![Spectrex SharpEye 20/20U Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/spectrex/sharpeye-20-20u/sharpeye-20-20u_user-and-maintenance-manual_1344030019.webp)
Spectrex Inc. - SharpEye™ UV Flame Detector Manual – TM 20/20UB Rev. E, August 2004
11
Optional Latching (default is non-latching):
The detector includes a latched alarm output capability, which operates
according to the DIP -switch SW1-1 position. Upon the detection of a fire, the
detection signal is latched until manually reset (disconnecting the power supply
or upon performing a manual BIT). Latching affects the Alarm Relay, 4 -20mA
output, Alarm LED, (the ACCESSORY RELAY will latch only when SW1-4 at
OFF position).
Built-in Test Options
(refer to 2.5):
Successful Manual BIT activates the following outputs according to SW1
switches:
SW1-6 ON:
The Alarm relay will be activated for 3
seconds. The 4-20mA output will provide
20mA for 3 seconds.
SW1-7 ON & SW1-6 ON:
The Accessory & Alarm relays will be activated
for 3 seconds. The 4-20mA output will provide
20mA for 3 seconds.
SW1-7 ON & SW1-6 OFF:
The Alarm relay will be activated for 3
seconds. The 4-20mA output will provide
16mA for 3 seconds.
ACCESSORY RELAY AS EOL:
If SW1-8 is ON then the Accessory Relay is
used as End of Line (EOL) relay. In this case
the accessory relay is always active as long as
the detector is powered.
Содержание SharpEye 20/20U
Страница 2: ......
Страница 4: ......
Страница 8: ...Spectrex Inc SharpEye UV Flame Detector Manual TM 20 20UB Rev E August 2004 IV ...
Страница 44: ...Spectrex Inc SharpEye UV Flame Detector Manual TM 20 20UB Rev E August 2004 36 ...
Страница 46: ...Spectrex Inc SharpEye UV Flame Detector Manual TM 20 20UB Rev E August 2004 38 ...
Страница 48: ...Spectrex Inc SharpEye UV Flame Detector Manual TM 20 20UB Rev E August 2004 40 ...