background image

Water Heaters

Workshop Manual

Thermo 230
Thermo 300
Thermo 350

with control unit 1572
model .30 and up

Thermo 230
Thermo 300
Thermo 350

with control unit 1572D
model .030 and up

Thermo 231
Thermo 301

model .01 and up

Thermo Rail

12/2012

Ident Nr. 9003656C II

Содержание thermo 231

Страница 1: ...al Thermo 230 Thermo 300 Thermo 350 with control unit 1572 model 30 and up Thermo 230 Thermo 300 Thermo 350 with control unit 1572D model 030 and up Thermo 231 Thermo 301 model 01 and up Thermo Rail 1...

Страница 2: ......

Страница 3: ...lectrodes 203 2 8 Temperature Sensor 204 2 9 Temperature Limiter 204 2 10 Overheat Thermostat Thermo 231 and 301 only 204 2 11 Circulation Pump 204 2 11 1 Aquavent 5000 U4814 and Aquavent 5000S U4854...

Страница 4: ...lenoid Valve Check 604 6 3 8 Nozzle Block Preheater Check 604 7 Circuit Diagrams 7 1 General 701 8 Servicing 8 1 General 801 8 2 Heater Servicing 801 8 3 Vehicle Servicing 801 8 4 Heater Test Run 801...

Страница 5: ...fications 902 9 2 Disassembly and Assembly 906 9 2 1 Temperature Limiter Replacement 904 9 2 2 Temperature Sensor Replacement 904 9 2 3 Burner Replacement 904 9 2 4 Combustion Air Fan Replacement 906...

Страница 6: ...705 System Circuit Daimler Chrysler Citaro Ident Nr 67131 706 706 System Circuit Van Hool Ident Nr 89401 707 707 System Circuit O405 O407 O408 Ident Nr 91292 708 708 System Circuit MAN Ident Nr 89404...

Страница 7: ...The general safety regulations for the prevention of accidents and the relevant operating safety instructions have to be observed at all times General Safety Regulations beyond the scope of these regu...

Страница 8: ...above all by the provisions in Annex VII of Directive 2001 56 EC NOTE The provisions of these Directives are binding within the territory governed by EU Directive 70 156 EEC and should similarly be ob...

Страница 9: ...and Improvements Deficiencies improvements or proposals for correction of this workshop manual are to be mailed to Spheros GmbH Friedrichshafener Stra e 9 11 D 82205 Gilching Telefon 49 0 8105 7721 88...

Страница 10: ...1 Introduction Thermo 230 231 300 301 350 104 Page empty for notes...

Страница 11: ...operates intermittently controlled by the temperature sensor The heaters Thermo 230 231 300 301 and 350 basically consist of the combustion air fan the fuel pump with nozzle block and nozzle the heat...

Страница 12: ...rated into the fuel pump opens and closes the fuel supply to the atomiser nozzle Three different fuel pumps are assigned to the different heating capacity classes of the Thermo series These are identi...

Страница 13: ...air mix is dispersed in the combustion chamber for combustion to heat the heat exchanger Heat exchanger Combustion chamber 2 5 Control Unit The control unit 1572 or 1572D is the central component to e...

Страница 14: ...noid valve of the fuel pump When the burner overheats the thermostat causes an error lockout Overheat Thermostat 2 11 Circulation Pump The externally mounted circulation pump ensures proper coolant ci...

Страница 15: ...n a time period of approx 45 minutes significantly less current dry running is detected The circulating pump motor is switched off After approx 2 minutes and circulating pump motor reactivation the op...

Страница 16: ...he series 230 300 350 126 and 190 Rail an optional heatable fuel filter is provided as an additional option also for 124 and 155 Rail If the electrical filter heating is hooked up the temperature swit...

Страница 17: ...lock preheater for extreme low temperatures Heaters with control unit 1572D only When connecting terminal 61 the heaters may operate in the auxiliary heating mode of operation Switching thresholds Con...

Страница 18: ...r 300 or 350 3 1 Switch On Upon switch on the operating indicator light goes on Combustion air fan fuel pump and circulation pump start operation If fitted and temperature is 0 C nozzle block preheate...

Страница 19: ...heating mode The power save mode is during auxiliary heating automa tically deactivated by the control device The lower temperature threshold for reactivation of the burner after control idle period...

Страница 20: ...Pre ignition 15 Safety period 16 Run down 3 Functional Description Thermo 230 231 300 301 350 304 temperature sensor short circuit during control idle temperature sensor open circuit during combustio...

Страница 21: ...approx 120 seconds Malfunctions during switch on Short or open circuit of temperature sensor flame sensor burner motor solenoid valve igniter box Malfunctions during start up short circuit of igniter...

Страница 22: ...y of the timer after a malfunction NOTE When the heater is operated by means of a switch the type of error is output during heater run down via a flash code of the operating indicator light After five...

Страница 23: ...fied by the vehicle manufacturer Only the type of fuel indicated on the identification plate may be used Also Diesel fuel with an addition of 5 PME vegetable oil methyl ester class EL fuel oils not fu...

Страница 24: ...V 24 Operating voltage V 20 28 Operating voltage valid for application Thermo 350 190 V 19 28 Nominal power consumption without circulation pump W 65 110 140 Permissible operating ambient temperature...

Страница 25: ...0 4 bar 6000 against 0 4 bar Nominal voltage V 12 or 24 24 24 24 Operating voltage range V 10 14 20 28 20 28 20 28 20 28 Nominal power consumption W 104 104 210 210 Dimensions Lenght 230 Width 100 He...

Страница 26: ...4 Technical Data Thermo 230 231 300 301 350 404...

Страница 27: ...fault symptoms of general nature Symptom Probable Cause Fault in electrical system Operating indicator light is not on no heater operation no power supply fuses wiring to terminals of connector A of...

Страница 28: ...cause air in heat exchangers or in system sections contaminated heat exchanger surfaces external insufficient air intake or exit fan rate of delivery low wrong sense of rotation resistance too high to...

Страница 29: ...refer to operating instructions for Diagnostic Computer Components Tester NOTE Checks with the components tester may only be performed on heaters equipped with control unit 1572 Using the components...

Страница 30: ...s trouble persist Check motor electrics and replace as required Replace cap and fan wheel Is voltage too low Rated value 20 5 volts 0 5 volts Check electrical wiring and connections Does trouble persi...

Страница 31: ...onents Is fuel filter contaminated or jellied Is fan wheel free to move Check cap motor and fan wheel Is motor o k Is viewing glass of flame sensor contaminated Clean window and viewing glass Replace...

Страница 32: ...n and restart approx 2 min Does same symptom show again Clean combustion tube Remove coke deposits Control unit defective replace Flame in run down Replace solenoid valve Flame sensor defective replac...

Страница 33: ...nents test with diagnostic computer o k audible click of solenoid valve Make electrical connections Control unit defective replace Does fuel leak from nozzle in run down Replace solenoid valve Investi...

Страница 34: ...temperature limiter Determine why temperature limiter has responded e g check shut off elements check water circulation in system is free from bubbles check circulation pump sense of rotation check c...

Страница 35: ...ustion functional checkouts nozzle replacement Setting procedure measure control unit power supply voltage operate heater for approximately 5 min measure CO2 contents and smoke spot number and compare...

Страница 36: ...glass of the window refer to Fig are to be cleaned if contami nated In case of damage or not obtaining the rated values replace flame sensor Check cover flame sensor glass bulb check resistance rated...

Страница 37: ...ed every 5 years CAUTION The electronic ignition coil must be removed for safety reasons Check remove igniter box refer to 9 2 7 1 remove nozzle screw on tester cover flame sensor switch on heater aft...

Страница 38: ...y clearing the area between solenoid valve and nozzle bore Check CAUTION Disconnect solenoid valve connector from control unit to avoid damage to the control unit Check electrics for the following val...

Страница 39: ...350 with control unit 1572 and with switch timer 1529 triple timer The circuit diagrams Fig 703 and 704 show possible heater circuits for Thermo 230 231 300 301 and 350 with control unit 1572D and wit...

Страница 40: ...ark S3 Switch external trigger circulation pump S4 Switch power save operation U1 Igniter box U2 Igniter electrodes A Plug connections 6 pole C Plug connections 1 pole D Plug connections 4 pole X1 Plu...

Страница 41: ...ter B4 Thermostat opens at T 8 C E1 Heating cartridge for nozzle preheating F2 Fuse 25A flat fuse SAE J 1284 F3 Fuse 25A flat fuse SAE J 1284 F6 Fuse 5A flat fuse SAE J 1284 H3 Light in item P symbol...

Страница 42: ...idge for nozzle preheating F1 Fuse 5 A flat fuse DIN 72581 part 3 F2 Fuse 25 A flat fuse DIN 72581 part 3 F3 Fuse 25 A flat fuse DIN 72581 part 3 H1 Light operation indicator light H2 Light flame indi...

Страница 43: ...ns 1 pole D Plug connections 4 pole F Plug connections 2 pole X1 Plug connections 6 pole X2 Plug connections 2 pole X3 Plug connections 8 pole X4 Plug connections 12 pole Y1 Solenoid valve Item Nomenc...

Страница 44: ...sensor observe polarity B2 Temperature sensor polarity optional B3 Temperature limiter B4 Thermostat for nozzle preheating E1 Heating cartridge for nozzle preheating F1 Fuse 25 A flat fuse DIN 72581...

Страница 45: ...preheating B5 Fire sensor Van Hool E1 Heating cartridge F2 Fuse see table F3 Fuse see table H1 Light operation indicator light H2 Light flame indicator K1 Relay in item A2 for circulation pump motor K...

Страница 46: ...ting cartridge for nozzle preheating F2 Fuse see table F3 Fuse see table H1 Light operation indicator light H2 Light flame indicator K1 Relay for circulation pump motor K2 Relay for combustion air fan...

Страница 47: ...5 A flat fuse DIN 72581 part 3 F3 Fuse 25 A flat fuse DIN 72581 part 3 H1 Light operation indicator light H2 Light flame indicator M1 Motor combustion air fan M2 Motor circulation pump S1 Switch on of...

Страница 48: ...or M1 Motor combustion air fan M2 Motor circulation pump S1 Switch on off S2 Continuity switch on water cock Pos Nomenclature Remark S3 Switch external trigger circulation pump required if S2 not inst...

Страница 49: ...part 3 H1 Light operation indicator light H2 Light flame indicator H4 Heating symbol on the display Power on indicator in item P K4 Relay M1 Motor combustion air fan M2 Motor circulation pump Item No...

Страница 50: ...7 Circuit Diagrams Thermo 230 231 300 301 350 712...

Страница 51: ...ds difficulties in the start up at least once a year in case of contaminated fuel more often the fuel filter or filter cartridge as well as the filter screen of the fuel pump must be replaced to avoid...

Страница 52: ...ler is upstream in exhaust pipe If muffler is dislocated in the exhaust pipe arrest muffler as described in NOTE Slot or drill exhaust pipe and refit 4 If the exhaust muffler has been lost it may be o...

Страница 53: ...al connection s to the temperature limiter and temperature sensor Opening or removal 1 Disconnect electrical connections to temperature limiter and temperature sensor 2 Loosen nuts 3 Fig 801 enough to...

Страница 54: ...n using the circulation pump Aquavent 6000 U4851 or Aquavent 6000S U4852 or Aquavent 6000SC U4856 the circulation pump automatically is switched off approx 15 seconds after switch on if coolant is lac...

Страница 55: ...senger Bus Vorlauf R cklauf 4 8 9 3 1 1 1 1 2 7 5 6 Water heating circuit Sidewall radiators and roof duct heating 1 Sidewall radiator with fan 2 Heat exchanger entrance 3 Heater unit 4 Circulation pu...

Страница 56: ...snow or intake of splash water is to be expected The combustion air intake and exhaust outlet is to be located so that no air pressure difference builds up in any operating condition of the vehicle Pe...

Страница 57: ...and fasten with hose clamps Torque clamps with 1 5 Nm Open water cocks 4 Connect fuel supply and return lines and tighten connections or screw tight with banjo bolt and new gaskets 5 Secure combustion...

Страница 58: ...isconnection of the heater power supply within 120 sec during run down 8 8 1 Water Circuit Bleeding NOTE Bleeding must always be performed in accordance with manufacturer s instructions For bleeding t...

Страница 59: ...The following components may also be replaced with the heater installed unless restricted space prevents access temperature limiter temperature sensor combustion air fan burner igniter box flame senso...

Страница 60: ...ction Inspect exhaust ducting in heat exchanger for sooting deposits damage and corrosion NOTE Deposits are to be removed with water jet and brush Inspect heat exchanger for exterior damage defor mati...

Страница 61: ...identification label Procedure CAUTION Control unit 1572D may only be used in combination with the igniter box delivered green connector cover The electrical connector is coded 1 Remove control unit...

Страница 62: ...al 1 Disconnect electrical connection to temperature sensor WARNING Prior to replacement of temperature sensor in installed condition relief overpressure in cooling system by opening the cooling circu...

Страница 63: ...eplacement Rubber cap Temperature Retaining clip 8 7 6 5 4 3 2 1 1 Temperature limiter 2 Temperature sensor 3 Connector 4 Coolant outlet 5 Cotter pin 6 Nut 2 7 Hinge bolt 2 8 Burner limiter NOTE Cotte...

Страница 64: ...thdraw fan motor 7 5 Perform procedures on components after disassembly refer to 9 1 1 9 2 4 2 Installation NOTE Fan motor 7 Fig 902 to be aligned with control unit recess in mounting flange and with...

Страница 65: ...0 231 300 301 350 9 Repair 907 Fig 902 Combustion Air Fan Replacement 1 2 3 4 5 6 7 8 9 1 Splash protection cover 2 Cap 3 Screw 2 4 Fan wheel 5 Slide lock 6 Screw 3 7 Fan motor 8 Clutch 9 Electrical c...

Страница 66: ...d 4 Disconnect electrical connector 8 NOTE During the following step ensure that escaping fuel is immediately neutralized and properly disposed of 5 Remove screws 9 with lock washers 6 Withdraw fuel p...

Страница 67: ...D and also control unit 1572 1 Control unit 1572D 15 Flame sensor 16 Screw 17 Burner housing 18 Strain relief clamp 2 19 Screw 2 20 Base plate for relays 21 Relay 22 Relay 23 Control unit 24 Heating c...

Страница 68: ...5 Install burner refer to 9 2 3 2 9 2 9 Flame Sensor Replacement 9 2 9 1 Removal 1 Remove burner if required refer to 9 2 3 1 2 If required lever off igniter electrodes Fig 904 from igniter box using...

Страница 69: ...it 1572D and also control unit 1572 1 Control unit 1572D 15 Flame sensor 16 Screw 17 Burner housing 18 Strain relief clamp 2 19 Screw 2 20 Base plate for relays 21 Relay 22 Relay 23 Control unit 24 He...

Страница 70: ...1 2 4 Install temperature sensor refer to 9 2 2 2 9 2 11 Combustion Chamber Replacement 9 2 11 1 Removal 1 Disconnect electrical connections to temperature limiter and temperature sensor 2 Swing burn...

Страница 71: ...d packaged so that they are protected against damage during handling ship ping and storage CAUTION When shipping a complete heater assembly it must be drained completely No coolant is allowed to escap...

Страница 72: ...10 Packaging Storage Shipping Thermo 230 231 300 301 350 1002 Page empty for notes...

Страница 73: ...Thermo 230 231 300 301 350 Annex A A 1 Annex A Scheduled Maintenance...

Страница 74: ...tions for leaks b Replace fuel filter cartridge with gasket c If existing open fuel shut off valves d Fuel pump e Replace fuel filter screen with gaskets in pump Check for leak proof connections in fu...

Страница 75: ...43 1 6043780 Belgien 8263 BC Kampen NL Tel 31 38 3371 137 Bosnien Herzegovina siehe Slowenien Bulgarien 1839 Sofia Tel 359 2 9420 555 Wei russland 220004 Minsk Tel 37 50172201894 Kroatien siehe Slowen...

Страница 76: ...s Papier verwendet Printed in Germany 12 12 Druck Steffendruck Friedland nderungen vorbehalten Subject to modification Sous r serve de modifications Spheros GmbH Spheros GmbH Friedrichshafener Stra e...

Страница 77: ...elling Statutory regulations require that this placard in the respective language of the destination country shall be affixed by the bus manufacturer near the fuel filler The bus operator shall observ...

Страница 78: ...ts bag Small parts for magnetic coil cpl ident no 386650Z may only be used for the below stated heaters Heater Thermo 230 231 300 301 350 with magnetic coil ident no 29313_ Heater DBW 230 2020 300 350...

Страница 79: ...gh technical changes For all magnetic clutch pumps new changed parts will be provided Shroud with changed design Additional gasket and a membrane The bearing splash guard is no longer used By means of...

Страница 80: ...uropa GmbH Abteilung After Sales Friedrichshafener Stra e 9 11 82205 Gilching Tel 49 0 8105 7721 887 Fax 49 0 8105 7721 889 www spheros de service spheros de Technical Information 05 2008 Shroud desig...

Страница 81: ...opa GmbH Abteilung After Sales Friedrichshafener Stra e 9 11 82205 Gilching Tel 49 0 8105 7721 887 Fax 49 0 8105 7721 889 www spheros de service spheros de Technical Information 05 2008 New gasket and...

Страница 82: ...n the nut SW 8 resp SW 12 ref figure and remove the coil body Thereafter the armature sleeve SW 16 can be loosened more easily For installation reverse the sequence Before installing the coil body the...

Страница 83: ...rews M5x16 with spring ring when replacing the old ignition unit 14845C by the new version 2710213A If required please order in the future the 11113935A ignition unit spare parts kit It contains the i...

Страница 84: ...vice spheros de Technical Information 02 2009 Nozzle Block Preheater for Thermo Heaters Installation Notes for Heating Element Retrofit Spheros spare parts kit to be used 86711B Retrofit bag heating e...

Страница 85: ...105 7721 889 www spheros de service spheros de Technical Information 02 2009 Step 2 Shield pre assembly Position thermostat into the shield Install serrated lock washer and hand tighten the nut For re...

Страница 86: ...8105 7721 889 www spheros de service spheros de Step 3 Substep 1 Insert the heating element Substep 2 Secure the heating element with the retaining clamp Substep 3 Remove dummy connector plug in the n...

Страница 87: ...8105 7721 889 www spheros de service spheros de Step 4 Substep 1 Place the pre assembled shield onto the burner head and align it so the ignition electrodes can be plugged in Substep 2 Install ignitio...

Страница 88: ...e spheros de Final result Thermo heater with retrofitted heating element Attention Please consider during all other activities done at the heater in regard to this retrofit the instructions given in t...

Страница 89: ...ros quality optimized spray character spray angle Below of emission limitation permitted per law Labeled with Spheros logo heating power and identification number Warranty and product liability only i...

Страница 90: ...used necessarily Content spare parts kit 1 strainer 7 4 0 1 mm and 2 O rings 7 65 x 1 78 For the previous fuel pump 82233A B the 19977D small parts fuel pump bag 1 repair resp the 1302999B small parts...

Страница 91: ...0 New Spheros ident no for Small parts for magnetic coil As of now the spare parts kit Small parts for magnetic coil can be ordered only using the new Spheros ident no 11113599B previously 386650Z The...

Страница 92: ...pump 11114892A continue to use the heating element 83933C without heating element pump 11114892A pump 11114957A continue to use the heating element 83933C and thermostat 98640B 82233A B only two pipe...

Страница 93: ...the heater fault lock out the related instructions of the appropriate Thermo Thermo S Workshop Manual should be considered see www spheros de Service Tech nische_Dokumente Heizsysteme aspx In this wa...

Страница 94: ...he previous generation Thermo 230 300 350 heaters now the optimized version of Thermo S 230 300 350 heaters can be used In length and diameter it is identical to the Thermo 230 300 350 series The opti...

Страница 95: ...kW 1st letter production month A January M December Nomenclature of production date recurring since 2008 2nd letter production year A 2001 K 2010 A January G July B February H August C March I Septemb...

Страница 96: ...ation Power Ident number Spheros label Thermo S 160 16kW 2710233B yes 230 23kW 2710234B yes 300 30kW 2710235B yes 350 35kW 2710236B yes 400 40kW 2710237B yes Thermo E 200 20kW 2711057A yes 320 32kW 27...

Страница 97: ...just the CO2 content according to the technical data if combustion air supply or exhaust gas applications are used After heater installation bleed the water system and the fuel supply system carefully...

Страница 98: ...heater locking will be reduced to a minimum with the new pump The fuel pumps can be exchanged 1 1 in the field All spare part kits contain fastening bolts Heater Fuel pump Spare part kit fuel pump The...