49IN Issue 1 27...
Страница 28: ...IM IBR17 49IN Issue 1 28...