20
POSSIBLE CAUSE
VERIFICATION
SOLUTION
Thermostat Not Level
Check level of thermostat
If necessary, level thermostat.
Defective Thermostat
With volt meter, check resistance of
If resistance, thermostat is O.K.
thermostat contacts.
If no resistance, replace thermostat.
Loose Low Voltage Wiring
Check all wiring connections for
Tighten all loose connections.
tightness.
Defective Blower Relay
Check relay as described on page 23 If defective, replace relay.
in this manual.
Defective Low Voltage Transformer
Check transformer as described on
If defective, replace transformer.
page 23 in this manual.
Inadequate Electrical Service
Check electrical service against
Replace electrical service with
minimum requirements.
adequately sized service.
CONDITION: ESP-V UNIT & CONDENSING UNIT WILL NOT START
POSSIBLE CAUSE
VERIFICATION
SOLUTION
Shorted Or Broken Wiring
Check wiring.
If necessary, repair or replace wiring.
Loose Low or High Voltage Wiring
Check all wiring connections for
Tighten all loose connections.
tightness.
Defective Blower Motor
Check motor as described on page 23
If defective, replace motor.
in this manual.
CONDITION: ESP-V UNIT WILL NOT START, BUT CONDENSING UNIT RUNS
POSSIBLE CAUSE
VERIFICATION
SOLUTION
Defective Thermostat
With volt meter, check resistance of
If resistance, thermostat is O.K.
thermostat contacts.
If no resistance, replace thermostat.
Loose Low Or High Voltage Wiring
Check all wiring connections for
Tighten all loose connections.
tightness.
Float Switch And Anti-Frost
Thermostat fan ON. With volt meter,
If no voltage, fan relay is defective.
Switch (Switches are wired in series)
check for 24v across terminal G on
Replace it.
the fan relay and terminal C on low
If read 24v, relay is O.K.
voltage terminal strip.
With volt meter, check for 24v
If no voltage, check coil for ice
at terminals YT and YC on low
and drain pan for excessive water.
voltage terminal block.
If ice check air filter, return air duct
& blower motor for air flow. If
excessive water check and clean
condensate drain lines.
If no ice on coil and water level in
drain pan is normal, check each
switch for continuity. If switch has no
continuity, replace it.
If 24v, switches are O.K.
Shorted Or Broken Wiring
Check wiring.
If necessary, repair or replace wiring.
Condensing Unit
Check according to manufacturer’s
Repair or replace as directed by
instructions.
manufacturer.
CONDITION: ESP-V UNIT RUNS, BUT CONDENSING UNIT WILL NOT START