![spega 421 404 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/spega/421-404/421-404_technical-manual_1346187026.webp)
Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
SCPTmaxRcv
Time
Maximum time for
receiving values on
nviDriveValue to detect
absence, if absence is
detected the damper
will be driven in safety
position and return
state 'comm_failure'
Type:
SNVT_time_sec
Range of values:
0 ... 6553,4 Seconds
0 no heartbeat
control
Presetting:
no heartbeat control {0}
SCPTmaxSend
Time
Maximum period of
time between sending
two telegrams, used for
nvoDrivePos and
nvoFire
Type:
SNVT_time_sec
Range of values:
0 ...6553,4 Seconds
0 no periodic re-sent
Presetting:
no periodic re-sent {0}
UCPTdrvBreak
Mode
Interruption mode for
active maintenance
Type:
Enumeration
Range of values:
-1
DBM_NUL
no interrupts
0
DBM_ON_FIRE
maintenens
ends at safety
requests with
failure
'fail_self_test'
1
DBM_ON_DRIVE
maintenens
ends at each
drive request
with fail.
'fail_self_test'
Presetting:
no interrupts {-1}
Function description
Depending on the connected damper type, a number of functions such as
position detection, runtime monitoring, channel monitoring, maintenance
and others are available, which are described in more detail below.
Damper types
The fire damper object can be used for different damper types. These can be
classified according to the following 3 aspects:
Version 3.01
Page 26 / 39