Figure 22: Zone Setup Screen
Figure 23: Initial System Purge
“Legend” button. Press inside the box to change the number to the number of zones that will be required for the
system. This screen can be seen in Figure 22.
8.
(Optional) Change the name of the zones in “Zone Setup” which can be accessed through the “Menu”. The user
can press any zone to change each to a more descriptive name of up to 8 characters.
7.1.2
Initial System Purge
When a Fire Protection System is first filled with nitrogen, it
mixes atmospheric air within the pipes and fittings. In order
to get pipes down to an acceptable purity level, the
AutoPurge System should be used. The Quick-Check’s
PowerSaver Manifold will vent out a small amount of gas to
eventually lower oxygen purity to a suitable level. To account
for the amount of time it will take for the system to get within
the parameters of the setpoint, the user can engage Initial
System Purge. This allows 40 days (default) of purging
without alarm.
To set up the Initial System Purge, open the “Zone Setup”
screen found in the “Menu”, then press “Start-Up Settings”
and the screen in Figure 23 will be displayed. User must turn
Initial System Purge on with the selector switch to the right of
the “Initial System Purge (Days)” to start it. Before conducting
this step, Initial System Purge(Days) can be set by the user by pressing in the box next to it (factory default = 40
days).
This feature will automatically turn off once the “Days left in Initial System Purge” reaches 0, but it may be turned off
manually at any point by pressing the toggle switch again.
7.1.3
Normal Start-up
Follow this procedure to start the Quick-Check for normal operation. If this is the first time the unit has been started,
follow the Initial Start-Up procedure above, otherwise:
1.
Open all APS zone ball valves and ensure all APS flow tuning is correct according to the APS Tuning Sheet.
2.
Toggle the “ON/OFF” button on the “Home” screen to the “ON” position to start the system
NOTE: If the generator or any part of the system has been opened to the atmosphere or water, the system must be
purged of any residual air/water to get within the limits of the purity setpoint. Another “Initial System Purge” is
advised.
7.2
SHUTDOWN
For normal shutdown, toggle the “ON/OFF” button to OFF on the “Home” screen.
WARNING: The Quick-Check PowerSaver Manifold will remain pressurized after shutdown. Before performing any
maintenance or opening any piping systems, always depressurize the system. Failure to do so may result in injuries.