SPECAVTOMATIKA DOKA Скачать руководство пользователя страница 2

Option 1

:

 

Application of one "DOKA - a" detector as an independent smoke 

detection and fire warning device.

Option 2

:

 

The detectors are grouped (AFA system) by a two-wire line. One of 

the detectors switches to the "Fire" state and generates the "Fire Alert" signal for the 

other detectors. These detectors switch to the "Alert" state. The maximum number 

of "DOKA - a" detectors in the AFA system is 40.

Option  3

:

 

Install  one  "DOKA-a"  detector  and  any  siren  with  its  own  power 

source.  "DOKA  -  a"  switches  to  the  "Fire"  state  and  closes  with  the  built-in  relay 

"Fire"  minus  wire  of  the  siren  power  supply  circuit.  The  siren  must  operate  at  a 

voltage of no more than 24 V and consume no more than 300 mA DC.

Option 4: 

 

The "DOKA-a" detector is connected to a normally open loop of any 

automation (ACU, Smart Home system, GSM alarm system, etc.), which performs 

the function of fire alert. "DOKA - a" switches to "Fire" and closes a normally open 

loop.  Upon  a  signal  from  the  loop,  the  automatics  will  execute  a  fire  alert.  The 

voltage in the loop must not exceed 24 V.

You can combine options 2, 3, 4 in any combination. The siren and/or ACU can 

be connected to any of the detectors in the AFA system. 

 

!

  

When connecting, observe the polarity according to the diagrams below.

˗

ACU

5.2. 

Options for use

To connect, disconnect the multi-connector as shown in the figure. Connect the 

wires as shown in the diagram with a screwdriver.

After connecting insert the multi-connector into the base. Place the wires under the clips.

5.4. 

Functionality test

Press and hold the "Test" button until the detector enters the "Fire" state. Then release 

the button. If you apply "DOKA - a" in options 2, 3, 4 (or any combination of these), make 

sure that all the selected fire alarm modes are executed. After releasing the "Test" button, 

the detector will return to the "Standby Mode" after a while.

6. 

TRANSPORTATION AND STORAGE

џ

 

The detectors must be transported in a packed form by any type of transport in 

accordance with the rules for the carriage of goods in force for this type of 

transport.

џ

 

Packed detectors during loading and unloading operations and transportation 

must not be exposed to sharp shocks and precipitation.  

џ

 

The method of laying and fixing of detectors on the vehicle must exclude their 

movement. 

 

џ

 

Transportation conditions must comply with storage conditions 5 in accordance with GOST 15150.

 

џ

 

The detectors must be stored in packages in a heated and ventilated storage areas on 

the racks at temperatures from +5 °C to +40 °C and relative humidity of not more 

than 80% at 25 °C (storage conditions 1 in accordance with GOST 15150).

  

7. 

MANUFACTURER WARRANTY

џ

 

The manufacturer guarantees the compliance of the detectors with the 

requirements of technical specifications, provided that the consumer meets the 

conditions of transportation, storage, installation and operation.

 

џ

 

The warranty operation period is 24 months from the date of putting the detector into 

operation. The warranty storage period is 12 months from the date of manufacture, provided 

that the conditions of Section 6 are met.

џ

 

Detectors found to be in non-compliance with the requirements of technical 

conditions during the warranty period shall be restored at the manufacturer's expense.

 

џ

 

Warranties apply to detectors that have no traces of mechanical impact 

and the warranty seal has not been damaged.

8. 

DISPOSAL CONSIDERATIONS

At the end of its service life, the detector is disposed of in accordance with the 

applicable nature protection legislation.

      

The detector contains no precious metals.

9. 

MAINTENANCE

џ

 

Maintenance of the detector during operation consists of cleaning the detector 

components and checking their functionality.

џ

 

It is recommended to check the functionality of the detector approximately once 

a month by triggering the detector with the "Test" button.

џ

 

In the event of false alarms, an unscheduled dust cleaning of the detector must 

be carried out or it must be handed over for repair. 

џ

 

If the detector generates a "Battery Discharge" sound signal, the detector must 

be disconnected from the base, the battery replaced and the functionality checked.

Sensing chamber cleaning

џ

 

Try to blow through the smoke inlet openings for 1 minute with compressed air 

on all sides (0.5 ... 3 kg/cm²).

џ

 

If this does not result in positive results, clean the sensing chamber by 

disassembling the detector according to instructions on www.dokasensors.by.

  

!

 

After the maintenance and/or removal/installation of the detector, perform its testing. 

 

!

 

When carrying out maintenance work, it must be ensured that the detectors are 

protected from construction materials and dust.

max 3.5 mm

 

12. 

CERTIFICATE OF ACCEPTANCE

       

Autonomous fire smoke detector IP 212-03K "DOKA - a" factory No. 

_________________, No. _________________,

N

o

.

_________________, 

N

o

.

_________________, complies with technical 

specifications of

 

 TU BY 100016872.097-20

20

 and deemed suitable for operation.

       

Incoming and technical control was conducted:

13. 

CONTACTS

MANUFACTURER'S ADDRESS

OJSC "ZAVOD SPECAVTOMATIKA"     

TECHNICAL SUPPORT  

+375 (29) 198-08-04
+375 (44) 549-88-49
[email protected]
www.dokasensors.by

Republic of Belarus            

220024, Minsk, Stebeneva Str., 12    

Tel./Fax +375 (17) 378-61-49

www.specavtomatika.by      

e-mail: [email protected]

SALES DEPARTMENT

+375 (17) 378-80-16
+375 (17) 325-64-15 (

Fax

)

+375 (29) 650-02-97

 

[email protected]

AFA

NO

Com

1

2

3

4

signal 

"Fire 

Alert"

 

NO

Com

1

2

3

4

AFA

˗

Siren power supply source  

АПС

    

relay "Fire"

NO

Com

1

2

3

4

5.3. 

Wire installation

After selecting any of "DOKA-a" applications (except for Option 1), carry out the 

wiring installation taking into account the wiring diagram and design of the detector.

Cables and wires of any type and brand with a maximum core cross-sectional area of 

1.5 mm² are permitted. Leave the required stock of wires for connection.

 

5.4. 

Base installation

Depending on how the cable is installed, select the holes in the base for the wires 

as shown in the drawings and attach them to the installation site. Mark the location 

of  any  two  opposite  fixing  holes.  Prepare  the  holes  and  fasten  the  base  to  a  flat 

surface (due to the curvature of the surface, the base may be skewed, which may lead 

to impossible connections of the detector to the base).

surface-mounted wiring 

 

break in the blanking 

cover

 

concealed wiring (for 

false ceiling) 

5 .. 7 

mm

 

remove the 

insulation

 

relay "Fire"

10.

Characteristic

 

TECHNICAL SPECIFICATIONS

 

Unit

 

Value

0.05-0.20

Supply voltage

V

 

7,6

 

 

9,9

Current strength of the detector in standby mode

(between smoke analysis cycles)

µA

 

 

25

 

Dimensions (length/width/height)  

mm

 

90x90x45

 

Weight (without power supply element)  

kg

 

 

0.15

 

Operating temperature range

 

°С

 

-

 

10°С 

 

+ 55°С

 

Relative air humidity at + 40°C

 

%

 

95

 

Ingress protection rating

-

IP40

Average time between failures

                                               

hours

60 000

Average service life

                                                                

years 

10

Guaranteed operating time from battery

                

months 

severity 

grade

 

 

12

Resistance to electromagnetic interference

2

Power supply element

-

6F22 

Parameters of the switched circuit

V

 24

А

 0.3 

Sound signal volume in the "Fire" state

Detector sensitivity

 

dB

dB/m

 

85

 

Chief of QCD

______________________________

Stamp here (surname, date)

AFA

NO

Com

1

2

3

4

Test fire detection time for the 

detector, no more than, sec.

External  impact 

parameters

Slab

Wall

Tree smoldering (TP-2)

745

780

Open burning of synthetic material 

(polyurethane foam) (TP-4)

110

 

150

Cotton smoldering (TP-3)

280

290

125

105

Wood burning (TP-1)  

312

335

Open burning of liquid 

(n-heptane) (TP-5)

11. 

TEST FIRE DETECTION TIME

Отзывы: