– 40 –
Inverter Air-to-Water Heat Pump
Parameter H (System Parameter)
H01
——Auto Start (Yes/NO)
When H01 = 0, the heat pump haven’t the auto restart function for regular ON-OFF. That is to say:
Every time the heat pump is connected to electricity, it is in power OFF status.
When H01 = 1, the heat pump has the auto restart function for regular ON-OFF. That is to say:
When the heat pump is connected to electricity, it will keep the power ON or OFF status before power failure.
H02
——Master/Slave Unit
H03
——Temperature Unit
H04
——4-way Valve Polarity On-Heating/Off-Heating
H06
——Frequency Control P Value
H07
——Frequency Control I Value
H08
——Frequency Control D Value
H09
——Min Frequency of compressor
H10
——Max Frequency of compressor
H11
——Type selection of compressor
H12
——Hand Drive Compressor Frequency
H13
——PFC Function Enable
H15
——Unit Address
Parameter P (Pump Parameter)
In normal modes of cooling, heating and electrical heating, the water pump will be started at least P04 time earlier and shut down
2 minutes later than the compressor. The water pump shall be started all the time during defrosting. The controller starts to inspect
water flow switch after P04-10s. If the water flow switch is inspected as ON for 10s successively, the compressor can be started.
P01
——Running Mode
P02
——Running Interval Time
P03
——Running Duration
P04
——Advanced Start Time
P05
——Manual-control
P04
P03 P02
Pump
2min
P02
P03
P03 P02
P02
P03 P02
Compressor
Содержание SIM-036
Страница 4: ... 4 Inverter Air to Water Heat Pump Specification Unit Dimensions inch SIM 036 SIM 060 ...
Страница 29: ... 29 Inverter Air to Water Heat Pump Section 6 Wiring Diagrams Definitions ...
Страница 44: ... 44 Inverter Air to Water Heat Pump Troubleshooting Chart Possible Cause Possible Solution ...
Страница 47: ... 47 Inverter Air to Water Heat Pump ...