Pressurised Thermophysical deaerator with operator manual for the control unit
6. Troubleshooting
Problem
Possible causes
Corrective action
The unit does not
start
No power
Check the input power
Auxiliary circuit protection on
Check the automatic switch of
the auxiliary circuit protection
in the control board.
Water level in
deaerator very
low.
The deaerator is
in alarm state.
Insufficient pressure of water supply
(< P steam gen 0.5 bar g)
Check the conditions of the
water supply. Check that the
water pressure is correct and
there are no pressure losses
when the deaerator load
increases. Clean the filter
upstream the regulator valve.
Check the shut-off valve on
the line is completely open.
The deaerator is loading
Wait until loaded and the
automatic alarm reset.
The water supply control valve is not
working correctly
Check the solenoid valve
mounted on the pneumatic
regulation valve and relative
control panel protection fuse.
Check the air pressure is
correct. If necessary replace
the solenoid valve or fuse.
Fault/malfunction of level controller
(LIC-01)
Check the settings. Check
that the I/P converter or
positioner of the control valve
reaches the control signal
from the controller. Switch to
the regulator manual control
to verify the operation of the
signal. If necessary replace
the controller.
Fault of level transmitter (LT-01) or
damage to measuring instrument
Check the transmitter signal
and that it corresponds to the
measure of the level indicator.
Check that the level display
does not remain stationary.
If necessary replace the
instrument.