Form No. 43539500
July 2021 A
–
19
–
TABLE 1
. --
LP Gas Pipe Sizing Between Single or Second Stage Regulator and Brooders Per ANSI Z223.1 National Fuel Gas Code-1992
Tubing Size, O.D. Type L
Nominal Pipe Size, I.D. Schedule 40
3/8”
1/2”
5/
8”
3/4”
7/8”
1-
1/8”
1/2”
3/4”
1”
1-
1/4”
1-
1/2”
2”
3”
4”
10 Ft.
39
92
199
329
501
935
291
608
1,146
2,353
3,525
6,789
19,130 39,018
20 Ft.
26
62
131
216
346
630
200
418
788
1,617
2,423
4,666
13,148 26,817
30 Ft.
21
50
107
181
277
500
161
336
632
1,299
1,946
3,747
10,558 21,535
40 Ft.
19
41
90
145
233
427
137
287
541
1,111
1,665
3,207
9,036
18,431
50 Ft.
18
37
79
131
198
376
122
255
480
985
1,476
2,842
8,009
16,335
60 Ft.
16
35
72
121
187
340
110
231
435
892
1,337
2,575
7,256
14,801
80 Ft.
13
29
62
104
155
289
94
198
372
764
1,144
2,204
6,211
12,668
100 Ft.
11
26
55
90
138
255
84
175
330
677
1,014
1,954
5,504
11,227
125 Ft.
10
24
48
81
122
224
74
155
292
600
899
1,731
4,878
9,950
150 Ft.
9
21
43
72
109
202
67
141
265
544
815
1,569
4,420
9,016
200 Ft.
8
19
39
66
100
187
58
120
227
465
697
1,343
3,783
7,716
250 Ft.
8
17
36
60
93
172
51
107
201
412
618
1,190
3,353
6,839
300 Ft.
---
---
---
---
---
---
46
97
182
374
560
1,078
3,038
6,196
350 Ft.
---
---
---
---
---
---
43
89
167
344
515
992
2,795
5,701
400 Ft.
---
---
---
---
---
---
40
83
156
320
479
923
2,600
5,303
Maximum propane capac
ities listed are based on 1/2” W.C. pressure drop at 11” W.C. setting
- Capacities in 1,000 BTU/hr.
TABLE 2.
Brooder #
Distance from
Regulator (ft.)
Flow Capacity
Required (Btu/hr)
Distance Used from
Table (ft.)
Smallest Pipe Size and
Capacity From Table
7 and 14
202
42,000
200
½”
--
58,000
6 and 13
174
84,000
200
¾”
--
120,000
5 and 12
146
126,000
150
¾”
--
141,000
4 and 11
118
168,000
125
1
”
--
292,000
3 and 10
90
210,000
100
1”
--
330,000
2 and 9
62
252,000
60
Note 1
1”
--
435,000
1 and 8
34
294,000
40
1”
--
541,000
Note 2
Note 1:
The distance used is rounded down to 60.
Note 2:
The actual smallest pipe size for the required capacity i
s ¾” from the table. However, the gas pipe size from brooders 3 and 4
to the regulator must be 1” diameter and therefore a smaller diameter pipe cannot be used. If ¾” pipe was used from the Tee to
brooder 1, the pressure drop in the rest of the system wo
uld exceed the design pressure drop of ½”W.C.
8.0)
ELECTRICAL CONNECTIONS
1. All electrical wiring shall conform to the latest edition of the National Electrical Code (ANSI/NFPA No.
70), or the code legally authorized in the locality where the installation is made. DO NOT use phone cable
for electric supply wiring.
2. The electrical system must be electrically grounded in accordance with the National Electrical Code
(ANSI/NFPA No. 70-latest edition) or the Canadian Electrical Code (C22.1 Part 1-latest edition) as
appropriate.
3. Each brooder requires a 24 volt-power supply via a 24 volt transformer. The 24 volt transformer MUST be
large enough to operate the number of brooders connected to it (see table below). This is calculated as
follows:
Note: The 24 volt common terminal must be grounded.