Speakman EYESAVER SE-570 Скачать руководство пользователя страница 1

 

SPEAKMAN

®

 

400 Anchor Mill Rd.  New Castle, DE 19720       Phone: 800-537-2107       Fax: 800-977-2747

 

02/01/18           www.speakman.com          92-SE-570-01 

SPEAKMAN

® 

SE-570 

Installation, Operation & Maintenance Instructions 

EYESAVER® EYEWASH 

 

DESCRIPTION 

Deck mounted emergency eyewash. Supplied with a ¼ turn ceramic PERFECT® valve that is activated when 
the eyewash is rotated 90° over an open sink. Unit is supplied with an adjustable flow regulator. Aerated 
spray outlets with individual flow restrictor, and flip-off dust covers. Unit mounts on counter tops up to 
2-1/4” thick. 
 

SPECIFICATIONS 

SPRAY HEADS: (2) AERATED YELLOW ABS SPRAY OUTLET, SPRAY FACE, AND DUST COVERS 
VALVE: ¼ TURN CERAMIC PERFECT VALVE® 
FLOW REGULATOR: BRASS, CHROME-PLATED 
INLET: 1/2" NPT MALE 
SHIPPING WEIGHT: 6 LB 
EMERGENCY SIGN: 7-7/8” X 7-7/8” PLASTIC WALL SIGN 

 

Options: 

ILS 

In-Line Strainer 

LH  

Left-Hand Operation 

 

INSTALLATION 

NOTE: This unit should be connected to an uninterrupted 
source of potable water, with a minimum flowing pressure 
of 15 PSI and a maximum static pressure of 80 PSI. 

 

Review drawing (as shown on other side) to assure proper installation. At desired location, use the supplied 
deck plate to mark mounting holes. Drill the 1” diameter hole through the countertop (2-1/4” thick max.), and 
drill the 1/4” diameter hole a minimum of 5/16” deep. Be sure the holes are drilled as straight as possible. 
Place eyewash through drilled holes making sure the threaded shank & ¼” stop screw fit with no interference, 
and that the eyewash is resting flat on the deck plate. Attach eyewash to countertop using the supplied 
hardware. Install the supplied volume regulator (use thread sealant on all joints), making sure the adjustment 
screw is facing in a direction that is easily accessible for later adjustment. Connect a water supply to unit that 
is a 1/2” minimum uninterrupted source of potable water (use pipe sealant on connection). Failure to use 
potable water can result in emergency units producing impure or contaminated water causing possible 
further injury. 

 

OPERATION 

Be sure unit is above sink or drain before activating. The eyewash is activated by grasping the eyewash and 
rotating it 90° to the full open position. Once the unit is activated, water will discharge from the spray outlets 
until the eyewash is manually rotated back to the off position. 
 

TESTING PROGRAM 

The American National Standards Institute (ANSI) states that all safety emergency equipment shall be 
activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a 
testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspectors initials 
should be noted. 

 

 