background image

INSTALLING IN WALL OPENINGS USING SEALANT

(NO WALL PLATES) 

IMPORTANT NOTE:  This installation applies to the use of SINGLE devices only.

Installing Around Previously Installed Cables

1.

Remove lid from raceway by unscrewing the two screws and sliding lid out of channel attachment tabs (on opposite side).

2.

Place raceway channel around cables (See Fig. 6).

3.

Replace lid and reinstall screws. Continue to install per the following steps for New Cable Installation.

Installing Prior to Installation of Cabling

1.

With fastening screw removed, install optional Positioning Clamp (Cat No. EZP133PC) around cable bundle and slide 
over raceway making sure that the flat feet of clamp are facing towards wall surface.  Use gauge marks located on raceway
to adjust clamp to thickness of wall.  When properly adjusted, lock clamp in place by installing and tightening fastening screw.

2.

Slide device into properly sized opening and center within wall (See Fig. 7).

3.

Moving to opposite side of wall, install second clamp around raceway and snug tightly to wall.  Tighten clamp securely.

4.

Caulk using approved sealant (SpecSeal

®

SSS, LCI, LC Series sealants, or Pensil

®

300 Silicone Sealant).  Apply 

sealant to a depth of 5/8” within annulus on both sides of wall.   Apply a 3/8” crown bead at areas of point contact. 

INSTALLING or PULLING CABLES

A resilient liner provides an adjustable seal within the raceway.  Liner must be protected from damage while adding or removing
cables.    Wrap  cable  ends  with  a  suitable  low  friction  tape  before  inserting  into  the  raceway. This  device  is  designed  to  be  fully
functional at all cable loadings from completely empty to visually filled and cables should easily slide through the raceway using
minimal  effort.  IF  RESISTANCE  IS  ENCOUNTERED,  DO  NOT FORCE  CABLES  OR  CABLE  BUNDLES  THROUGH  THE
RACEWAY. DAMAGE MAY RESULT. Upper curved liner may be depressed if necessary when inserting cables using a flat, smooth
implement and removing after cables are installed.

GROUNDING

At the option of the installer, this device may be grounded.  After device(s) has been installed, insert ground
screws where indicated (See Fig. 8).  For installations using single, double, or triple wall plates, or optional
positioning clamps, two ground screws are required and are included in these kits.  

WALL LABELING

Wall labels are provided with the wireway as well as wall plate kits. Larger orange colored label is intended to be used to identify
the wireway’s installer as well as to provide applicable UL System information.  Smaller secondary labels are included with double
and triple wall plates as an optional method for identifying or marking cable types, uses, or trades. Two sets of labels are provided
for marking both sides of wall.  

MAINTENANCE

No maintenance of the raceway is normally required.  Interior of device should be inspected before and after any modifications to
cable bundle.  If any damage to intumescent pads lining top and bottom of the raceway is found, contact the factory to determine
if replacement is required.

Page 2 of 2

Installation Sheet  • 

EZ PATH

ZIS1003

01/03

Important Notice:

All statements, technical information, and recommendations contained herein are based upon testing believed to be reli

able, but the accuracy and completeness thereof is not guaranteed.

WARRANTY:

Specified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within

one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price.

Limitations and Exclusions:

THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING

THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL SPECIFIED
TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES.  PRIOR TO
USE, THE USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER ASSUMES ALL
RISKS AND LIABILITY FOR SUBSEQUENT USE.  No statement or recommendation not contained herein shall have any force or effect unless
in an agreement signed by officers of seller and manufacturer.

MADE IN THE USA – COPYRIGHT © 2002 SPECIFIED TECHNOLOGIES, INC.

 

 

     

 

 

 

 

     

 

 

 

 

 

 

 

  

TABLE B: Required Components

Fig. 6

Fig. 7

6.

Install remaining wall plate around raceway (TOP up) and slide it toward wall surface. While pulling raceway
toward you, push wall plate and gasket tightly to wall and tighten set screws. Check device for excessive play.
If device appears to be loose or can easily be moved, readjust wall plates as necessary to tighten device 
firmly against wall.

New Cable Installations Using 

Wall Plates

Single Raceway (Complete Kit)

(1) EZDP33FW

Single Raceway

N/A

(1) EZD33FW (1) EZP133W

N/A

Double Raceway

N/A

(2) EZD33FW (1) EZP233W

N/A

Triple Raceway

N/A

(3) EZD33FW (1) EZP333W

N/A

New/Existing Cable

Installations Using Sealant

Single Raceway

N/A

(1) EZD33FW

N/A

(1) EZP133PC

All Components

Included

Raceway

Wall Plate Kits

Positioning

Clamp Kit

Fig. 8

Отзывы: