Product Overview
30
SharpEye™
Ultra Fast UV/IR Flame Detector User Guide
2.4.7
Auxiliary Relay as End-of-Line
The auxiliary relay can be used as End-of-Line in models with suffix
–
4XXXX and
5XXXX only. In this case, the auxiliary relay is active as long as the detector is
powered.
2.5
Internal Detector Tests
The detector performs 2 types of self-tests:
•
•
2.5.1
Continuous Feature Test
During normal operation, the detector tests itself continuously and indicates a
fault if a failure is found. This type of test complies with SIL-2 requirements.
The detector continuously tests:
•
Input voltage level
•
All internal regulator voltage levels
•
Voltage level status of sensor and sensor circuitry for noise or disconnection
in the electronic circuitry
•
0
–
20mA level output
•
Relays and heater operation
•
Processor watchdog
•
Software
•
Memory
•
Oscillator frequency
2.5.2
Response to Fault Indication
If a failure is found, the detector indicates by:
•
Fault relay:
•
Opens in wiring options 1, 2, and 4
•
Closes in wiring options 3 and 5
•
0
–
20mA: indicates fault (0mA or 2mA) in wiring options 1, 2, and 3
•
LED
–
Yellow flashes (4Hz)
•
Correcting the fault
The fault indications remain until the detector’s power is removed. The fault
indications return if the fault is still found when power is restored.