TYPICAL THERMOSTAT WIRING INSTALLATIONS FOR STANDING PILOT (N1, N1A, L1 OR N1B,
L1B CONTROLS) IGNITION SYSTEM
12) VENTILATION
Where unvented infrared heaters are used, natural or mechanical means shall be provided to supply and
exhaust at least 4 cfm per 1000 Btu per hr input of installed heaters.
Exhaust openings for removing flue products shall be above the level of the heaters.
This heater requires ventilation in the building to dilute the product of combustion and provide fresh air for
efficient combustion. Power ventilation is recommended, and the minimum vent flow required is as follows:
RSCA3 = 109 cfm
RSCA6 = 218 cfm
RSCA10 = 436 cfm