Specifications
TM40/40L Rev. (Ag), February 2019
57
Appendix A:
Specifications
A.1
Technical Specifications
Spectral Response
40/40L-LB
UV:0.185
–
0.260µm IR:2.5
–
3.0µm
40/40L4-L4B UV:0.185
–
0.260µm IR:4.4
–
4.6µm
40/40L-LB
Detection Range
(at highest sensitivity
setting for 1ft
2
/0.1m
2
pan fire)
Fuel
ft/m
Fuel
ft/m
Gasoline
50/15 Hydrogen
*
33/10
n-Heptane
50/15 Methane
*
26/8
LPG*
43/13 Ethanol 95%
25/7.5
JP5
37/11 IPA
25/7.5
Kerosene
37/11 Methanol
25/7.5
Diesel Fuel
37/11 Paper
16/5
Polypropylene 33/10
30”/0.75m high, 10"/0.25m width plume fire
40/40L4-L4B
Detection Range
(at highest sensitivity
setting for 1ft
2
/0.1m
2
pan fire)
Fuel
ft/m
Fuel
ft/m
Gasoline
93/28 Polypropylene
60/18
n-Heptane
93/28 LPG*
60/18
IPA
70/21 Methane*
60/18
JP5
70/21 Ethanol 95%
57/17
Kerosene
70/21 Methanol
57/17
Diesel Fuel
70/21 Paper
33/10
*
30”/0.75m high, 10"/0.25m width plume fire
Response Time
Typically 5 seconds
Adjustable Time
Delay
Up to 30 seconds
Sensitivity Ranges
•
1ft2/0.1m2 n-heptane pan fire from 50ft/15m for
models 40/40L-LB
•
1ft2/0.1m2 n-heptane pan fire from 93ft/28m for
models 40/40L4-L4B
Fields of View
Horizontal 100
, Vertical 95
Built-In-Test (BIT)
Automatic (and Manual)