Recommended action
Ensure the detector window and reflector mirror are clean.
Potential cause
Faulty detector.
Recommended action
Re-power the detector.
6.4
Light-emitting diode (LED) constantly red,
alarm relay energized, 0-20 mA indicates alarm
Potential cause
Existing alarm condition.
Recommended action
Check cause of alarm.
Potential cause
Alarm latched.
Recommended action
Ensure the alarm latch is not enabled in the detector settings.
Potential cause
Faulty detector.
Recommended action
Re-power the detector.
6.5
No HART
®
communication, 0-20 mA shows 0
mA
Potential
No HART is available at 0 mA level.
Recommended action
For Fault mode, the default indication is 1 mA. Configure this to 0 mA.
Emerson does not recommend this when using a HART connection in order to
preserve the HART communication.
Troubleshooting
Reference Manual
December 2021
00909-0100-4975
32
Spectrex.net
Содержание SharpEye 40/40C Series
Страница 4: ...4 ...
Страница 10: ...Introduction Reference Manual December 2021 00909 0100 4975 10 Spectrex net ...
Страница 24: ...Installation Reference Manual December 2021 00909 0100 4975 24 Spectrex net ...
Страница 30: ...Maintenance Reference Manual December 2021 00909 0100 4975 30 Spectrex net ...
Страница 40: ...Specifications Reference Manual December 2021 00909 0100 4975 40 Spectrex net ...
Страница 42: ...Reference data Reference Manual December 2021 00909 0100 4975 42 Spectrex net ...
Страница 46: ...FM fuel test responses Reference Manual December 2021 00909 0100 4975 46 Spectrex net ...
Страница 49: ...Reference Manual 00909 0100 4975 December 2021 SharpEye 40 40 49 ...