Space-Ray VF80-L5 DSI Скачать руководство пользователя страница 1

 

Form No. 43539480 

 

May 2021 

 

  

INSTALLATION AND OPERATION INSTRUCTIONS 

 

AGRICULTURAL AIR HEATER 

 

                MODELS:

 

 

  

 

VF80-L5 DSI, VF80-N5 DSI 
 
 
 

 

OWNER/INSTALLER: 

  For  your  safety  this  manual  must  be  carefully  read  before  installing,  operating  or 

servicing this air heater.  This air heater is intended for use with either Natural Gas or Propane Gas.  It must 
be installed by a qualified service person or a licensed contractor in accordance with state and local codes.   

 

WARNING:

  Improper installation, adjustment, alteration, service or maintenance can cause injury, property 

damage  or  death.    Refer  to  this  manual.    For  assistance  or  additional  information,  consult  a  qualified 
installer, service agency or the gas supplier.  

 

INSPECT

 all combustion air openings into the building and, if necessary, clear as they become blocked by 

litter, dust, feathers or other matter. 

 

 

 

FOR  YOUR  SAFETY:

    EXHAUST  FANS 

MUST

  be  operating  on  an  appropriate  cycle  when  air  heaters  are 

operating  to  avoid  a  high  concentration  of  carbon  monoxide.    When  used  without fresh  air,  this  air  heater 
may give off carbon monoxide, an odorless and poisonous gas.  

CARBON MONOXIDE POISONING MAY LEAD 

TO  DEATH.

    Early  signs  of  carbon  monoxide  poisoning  resemble  the  flu  with  headaches,  dizziness  and 

nausea.  If you experience these signs, 

GET FRESH AIR IMMEDIATELY!

  Have the air heaters serviced as soon 

as possible and check the ventilation in the house.   

 

 

 

These air heaters are designed for agricultural applications and may operate with the use of either Natural 
Gas or Liquid Propane (LP) Gas.  Check the air heater

’s nameplate to determine the correct gas type before 

proceeding with installation. 

 

 

 

IF YOU SMELL GAS: 

 

!

 

DO NOT

 try to light any appliance. 

!

 

DO NOT

 touch any electrical switch; do not use any 

telephone in your building. 

!

  IMMEDIATELY

  call  your  gas  supplier  from  a  neighbor's 

telephone.    Follow  the  gas  supplier's  instructions.    If  you 
cannot reach your gas supplier, call the fire department. 

 

 

 

 

DO NOT 

store or use gasoline or other 

flammable vapors and liquids in the 
vicinity of this or any other appliance. 
 

SAVE THIS MANUAL 

FOR FUTURE REFERENCE.

 

 

 
 
 

 

!IMPORTANT: SAVE THIS MANUAL FOR FUTURE REFERENCE.

 

SPACE-RAY 

1700 Parker Drive  

  Charlotte, NC  28208 

Phone  (704) 372-3488  

  Fax  (704) 332-5843  

  [email protected] 

FOR YOUR SAFETY 

Scan warranty QR code on the right to 
register your product. 

 

Содержание VF80-L5 DSI

Страница 1: ...n monoxide an odorless and poisonous gas CARBON MONOXIDE POISONING MAY LEAD TO DEATH Early signs of carbon monoxide poisoning resemble the flu with headaches dizziness and nausea If you experience the...

Страница 2: ...nt thinner dust particles or unknown chemicals Failure to follow these instructions may result in a fire or explosion property damage personal injury or loss of life FIRE AND EXPLOSION HAZARD Not for...

Страница 3: ...ARD The barns must be ventilated sufficiently for the present equipment and livestock Heater ventilation requirements are outlined in the Ventilation Section of this manual Inadequate ventilation will...

Страница 4: ...NG 18 14 1 MOTOR AND BLOWER ASSEMBLY 19 14 2 AIR PROVING SAIL SWITCH 19 14 3 IGNITION CONTROL MODULE DSI 19 14 4 TRANSFORMER 20 14 5 HIGH TEMPERATURE LIMIT SWITCH 20 14 6 FLAME SENSOR 20 14 7 SPARK EL...

Страница 5: ...is manual to indicate important safety information Warning instructions must be followed to prevent or avoid hazards which may cause serious injury property damage or death Caution instructions must b...

Страница 6: ...LATION and is used in an UNVENTED mode The term Unvented actually means Indirect Vented While the products of combustion are expelled into the building national codes require ventilation in the buildi...

Страница 7: ...s are posted on the burner box In areas used for storage of combustible materials where they may be stacked below the heater NFPA54 requires that the installer must post signs that will specify the ma...

Страница 8: ...liters per hr Natural Gas 7 0 m3 hr ELECTRICAL SUPPLY 230 Vac 1 Phase 50Hz TOTAL AMP DRAW 2 0A MOTOR RATING 1 4HP 1100 rpm AIRFLOW DELIVERED 1 700 m3 h The minimum inlet gas supply pressure for the p...

Страница 9: ...Form No 43539480 May 2021 8 6 0 DIMENSIONS Model No W width D depth H height VF80 N5 DSI 779mm 465mm 722mm VF80 L5 DSI...

Страница 10: ...r etc 6 Heaters must not be supported by gas or electric supply lines and must be suspended from a permanent structure with adequate load capacity 7 Locate the heater away from livestock so that they...

Страница 11: ...usage Check with the authorities having jurisdiction and or local codes prior to choosing an individual gas connection method 8 The gas pipe flexible hose and connections must be self supporting The...

Страница 12: ...trap see figure below must be installed in the gas line at a point before the air heater The sediment trap must be installed vertical to properly function b This sediment trap or drip leg acts to tra...

Страница 13: ...per square inch are not accurate enough to measure or set the manifold pressure All measurements MUST BE made when this heater and all other gas burning equipment that is connected to the gas supply s...

Страница 14: ...tional harmonized 3 wire PVC thermoplastic jacket supply cable with earth 0 75 mm2 to National or Local standard specifications connect the power supply leads to the terminal block and earth connectio...

Страница 15: ...ions DSI S1 Flame sensor GND 24Vac transformer ground to module V2 24Vac transformer ground to Gas valve 24 VAC 24Vac supply to module L1 HOT 230Vac supply to module IND 230Vac supply to blower motor...

Страница 16: ...pre purge for 3 seconds and spark for 10 seconds Turn the thermostat or power off for 60 seconds to take the system out of lockout 5 If the heater does not light manually reset the thermostat or shut...

Страница 17: ...propriate cycle when heating the building to avoid high concentrations of carbon monoxide and water vapor The temptation particularly during the winter months is to close up the heated space to conser...

Страница 18: ...liance area is kept clear and free from combustible materials gasoline and other flammable vapors and liquids Insulated Air Duct Disconnect air ducting if equipped and inspect internally using a flash...

Страница 19: ...the heater may have been hit accidentally and tighten any loose hanging points Check that S hooks are closed Check that there is no evidence of wear on the chain threaded rod or other suspension metho...

Страница 20: ...the motor and blower assembly and clean the impellor with compressed air If vibration persists the impellor needs replacing 14 2 AIR PROVING SAIL SWITCH The air proving sail switch is not serviceable...

Страница 21: ...ontinuity after the red reset button has been pressed Annual test be careful the switch will be hot in some areas To test the operation of the high temperature limit switch remove it and hold a small...

Страница 22: ...e pressure on the outlet side of the gas valve after energizing the gas valve Replace if necessary 14 9 BURNER ORIFICE Inspect the burner orifice for dirt or insect debris Clean the orifice hole with...

Страница 23: ...et screw torque to 16 3 Nm onto the flat side of the motor shaft 6 To replace the motor remove the blower wheel as described in 5 7 Remove the 4 hex nuts from the motor and slide away from the motor p...

Страница 24: ...it 4 Replace module in reverse order Note Refer to the wiring connection diagrams in section 9 0 15 4 REMOVAL OF TRANSFORMER DSI MODELS Replacement procedure 1 Rotate the latching knob and open the sm...

Страница 25: ...he large size door at the burner gas valve compartment 2 Disconnect the lead wires from the limit switch 3 Remove the 2 sheet metal screws holding the high temperature limit switch and remove it 4 Rep...

Страница 26: ...ctrode and remove it 4 Replace this in reverse order Note Refer to the wiring connection diagrams in Section 9 0 15 8 REMOVAL OF GAS VALVE AND BURNER ORIFICE DSI MODELS Replacement procedure 1 Rotate...

Страница 27: ...emove the screw attaching the ground wiring onto the burner 3 For Pilot models disconnect the pilot assembly from the main burner by removing the wing screw 4 Remove the machine screw and washer from...

Страница 28: ...Form No 43539480 May 2021 27 16 0 TROUBLESHOOTING 16 1 TROUBLESHOOTING CHART DSI...

Страница 29: ...Form No 43539480 May 2021 28 TROUBLESHOOTING CHART DSI continued...

Страница 30: ...Form No 43539480 May 2021 29 17 0 REPLACEMENT PARTS GUIDE...

Страница 31: ...50 Plate Burner Mounting Heater 250K 1 18 50000100 Bolt Carriage 10 24 7 1 2 W Short Square 302 SS 2 19 50000250 Nut Hex Serrated Flange 10 24 SS 2 19a 02167040 Nut Hex 8 32 SS 2 20 44597010 Plate Blo...

Страница 32: ...odulating NG 1 2 NPT 1 57 44601500 Bracket Gas Valve HW VR8215M 250K Heater 1 57a 50000040 Bolt Hex Cap 3 8 16 X 3 4 Zinc 1 58 50000180 Screw Sheet Metal 8 X 3 8 410 SS Slotted Hex Head 84 59 50000190...

Страница 33: ...l Lighting Shutdown DSI 1 89 44593610 Label Wire Diagram DSI 1 90 44603000 CARTON not shown 1 Note 1 Screws Nuts and Washers are standard hardware items and can be purchased at any local hardware stor...

Страница 34: ...Form No 43539480 May 2021 33...

Страница 35: ...Form No 43539480 May 2021 34...

Страница 36: ...Form No 43539480 May 2021 35...

Страница 37: ...where any acid or acid based product causes damage to the metal components or e any heater or component part which has been repaired or replaced with other than factory parts modified in any way misu...

Страница 38: ...ed Products Inc 1700 Parker P O Box 36485 Charlotte NC 28236 Phone 704 372 3488 Fax 704 332 5843 email info spaceray com FOR YOUR RECORDS Space Ray Brooder Model Number ______________________________...

Отзывы: