III. INSTALLATION 

The SE-4000 comes complete with:

*NOTE: 

Where physically challenged people in wheel- 

chairs use this product it may be necessary to lower the  
installation height to between 32” and 34” for ease of use. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

READ THIS SECTION COMPLETELY BEFORE INSTALLING 

The following is a step-by-step sequence of how to 
install and maintain your Speakman SE-4000 
GRAVITYFLO™ Eyewash. 

FIG. 1 

Caution: The Eyewash SE-4000 weighs 
approximately 185 lbs. When filled with 21 gallons 
of water.

 

IMPORTANT: 

When fastening or mounting the SE-4000 

to a wall, make sure that the wall construction is suitable to 
hold a vertical load of 300 lbs. The SE-4000 comes 
complete with a tubular wall bracket and hardware to mount 
the bracket. The tubular bracket must be fastened securely  
to the wall studs as shown in Fig. No. 1. Where concrete or 
other composition wall constructions are involved, consult a 
building contractor for the correct fastening and mounting 
hardware to install the tubular wall bracket. Installation 
height for the SE-4000 should be 33” to 45” from floor to 
eyewash spray heads (to meet ANSI Z358.1). See Fig. No. 2. 

1. Clean inside of tank and flush system with clean 
    water. Rinse thoroughly. (For periodic cleaning and 
    maintenance see Section V of this manual.) 
 
2. Select a suitable location. Do not allow your 
    GRAVITYFLO™ product to freeze or become 
    overheated. We recommend the emergency 
    Eyewash unit be in an accessible location that  
    requires no more than 10 seconds to reach and  
    within a travel distance of no more than 100 ft. from 
    the hazard (to meet ANSI Z358.1). The area  
    around the Eyewash should be well-lighted. 

FIG. 2 

A clear area at each Eyewash station should be at 
least 48” by 48” and should allow either a forward or parallel 
approach by a person using a wheelchair. (See Fig. No. 3) 

3. Position tubular wall bracket as shown in Fig. No. 1 
    and secure with four (4) 1/4" lag screws provided. 
    When drilling into tile, masonry, concrete, or other 
    hard materials, wear safety goggles to prevent eye 
    injuries. 
 
4. Insert SE-4000 down into the tubular wall bracket as 
    shown in Fig. No. 2. Make sure that overhangs on  
    left and right hand side of plastic Eyewash 
    container rest securely on tubular side arms. 

NOTE: 

Tubular bracket can also be mounted flush to wall surface, 
providing adequate reinforcement and wall supports are installed. 
Spacer block not required when flush mount installation is chosen.

 

Отзывы: