Space Pak LAHP48 Скачать руководство пользователя страница 23

– 23 –

Model 

LAHP48

 Air to Water Heat Pump — Installation, Operation & Maintenance Manual

Section 11:  Annual Maintenance

Perform Annual Inspection

Check Glycol/Water Mixture

1.

  

At least once annually, sample the system fluid to verify that 

the glycol concentrations meet the minimum value given in 

Figure 13. Also test the inhibitor concentration. Add glycol 

and inhibitor as needed to return the system to the correct 

concentrations.

2.

  

Perform any and all other tests as recommended by the anti-

freeze manufacturer’s instructions in order to ensure optimal 

performance and maintain warranty protection on all installed 

components.

Check Operating Pressure

1.  

Check the glycol/water system pressure. Operating pressure 

should be between 15 and 25 PSIG. Adjust fluid volume if 

needed to restore pressure.

2.  

If pressure is low, check system for evidence of leaks. Repair 

all leaks immediately. Perform annual inspection

 

Electrical shock hazard

 — Disconnect all electrical 

power before proceeding with the following.

Inspection of System

At least once annually, perform a complete inspection of the 

system, including at least the following:

•  Inspect the LAHP for signs of dirt or debris accumulation. 

Remove any debris and notify the building owner that the 

unit must be kept clean and unobstructed.

•  Inspect glycol/water system piping and components. 

Repair or replace any defective components. Repair all 

leaks immediately.

•  Close the isolation valves on either side of the y-strainer 

at the SpacePak heat pump return connection. Remove 

the screen and inspect for sediment. Clean if necessary.

NOTE: If the strainer has become clogged with sediment, 

determine whether the system needs to be drained, 

cleaned and re-filled. Excessive sediment accumulation 

in the strainer will reduce flow and cause the unit to shut 

down.

•  Inspect all wiring and wiring connections. Tighten 

connections if needed. Correct any problems found.

•  Check the fuses or breakers to ensure they are correctly 

sized and properly installed.

•  Clean the LAHP heat exchangers and air openings.
•  Cycle the system on heating and cooling. Verify that all 

components operate correctly.

Preparing The LAHP For Shut Down

DO NOT turn off power to the LAHP in the winter or any time 

when there is a possibility of freezing. Power must be ON for the 

automatic anti-freeze operation to occur. See information below 

for preparing the unit for shut down.

1.

  

When the water temperature drops below 34°F during periods 

of non-use, the pump will start and the anti-freeze heater 

(optional, when installed) will energize and continue to operate 

until the temperature reaches 38°F.

2.

  

If the LAHP must be turned off or left idle during periods when 

freezing is possible, one of the following must be done:
a.  Verify that sufficient glycol solution is present to protect 

against most extreme anticipate conditions 

b.  — OR — Drain heat pump and external piping completely.

To restart after shutdown

1.  If unit was drained, refill.
2.  Follow start up procedure in Section 8.

Содержание LAHP48

Страница 1: ...PIPING 13 SECTION 7 GLYCOL WATER SYSTEM Glycol Water System Design Installation 14 15 SECTION 8 START UP AND TEST Preparing for Start Up 15 BEFORE Starting the Unit 16 Start the SpacePak Low Ambient...

Страница 2: ...t capacity under extreme cold conditions and uses that heat energy to increase the compression and therefore usable heat produced by the compressor A generously sized outside coil to absorb heat in he...

Страница 3: ...3 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 1 LAHP Controller Section 2 LAHP Field Adjustable Parameters...

Страница 4: ...main menu Note a The parameters that have been modified without being confirmed using the sel button return to the previous value b If no operations are performed on the keypad for 60 seconds the con...

Страница 5: ...osting 0 360 Second 45 Duration of fan operation at full speed to clear water from coil 66 d17 Defrost with compressors OFF 0 80 0 F 55 0 Temperature above which defrost occurs with fans only 66 F02 F...

Страница 6: ...Heating F03 F05 OUTSIDE COIL PRESSURE BAR FAN SPEED PERCENTAGE SOLSTICE EXTREME FAN SPEED CONTROL COOLING F04 F06 F07 OFF r01 r19 r17 0 AS SHOWN r18 OUTDOOR AMBIENT TEMPERATURE F WATER TEMPERATURE SP...

Страница 7: ...mp sized to provide the minimum ow rates speci ed in this manual Pump selection must consider the pressure loss through the system and its components plus the pressure loss through the LAHP s heat exc...

Страница 8: ...min Pressure drop at recommended flow 17 1 ft 7 4 PSI 35 8 kPa Heating current 31A Cooling Current 23 5A Noise level at max fan speed Heating or Cooling 62 dB A Compressor EVI Scroll Installed weight...

Страница 9: ...l LAHP48 Cooling Performance 0 0 1 0 2 0 3 0 4 0 24 000 28 000 32 000 36 000 40 000 44 000 48 000 65 70 75 80 85 90 95 100 COOLING CAPACITY BTU hr OUTDOOR AMBIENT TEMPERATURE F 42 44 47 Coefficientof...

Страница 10: ...00 40 000 48 000 56 000 64 000 72 000 80 000 10 5 0 5 10 15 20 25 30 35 40 45 50 H H E E A A T T I I N N G G C C A A P P A A C C I I T T Y Y B B T T U U h h r r O OU UT TD DO OO OR R A AM MB BI IE EN...

Страница 11: ...11 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 9 Model LAHP Dimensions all dimensions in inches Section 4 Dimensions...

Страница 12: ...ted where the cables cross with sufficient padding such as multiple layers or corrugated cardboard Use caution when handling The unit is heavy and could cause severe injury or damage if dropped or han...

Страница 13: ...Make sure no other equipment located in the space will be affected by the units air flow All clearances must be maintained to ensure free air ow into and out of the enclosure Make sure no other equipm...

Страница 14: ...plier Heating 1 34 1 46 1 5 Minimum Expansion Volume System Volume Heating and Cooling 1 gallon expansion per 15 gallons system volume Heating only HP only 1 gallon expansion per 20 gallons system vol...

Страница 15: ...re Calculate the system volume 2 See Figure 13 for required glycol concentration for the mini mum expected outside temperature 3 Obtain the required volume inhibited glycol water solution premixed or...

Страница 16: ...efrigeration system will initiate and the numeral 1 will begin ashing on display 7 After 1 to 2 minutes the 1 numeral will change to constant the compressor symbol will turn on and the compressor will...

Страница 17: ...17 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 15 SpacePak LAHP Pictorial Wiring Diagram Section 9 Electrical Diagrams...

Страница 18: ...18 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 16 SpacePak LAHP Electrical Ladder Diagram Section 9 Electrical Diagrams continued...

Страница 19: ...19 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 17 Field Connections Section 9 Electrical Diagrams continued...

Страница 20: ...20 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual Figure 18 Wiring Diagram Section 9 Electrical Diagrams continued...

Страница 21: ...Stop E3 OS coil temp sensor fail Automatic None None None None E4 Refrigerant pressure sensor fail Automatic Stop None Stop None E8 Ambient temp sensor fail Automatic None None None None ESP Lost com...

Страница 22: ...cooling operation i e 55 F If low ambient cooling is desired contact Technical Support for procedure to modify fan operating parameters Compressor will not run Power supply failure Supply correct pow...

Страница 23: ...aks immediately Close the isolation valves on either side of the y strainer at the SpacePak heat pump return connection Remove the screen and inspect for sediment Clean if necessary NOTE If the strain...

Страница 24: ...0 430048 Fan Speed Controller 17 45R2000 3202 Sensor 5k 18 45R20000 120100 Plate Heat Exchanger EVI 19 45R20000 140027 Filter 20 45R20000 140194 EVI Solenoid Valve 21 45R20000 140234 Electronic Expans...

Страница 25: ...or parts thereof c To any workmanship of the installer of the Product This limited warranty is conditional upon a Shipment to the Manufacturer of that part of the Product thought to be defective Goods...

Страница 26: ...26 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual...

Страница 27: ...27 Model LAHP48 Air to Water Heat Pump Installation Operation Maintenance Manual...

Страница 28: ...IN UNITED STATES 260 NORTH ELM ST WESTFIELD MA 01085 800 465 8558 FAX 413 564 5815 IN CANADA 7555 TRANMERE DRIVE MISSISSAUGA ONTARIO L5S 1L4 905 670 5888 FAX 905 670 5782...

Отзывы: