Nitrogen Generator FPS-1750, FPS-3000, and FPS-6000
South-Tek Systems
Version:
7
Revision Date: 5/24/16
Page 13 of 25
adjustment is required.
4.5
PANEL LAYOUT AND GAS CONNECTION
Air Input is located on the left side of the unit. Nitrogen outlet will be located on
the right side of the unit. Double-check all connection locations before turning on
the system or opening any valves.
Note:
All N
2
-BLAST
®
models are factory equipped with ½”NPT Female
connections. See drawing (DD-TYP2M-FPS and DD-A01-0100-04-04) for detail
generator and tank connections.
4.6
BLASTOFF™ – AIR BYPASS SETUP (OPTIONAL)
The BlastOff™ - Air Bypass Option ensures that nitrogen is the only supervisory
gas entering the FPS. It safeguards your installation all while providing piece of
mind knowing the FPS is being filled with nitrogen vs any other gas. It will alarm if
the N
2
-BLAST
®
Generator is being bypassed by the air compressor. It safeguards
against a maintenance technician from inadvertently leaving the “air bypass” open
or the N
2
-BLAST
®
being powered in the off position. It will provide a visual alarm
when it is in alarm mode. See wiring diagram and installation drawing included
with this package. For electronic copies, please contact your local distributor.
4.7
CHECK FOR LEAKS
When a leak is suspected, first try to listen for leaks and/or spray with soapy water
around the connection ports. If a leak is found, isolate the area and relieve any
pressure on it prior to working on it. Fix the leaking part and return the system back
to operation. If no leak are heard (or visually seen with the soapy water), turn off
the unit and try isolating sections to see if there’s a pressure loss. If the BlastOff™
option is included with your unit, the system will alarm indicating that there is a
leak in the line. Consult with your installer if you cannot locate the leakage area.
For more information on leak checking go to