Manual for dialog WebOrder no.: 443 150
Technical Manual dialog Web
Version 2.01
Radevormwald, 01.09.2020
Page 1 / 47
01.09.2020
Страница 1: ...Manual for dialog Web Order no 443 150 Technical Manual dialog Web Version 2 01 Radevormwald 01 09 2020 Version 2 01 Page 1 47 01 09 2020 ...
Страница 2: ...mmissioning 13 3 Configuration 14 3 1 IP configuration 14 3 2 Service pin of the EIA 852 LON over IP device 17 3 3 Configuration of the operator interfaces 17 3 4 List of rooms 18 3 5 User administration 19 3 6 License management 19 3 7 Backup Restore configuration 19 3 8 Firmware update 20 4 Applications 21 4 1 List of available applications 21 4 2 SC443150EC_01 web room control unit 21 4 2 1 SC4...
Страница 3: ...Manual for dialog Web Order no 443 150 4 3 1 Web room control unit object 27 5 Glossary 44 Version 2 01 Page 3 47 01 09 2020 ...
Страница 4: ...his manual in a location which is easily accessible to all users 1 1 Using the manual The manual is aimed at all persons concerned with the planning installation commissioning and maintenance of the system To provide an easy overview here is a list showing which part of the manual is of interest for different users Introduction Product description Technical Data Mounting and installation Operation...
Страница 5: ...ht to refuse liability for damage to the product Additionally spega shall not be liable for consequential damage and or injury to people or property in such cases 1 4 Explanation of used pictograms These instructions contain pictograms which are used as cautionary notes to facilitate the safe operation and complete commissioning of the system VOLTAGE Denotes immediate danger of electrocution in th...
Страница 6: ...e which has been approved by spega should be used for this device The system integrator should ensure that the software and relevant parameterization correspond with the wiring and intended use of the device Please observe the relevant local standards guidelines and regulations when planning and installing electrical devices 1 6 Order information Order number Description 443 150 dialog Web Server ...
Страница 7: ... more than 150 rooms respectively more dialog Web Server are needed The configuration of the user interface has to be done only once for all servers in one network cluster This offers a maximum overview and a maximum time saving during configuration and commissioning 2 1 Applications Controlling room automation functions with the already existing PC via web browser Controlling room automation func...
Страница 8: ...Manual for dialog Web Order no 443 150 Room control via web browser on mobile devices Version 2 01 Page 8 47 01 09 2020 ...
Страница 9: ...receives from the building network LON IP all data required for the status display of a room such as room temperature setpoint lighting status According to the configuration the data are displayed on the corresponding operating clients PC or telephone For the operation of a room this is done in the opposite direction When a button is pressed e g to switch on the lighting a defined LON telegram is ...
Страница 10: ...Manual for dialog Web Order no 443 150 rooms Thus it can be defined which rooms can only be operated via web browser and which additionally via IP telephone Version 2 01 Page 10 47 01 09 2020 ...
Страница 11: ...r supply connector Control elements Main control switch Power on power off reboot configurable Display elements Power LED State of the device HD LED HDD activity Housing Material metal Dimensions 59 x 168 x 140 mm H x W x D Type of installation Mounting on DIN rail DIN EN 50022 or as tabletop unit Ambient conditions Operating temperature 5 C 50 C with airflow Storage temperature 20 C 80 C Rel humi...
Страница 12: ...Manual for dialog Web Order no 443 150 Standards guidelines Certification CE Version 2 01 Page 12 47 01 09 2020 ...
Страница 13: ...wever only the power supply connection B the PE connection A and the ports for LAN A C and possibly LAN B D are to be used All other connections must remain free This is the only way to ensure correct functioning A B C D 2 7 Commissioning Plug the Ethernet cable into port LAN A Connect the power supply cable to a suitable power source After approx 3 minutes the device is ready for operation and ca...
Страница 14: ...ers Mozilla Firefox version 3 6 or higher and Safari version 4 or higher Enter the default IP address 192 168 1 250 in your web browser Log in as user administrator with the password dialogweb This takes you to the central administration page If the IP address of your PC is not located in the subnet 192 168 1 x you must first change the IP address of your PC accordingly Version 2 01 Page 14 47 01 ...
Страница 15: ...net interface LAN A Access to the web server HTTP and the EIA 852 part LON over IP is via separate IP addresses The setting for using LAN B is disabled on LAN B address of LAN B is used for HTTP is set to LAN A 3 The device is operated with both available Ethernet interfaces Access to the web server HTTP and the EIA 852 part Lon IP is via separate IP addresses The setting for using LAN B must be s...
Страница 16: ...le is displayed for an overview Standard entries cannot be changed or deleted For operation as an EIA 852 Lon IP device the Configuration Server must be specified Click for LonIP Here you can specify the EIA 852 configuration server and the ports to be used The default ports 1628 and 1629 for the Lon over IP protocol are preset Please note that the dialog Web Server must be made known to the confi...
Страница 17: ...vers that are located in an LNS project This function can be found in the plug ins in the File menu and is called Transfer parameter Thus the LON configuration for each room type must effectively be entered only once The user interface is configured via the web interface An interface must be defined for each LON configuration or room type You can access the individual configuration dialogs via the...
Страница 18: ...LON configuration a room name can be specified for each Lonmark object This name is displayed here in the column Room and serves as an help when assigning the room name as it should be displayed on the user interface In the RBG variant column select the user interface configuration that matches the respective room or the configuration of the Lonmark object At this point you therefore combine the L...
Страница 19: ...changes it is possible to export the user data to a CSV file edit it in a suitable program such as Microsoft Excel and import it again Use the User data dialogs for this purpose Mass Import Mass Export dialogs accessible via the central administration page and follow the instructions on the screen Note For security reasons the password for the Administrator user cannot be reset If you have forgott...
Страница 20: ...s restored 3 8 Firmware update Before updating the firmware you should first make a backup of the configuration and save the license as a file To update click Master in the Firmware update category on the central administration page Specify the location of the firmware file press Transfer and follow the instructions on the screen Version 2 01 Page 20 47 01 09 2020 ...
Страница 21: ... of the specified resource files is recommended 4 1 List of available applications SC443150EC_01 There are 150 room control unit objects available each with 8 freely configurable push button sensors for lighting sunblinds and windows a climate control unit and scene control for 16 scenes 4 2 SC443150EC_01 web room control unit 4 2 1 SC443150EC_01 software files Software files Web room control unit...
Страница 22: ...T_config nviFilePos SNVT_file_pos nvoFileStat SNVT_file_status nviFileReq SNVT_file_req UFPTwebOperationPanel UFPT 23203 Scene Panel SCC Command Module Switch 8x nviValueFb changeable NV type nvoValue changeable NV type nviEnergyHoldOff SNVT_switch nvoSetptOffset SNVT_temp_p nviSpaceTemp SNVT_temp_p nvoOccupancy SNVT_occupancy SCPTnvType SCPT 254 structure SCPTmaxNVLength SCPT 255 unsigned short n...
Страница 23: ...FilePos controls the read write position in files and the length of the next data transfer Type SNVT_file_pos Receiving inspection not available Version 2 01 Page 23 47 01 09 2020 UFPTnodeObject UFPT 0 nviRequest SNVT_obj_request nvoStatus SNVT_obj_status nvoFileDirectory SNVT_address nvoAlarm SNVT_alarm_2 nviConfig UNVT_config nvoConfig UNVT_config SCPTdevMajVer SCPT 165 unsigned short SCPTdevMin...
Страница 24: ... Type SNVT_address Transmission during file transfer or by polling nvoAlarm transmits alarms for device and function blocks Type UNVT_alarm2 Transmission on change in value nvoConfig communication interface for plug ins Type UNVT_config Transmission on request via nviConfig nvoFileStat returns status of the last file request via nviFileReq Type SNVT_file_status Transmission during file transfer or...
Страница 25: ... 0 0 0 0 0 0 0 0 0 0 Function description The NodeObject is used to manage all function objects of the device It enables status requests and provides error messages for the device and its objects Device management Various requests and commands can be sent to the device and its function objects via the network variable nviRequest The availability of the commands for the individual function objects ...
Страница 26: ...eObject has the number 1 Status mask Send a telegram to the network variable nviRequest to query all supported status messages of the device or a specific object nviRequest Meaning RQ_REPORT_MASK 0 determine status mask of the device RQ_REPORT_MASK i determine the status mask of the i th function object on the device first object after the NodeObject has the number 1 In the status mask all status ...
Страница 27: ...PTsourceInfo UCPT 6 enumerated UCPTenableLightMem UCPT 101 boolean UCPTbuttonEvent 6 UCPT 102 enumerated UCPToperatingLocation UCPT 88 unsigned char 16 UCPTstptRange UCPT 91 structure UCPTfanLevels UCPT 92 unsigned short UCPTfreshAirCmdOn UCPT 18 SNVT_lev_cont UPCThvacMode 4 UCPT 99 enumerated UCPToccCmds UCPT 90 structure UCPTenableFreshAir UCPT 51 boolean UCPTenableFan UCPT 93 boolean UCPTenable...
Страница 28: ...ion 2 01 Page 28 47 01 09 2020 UFPTwebOperationPanel UFPT 23203 Switch 8x nviValueFb changeable NV type nvoValue changeable NV type SCPTnvType SCPT 254 structure SCPTmaxNVLength SCPT 255 unsigned short UCPTswitchUse UCPT 97 enumerated SCPTstepValue SCPT 92 SNVT_lev_cont UCPTslatAngleStep UCPT 25 SNVT_angle_deg UCPTenableAuto UCPT 98 boolean UCPTswitchOnValue UCPT 21 SNVT_switch UCPTminOut UCPT 26 ...
Страница 29: ...g values switching dimming sun protection control output of movement commands blinds shutters windows Type adjustable Presetting SNVT_setting Preallocation AUS 0 0 0 0 00 Transmission Once when operating a button Configuration parameter Parameterization of network variables SCPTnvType type of the respective network variable Type structure SCPT 254 Preallocation SNVT_setting 0 0 0 0 0 0 0 0 0 117 N...
Страница 30: ...pe SNVT_lev_cont UCPT 92 Value range 0 5 100 0 Preallocation 5 10 UCPTslatAngle Step step angle for slat adjustment Type SNVT_angle_deg UCPT 3 Value range 90 90 Preallocation 10 500 UCPTswitchOn Value value at switch on Type SNVT_switch UCPT 21 Value range SNVT_switch Preallocation On with 100 200 1 UCPTminOut smallest value that may be sent Type SNVT_lev_cont UCPT 26 Value range 0 0 100 0 Preallo...
Страница 31: ... 1 ON switch on 2 DOWN dim down 3 UP dim up 4 STOP stop 5 SB_DOWN drive down 6 SB_UP drive up 7 SLAT_DOWN slat angle down 8 SLAT_UP slat angle up 9 TOGGLE toggle 14 NO_MSG no action Preallocation no event 14 Parameter usage The following table shows which of the configuration parameters described in the previous section must be set for the respective adjustment module type Parameter SCPTmaxOut UCP...
Страница 32: ...ty In UCPTbuttonEvent it can be specified for up to 6 buttons which function should be triggered when they are operated The functions listed below are available for selection EV_ Function Value on nvoValue NUL send invalid The object sends an invalid command e g to cancel priority commands Only possible if activated in UCPTenableAuto SNVTswitch 0 1 SNVTsetting SET_NUL 0 0 OFF switch off The object...
Страница 33: ...for sun protection devices and windows SNVTsetting SET_UP 100 0 SLAT_DOWN Slats down The object sends a slat turn command by SA UCPTslatAngleStep for adjusting sun protection devices SNVTsetting SET_DOWN 0 SA SLAT_UP Slats Up The object sends a slat turn command by SA UCPTslatAngleStep for adjusting sun protection devices SNVTsetting SET_UP 0 SA TOGGLE toggle The object alternately sends a switch ...
Страница 34: ... char 16 UCPTstptRange UCPT 91 structure UCPTfanLevels UCPT 92 unsigned short UCPTfreshAirCmdOn UCPT 18 SNVT_lev_cont UPCThvacMode 4 UCPT 99 enumerated UCPToccCmds UCPT 90 structure UCPTenableFreshAir UCPT 51 boolean UCPTenableFan UCPT 93 boolean UCPTenableOcc UCPT 94 boolean UCPTenableHvacMode UCPT 103 boolean SCC Command Module nviEnergyHoldOff SNVT_switch nvoSetptOffset SNVT_temp_p nviSpaceTemp...
Страница 35: ...ection OC_NUL Comf OC_OCCUPIED Comf ext OC_BYPASS Standby OC_STANDBY Econ OC_UNOCCUPIED Preallocation Build Protection OC_NUL Special feature polled nviEnergyHld Off input for locking the heating cooling function e g when opening windows Type SNVT_switch Value range state with the following meaning 0 Normal operation 1 Heating cooling interrupted Preallocation Normal operation 0 0 0 Special featur...
Страница 36: ...ht cooling 6 OFF Off 8 EMERG_HEAT Emergency heat Preallocation HVAC_NUL 0 00 0 00 0 00 0 00 0 00 0 Special feature polled nviSetpt OffsetFb input for local setpoint shift Type SNVT_temp_p Value range 10 00 10 00 C Preallocation 0 00 C 0 Special feature polled nviSpaceTemp room temperature Type SNVT_temp_p Value range 0 00 60 00 C Preallocation 327 67 C 32767 invalid value Special feature polled nv...
