Error Codes & Troubleshooting Problems

 

How to troubleshoot spa problems 

 

 
 
 
SV spa controllers feature self diagnostics and scrolling error messages to quickly 
troubleshoot possible problems. Should the spa control encounter a problem the error 
code / message will scroll across the topside panel screen until the problem is resolved. If 
an error condition is experienced all spa functions are shut down and the spa should not 
be used until the error condition has been resolved. A list of error codes with 
descriptions of problems and possible solutions is detailed below for your reference.  
 

  

 

IMPORTANT NOTE 

 

For most error codes mains power to the spa control must be turned 
OFF and then back ON before the error condition will be cleared. 

 

Heartbeat LED 

 
All SV model spa packs feature a red flashing heartbeat LED light. The heartbeat LED is 
located on the front right hand side of the spa pack itself (

installed underneath spa skirt). 

 

 
The heartbeat LED flashes to indicate the current health/status of the spa pack. When 
the spa pack is functioning correctly with no errors to report the heartbeat LED emits a 
single flash in a constant pulse much like a heartbeat (ON, OFF, ON, OFF). If the spa 
pack encounters a fault the heartbeat LED will begin flashing in sequence with the error 
code number being experienced (ie. ER2 = ON,ON;  OFF  ON,ON;  OFF). 
 
If the keypad display is ever blank a spa user can still determine the health / status of the 
SV controller by removing a panel from the spa skirt and checking the heartbeat LED on 
the front of the spa pack itself. 
 

 

ER-2  HEATER PLUG 

 

 

Problem: 

No heater sensor communication 

 
Cause:   

Internal heater sensor communication problem 

 
Solutions: 

Turn mains power OFF, wait 5 minutes then restart spa 

 

 

 

Contact spa reseller if problem is not resolved with power reset 

ER-3  WATER PRIME 

 

 

Problem: 

Water prime failed – air detected in heater tube 

 
Cause:    

Airlock in pipe work, low water level, dirty filter cartridges  

 
Solutions: 

Press Pump A button to retry water prime 

 

 

 

Check spa water level (refill if necessary) 

 

 

 

Remove filter cartridges and press Pump A button to retry prime 

 

Bleed airlock from pipe work by slightly loosening couplings on front of 
filtration pump 

 

Remove filter cartridges and flush water down pipe work with a hose  

 
 

ER-4  THERMAL TRIP   

 
Problem: 

Heater thermal trip activated. Heater has been active and has had 
insufficient water flow over the element. Low or no water flow has 
caused the heater temperature to exceed its maximum limits and the 
spa control has shut down operation to prevent any damage to the 
heater unit 

 
Cause:   

Low water level, airlock in pipe work, closed shut-off valves, dirty  

 

 

filter cartridges, filtration pump failed or operation intermittent  

 
Solutions: 

Turn mains power OFF and wait 10-15 minutes for element to cool  

 

 

and thermal cut-out device to reset. Then turn power back ON 

 

 

 

Check spa water level (refill if necessary) 

 

Remove filters and clean as per manufacturer’s recommendations or 
replace cartridges if required 

 

Check under spa cabinet to ensure all shut-off valves are in the OPEN 
position

 

 

Bleed airlock from pipe work by slightly loosening couplings on front of 
filtration pump or by removing filters and flushing water down pipe 
work with a hose.  

Содержание SV4

Страница 1: ......

Страница 2: ...ontroller will initiate a water priming sequence on start up During a priming sequence the filtration pump will run for up to 20 seconds at a time in an attempt to purge air from the plumbing The keypad display will scroll PRIMING during this sequence If the spa controller is successful in clearing all of the air from the heater tube the system will begin normal operation However if air is still d...

Страница 3: ...cking the heartbeat LED on the front of the spa pack itself ER 2 HEATER PLUG Problem No heater sensor communication Cause Internal heater sensor communication problem Solutions Turn mains power OFF wait 5 minutes then restart spa Contact spa reseller if problem is not resolved with power reset ER 3 WATER PRIME Problem Water prime failed air detected in heater tube Cause Airlock in pipe work low wa...

Страница 4: ...d Systematically unplug lights in pool temp sensor keypads and expansion port loads from spa pack one by one to identify faulty part Contact your spa reseller if problem persists ER 8 CTRL FAULT HVS Problem Heater relay is on when it should be off Cause Power surge periods of low or high voltage water on spa pack terminal block relay problem Solutions Turn mains power OFF and back ON again to see ...

Страница 5: ...at exchanger thermal cut out open IMPORTANT NOTE If a heat pump encounters an error the heat pump will remain disabled until the mains power to the SV spa controller is turned OFF and back ON again The heat pump warning message will continue to scroll every 60 seconds until the power is reset Maintenance Timers SERVICE REMINDER MESSAGES Certain spa manufacturers will choose to take advantage of th...

Страница 6: ...etails Spa Net Pty Ltd Unit 4 103 Railway Road North Mulgrave NSW 2756 Australia Phone 61 2 4587 7766 Fax 61 2 4587 8766 www spanet com au Technical Support Service service spanet com au Accounts Department accounts spanet com au Sales Department sales spanet com au ...