Mounting for Duct Installation
TM794200
Rev Ad, March 2019
49
5.4.6
Conduit/Cable Installation
•
To avoid water condensation in the detector, it should be installed with
the conduits/electrical entries facing downward.
•
When using the swivel mount or duct mount, use flexible conduits for
the last portion connecting to the detector.
•
When pulling the cables through the conduits, ensure that they are not
tangled or stressed. Extend the cables about 12”/30cm bey
ond the
detector location to accommodate wiring after installation.
•
After the conductor cables have been pulled through the conduits,
perform a continuity test.
5.4.7
Harness Connection
➢
To prepare the harness connection (see Figure 11):
1
Remove the 4 threaded plugs (13) from detector front.
2
Release the 4 socket-head screws (14) that secure the detector
housing (1) to its back cover (2) using no. 5 hex key for M6 screw.
3
Hold the housing during the removal of the screws.
4
Pull the detector housing from its cover.
The cover remains attached to the detector swivel mount. The housing
slides under the cover and remains attached to it by a securing cable
(8). Do not let the cover simply drop but rather support it until it
hangs.
The terminal board (12) inside the detector cover is now revealed.
5
Remove the protective plug (6) mounted on the detector conduit inlet.
6
Pull the wires through the detector cover (2) and secure them firmly to
the cover using the cable-tie (16) attached to it.
Use a 3/4”
-14NPT explosion-proof conduit/electrical entry connection
to assemble the conduit/cable to the detector.
7
Connect the wires to the required terminals (12) according to the
wiring diagram (see Appendix B).
8
Connect a grounding cable to the ground terminal (7) outside the
detector cover (2). The detector must be well grounded to earth
ground for proper operation.
9
Verify the wiring. Improper wiring may damage the detector.
10
Check the wires for secure mechanical connections and press them
neatly against the terminal board (12) to prevent them from
interfering while closing the detector housing.
11
Dress all wires so they will not interfere with the closure of the unit.
12
Seal the conduit inlet and outlet.
Содержание SafEye 300 Series
Страница 2: ......
Страница 10: ......
Страница 32: ......
Страница 58: ......
Страница 64: ......
Страница 67: ...TM794200 Rev Ad March 2019 67 Appendix B Wiring Option Configurations Figure 13 Detector Wiring Diagram ...
Страница 70: ......
Страница 71: ...TM794200 Rev Ad March 2019 71 Appendix C Outline Drawings ...
Страница 72: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 78: ......
Страница 79: ......