![Speech Technology Center STC-H476 Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/speech-technology-center/stc-h476/stc-h476_operation-manual_1345115056.webp)
SIZE
DWG NO.
TYPE
B
SHEET
TITLE
ISSUE
DATE
OF
TOLERANCES
SCALE
APPROVED
CHECKED
DRAWN
DESIGN
MATERIAL
FINISH
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.
ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF
REVISIONS
LTR
DESCRIPTION
APPD
DATE
REV
X.X
0.04"
X.XX
0.02"
X.XXX
0.01"
[X]
1mm
[X.X]
0.5mm
[X.XX]
0.25mm
030-716-08
CUSTOMER CONNECTION
23" SHELF, 3.6kW CORDEX
PER P.O. and
Doc. 070-024-83
1 2
WH
J.U.
2004/05
2005/02
D2
c 2005 ARGUS TECHNOLOGIES
O
D
J.K.
2005/03
G.S.
2005/03
N.T.S.
REV BY
B
LIST 81 UPDATED
MP/JU 2005/10
C
CORRECTED VIEWS DESCRIPTION
MP
2005/10
WES
GS
CORRECTED VIEWS DESCRIPTION
UPDATED LIST 85 LABELS
D
SDW
L1
L2
L3
L3
L2
L1
LIST 83: DUAL 3-PHASE INPUTS, 208 - 240VAC
NO NEUTRAL
LIST 84 - DUAL 3-PHASE INPUTS, 360 - 480 VAC,
WYE SOURCE, NEUTRAL REQUIRED
L3
L2
L1
N
N
N
D
L1
L2
L3
N
N
N
CONNECT NEUTRAL TO ANY
ONE OF THE THREE
TERMINAL BLOCK POSITIONS
LABELED 'N'
SWITCH SETTING FOR CAN TERMINATION
CAN
TERMINATED
CAN
UNTERMINATED
AC WIREWAY, BOTH SIDES,
1.3 [34] HOLE FOR CUSTOMER
SUPPLIED 1" CONDUIT FITTING
PROTECTIVE EARTH
TERMINAL - 2 PLACES
AC WIREWAY
BLANK PLATE
SEE DETAIL 'A'
DETAIL 'A' - AC INPUT OPTIONS
REAR VIEW - AC REAR COVER REMOVED
L1
L2/N
L1
L2/N
L1
L2/N
J8
J7
CAN OUT RJ12 OFFSET
PIN OUT (J8)
CAN IN RJ12 OFFSET
PIN OUT (J7)
GND
1.
CAN H
2.
NOT CONNECTED
3.
CAN L
4.
NOT CONNECTED
5.
NOT CONNECTED
6.
GND
1.
CAN H
2.
NOT CONNECTED
3.
CAN L
4.
NOT CONNECTED
5.
NOT CONNECTED
6.
LIST 85 - SINGLE PHASE INPUTS, 208V - 277VAC
L1
L2/N
L1
L2/N
L1
L2/N