General Instructions for Electrical Wiring
67
B
Wiring Instructions
➣
In this appendix…
General Instructions for Electrical Wiring
page 67
page 69
B.1
General Instructions for Electrical Wiring
Follow the instructions detailed in this section for determining the correct
wire gauge to be used for the installation.
1
Use Table 25 to determine the required wire gauge/size for general
wiring, such as relay wiring. Calculate the permitted voltage drop with
respect to load current, wire gauge, and length of wires.
Table 25: Maximum DC Resistance at 68°F/20ºC for Copper Wire
AWG #
mm
2
Ohm per 100ft
Ohm per 100m
26
0.12
–
0.15
4.32
14.15
24
0.16
–
0.24
3.42
11.22
22
0.30
–
0.38
1.71
5.60
20
0.51
–
0.61
1.07
3.50
18
0.81
–
0.96
0.67
2.20
16
1.22
–
1.43
0.43
1.40
14
1.94
–
2.28
0.27
0.88
12
3.09
–
3.40
0.17
0.55
10
4.56
–
6.64
0.11
0.35
2
Use Table 26 to select wire gauge for power supply wires. DO NOT
connect any circuit or load to detectors’ supply inputs.
Select
Number of detectors
connected in 1 circuit.
Select wiring
Length
per your installation requirements.
Refer to
Power Supply Range
for voltage extreme applied.
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......