Страница 37: ...Preallocation 0 00 C 0 Special feature polled nvoSetpt Offset local setpoint adjustment Type SNVT_temp_p Value range 10 00 10 00 C Preallocation 0 00 C 0 Transmission once for button click nvoSccSync for output of the controller statuses for synchronisation with other room climate control units Type structure UNVT_scc_sync Transmission once for button click Configuration parameter UCPToperating Lo...
Страница 38: ...anges Type structure UCPT 90 Value range cmd_on SNVT_occupancy cmd_off SNVT_occupancy Preallocation occupied unoccupied 0 1 UCPTenable FreshAir indicates whether the supply air request is permitted Type boolean UCPT 51 Value range 0 BOOL_FALSE 1 BOOL_TRUE Preallocation permitted 1 UCPTenableFan indicates whether fan speed control is permitted Type boolean UCPT 93 Value range 0 BOOL_FALSE 1 BOOL_TR...
Страница 39: ...cribed in the previous section must be set for the respective adjustment module Parameter UCPTstptRange UCPTenableHvacMode UCPThvacMode 4 UCPToccCmds UCPTenableOcc UCPTenableFan UCPTfanLevels UCPTenableFreshAir UCPTfreshAirCmdOn Operating module Room temperature x x x Energy level x x Fan control x x x x Operating module Room temperature The room temperature operating module offers functions for b...
Страница 40: ...ontroller function can only be set if the function in UCPTenableHvacMode is enabled It is only possible to switch between controller functions that are entered in UCPThvacMode The output is done via the nvoSccSync heat_cool Setpoint In principle setpoints can be specified in 2 different ways relative to a setpoint parameterised in the room climate controller or absolute If the standard variables n...
Страница 41: ...on status can be recognised and thus displayed via nviUnitStatus in_alarm bit1 and nviSccSync in_alarm bit1 Operating module energy level The energy level operating module is used to record display and set the energy level for the room climate controller It can also be used for manual log on and log off Value Function used interface components energy level registration and display nviEffectOcc set...
Страница 42: ...nc damper_output setting Parametrization UCPTenableFreshAir UCPTfreshAirOnCmd Output nvoSccSync damper_output Fan The fan is displayed and adjusted in stages with evaluation of the UCPTfan levels The values recorded from nviUnitStatus fan_output and nviSccSync fan_output are evaluated for display If the setting of the fan level in the parameter UCPTenableFan is enabled it can be increased or decre...
Страница 43: ...ll up or learn external scene Type SNVT_scene Value range SNVT_scene function with 0 SC_RECALL calling up a scene 1 SC_LEARN learning the scene Preallocation SC_RECALL 0 Transmission once for button click Version 2 01 Page 43 47 01 09 2020 UFPTwebOperationPanel UFPT 23203 Scene Panel UCPTscButtonConfig scBtCount UCPT 45 structure UCPTscButtonCount UCPT 12 unsigned short UCPTscDesc scBtCount UCPT 8...
Страница 44: ... no fixed allocation 0 BOOL_FALSE UCPTsource Info for future use Type enumerated UCPT 6 Value range depending on function Preallocation no information 0 Functional description Scene control is used to operate scenes in the room via up to 16 scene button operating modules Scene identification The parameter UCPTscDesc is used to create a plain text for each scene that is displayed in the web configu...
Страница 45: ...less telecommunications DIN Deutsches Institut für Normungen e V German Institute for Standardization D Sub 9pole design of a connector system for data connections EN European Norm EnOcean supplier for battery free wireless sensor technology ERK smoke extraction damper FSDA Fire Smoke Damper Actuator FTT free topologie transceiver functional object functional component of a device application Grou...
Страница 46: ...able PDA personal digital assistent Plug in tool to configure commission and log components of applications Ressource Files files including definitions of interface components which can be used from network management tools to display and interpret the data properly RS232 standard for serial interfaces SCPT standard configuration property type SELV safety extra low voltage SNVT standard network va...
Страница 47: ...ation for wireless transmitters based on EnOcean technology UCPT user configuration property type UNVT user network variable type VDE VDE Verband der Elektrotechnik Elektronik und Informationstechnik e V Association for Electrical Electronic Information Technologies Version 2 01 Page 47 47 01 09 2020 ...