H3-EM-62-100 Electronic Swinghandle 

     Operating Instructions 

 

J-H3-EM-62-100-M 

                                 

 

Page 2 of 4 

 
The actuator module of the swinghandle is accessed with a six-position 
connector on the rear of the unit, shown below. 
 

 

 
 

Pin 

Description 

Note 

V

GND

 

ground (must be same as RFID reader 
module) 

V

SUPPLY

 

12 to 24 VDC power supply input (may be 
connected to prox reader V

CC

 input) 

N/C 

no connect 

Control Signal 

command input (9VDC up to supply 
voltage, 100 milliseconds minimum) 

Electronic Lock 
Status  

open collector output (rated for V

SUPPLY

100mA max. load) 

Mechanical Lock 
Status 

open collector output (rated for V

SUPPLY

100mA max. load) 

 
 
The RFID reader module of the swinghandle is accessed with a four-
position connector attached to a harness connected to the module’s circuit 
board

.  The module’s connector pinout is: 

 

 

 

Pin 

Wire Color 

Description 

Note 

Black 

GND  

ground (must be same as actuator 
module) 

Red 

VCC  

12 to 24VDC power supply input 
(may be connected to EML V

SUPPLY

 

input) 

Green 

DATA0  

DATA0 output 

White 

DATA1  

DATA1 output 

 
 

 

NOTE:

  The mating connectors/harnesses are not provided with the 

H3-EM-62-100.  Refer to Southco trade drawing J-H3-EM-62-100 for 
mating connector/harness requirements. 

 
 

 
Wiegand Data Output 
 

125kHz Prox Cards 

 
The RFID module will read the site and user codes from a compatible prox 
card, and convert to Wiegand data format, including upper even parity (Pe) 
and lower odd parity (Po) bits, as shown below. 
 

 

 

13.56MHz RFID Cards 

 
The RFID module will read the 4, 7, or 8 byte UID from a compatible RFID 
card, and convert to Wiegand data format in reverse byte order, including 
upper even parity (Pe) and lower odd parity (Po) bits, as shown below. 
 

 

 

 
Control Input Signal 

 
This signal is used to control the electronic lock slide position.   

 

 

for UNLOCKED position:  Supply 9VDC minimum (do not exceed 
supply voltage) for at least 100 milliseconds.  The lock will 
remain unlocked for as long as the signal is present, or a 
minimum of 3 seconds.  Signal timing can typically be adjusted 
at the access control device.  The control signal current draw is 
less than 10mA. 

 

for LOCKED position: Supply an open contact or 0VDC (0 to 
0.5V) 

 
 
Electronic Lock Status Output and Mechanical Lock Status Output 
Signals 
 

Electronic Lock Status Output Signal 
 

This output will be LOW (GND) when the lock slide is electromechanically 
moved to the unlocked position.  It will be in the open collector state (high-
impedance) when in the locked position.  
 

Mechanical Lock Status Output Signal 
 

This output will be LOW (GND) when the handle is in the open position or 
when the keylock in the actuator is manually unlocked.  It will be in the 
open collector state (high-impedance) when in the secured position. 
 

  

NOTE:

  These outputs are open collector outputs rated for V

SUPPLY

 with 

a maximum load of 100mA.  To avoid damage to the H3-EM, do not 
exceed voltage and current ratings.   

 
 

Содержание H3-EM-62-100

Страница 1: ...econd maximum NOTE Power must be present during transit times If power is removed while the lock slide is in transit it will complete it s cycle when power is restored Electronic Unlock Time 3 seconds minimum Open Collector Outputs Rated for VSUPPLY maximum load RFID Reader Module Supply Voltage VCC 12VDC to 24VDC Operating Current 125mA maximum no external devices attached Transmit Frequency 13 5...

Страница 2: ...d convert to Wiegand data format including upper even parity Pe and lower odd parity Po bits as shown below 13 56MHz RFID Cards The RFID module will read the 4 7 or 8 byte UID from a compatible RFID card and convert to Wiegand data format in reverse byte order including upper even parity Pe and lower odd parity Po bits as shown below Control Input Signal This signal is used to control the electron...

Страница 3: ...ts open collector state if the electronic lock slide is in the locked position It will be 0V if the lock slide is in the unlocked position The mechanical lock status output is 0V NOTE The lock sensor is an optical device that senses the presence of the lock pawl Reflectivity of the lock pawl material can affect sensing Use only Southco supplied locks Mechanically Released State Handle not Fully Cl...

Страница 4: ... This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning...

Отзывы: