![Spirax Sarco DLV7 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/spirax-sarco/dlv7/dlv7_installation-and-maintenance-instructions-manual_1347915034.webp)
IM-P204-03
CH Issue 8
34
16
Carefully screw head set onto spindle until hand tight.
Caution:
ensure plug adaptor is engaged in the spindle guide plate before tightening fully,
otherwise damage to the bellows may occur.
Refit two M14 nuts onto the stem and lock together.
5.3 Replacement of the bellows assembly (continued)
17
Replace the guide plate and screw the new head set onto the stem (hand tight). Then
proceed to tighten by holding the nut
B
using a 22 mm A / F spanner and tighten the
head adaptor nut
C
with a 24 mm A / F spanner to a torque of 15 ±1 N m for the DN15
- DN20 and 20 ±2 N m for the DN25 - DN100.
Caution:
to prevent any damage care
must be taken not to twist the bellows. To prevent over-extension (stretching) of the
bellows locate the guide plate on the head set before tightening the plug to the stem.
When replacement of the head set is complete, remove nuts
A
and
B
.
C
B