Source 1 S1-LXPROG Скачать руководство пользователя страница 2

P/N 88-810     Rev. 2

S1-LXPROG

USB PROGRAMMER

After the USB Programmer has been properly connected and recognized by the thermostat, choose 
from the following options:

Upload text only:  

Press the Upload Text button to upload service information
and thermostat messages to the thermostat.  Only text will
be copied to the thermostat when this button is pressed.  

This is the only button that will upload text.

Upload time only:

Press the Upload Clock button to upload time and day 
information to the thermostat.  Only the time and day will 
be copied to the thermostat when this button is pressed.  

Upload all settings:

Press the Upload All button to upload time and day 

and

 all 

information listed in the 

Data Transfer Table

 below, to the 

thermostat. 

This button will not upload text.

Download all settings:

Press the Download All button to copy time and day 

and

 all 

information listed in the 

Data Transfer Table

 below, to the 

USB Programmer.  This function may be used to copy data 
from one thermostat to another.

This button will not download text.

4. Uploading settings and text to the thermostat (cont.):

(B)

Upload Clock

Button

Upload Text

Button

Upload All

Button

Download All

Button

LED

                         Do not disconnect the USB Programmer 
from the thermostat during data transmission.  

Important:

OVERRIDE

Thermostat

Accessory

Port

Thermostat

Accessory

Cable

Description     

Time of day
Day of week
F or C readout
Cycles per hour
Compressor minimum 
off minutes
Scrolling method
Language
Control temp source 

Aux Heat lockout temp

Security level

Setpoint limits
Program mode
Available modes

Backlight 

Time schedule

Minimum Heat/Cool 
setpoint difference
Service Alerts

Deadband Settings
Fan off delay

Filter runtime set
UV runtime set
Humidity runtime set

Cool to Dehum
Max Dehum Overcool

Preoccupancy purge

Data Transfer Table, by Thermostat Model 

S1-THSU21P1  S1-THSU32P7 

S1-TBSU22HN  S1-TBSU32P7  S1-TBSU32HP7 

Programmable Fan
Fan on w/Hum

Reheat  w/Cool to 
Dehum

S1-THSU32HP7 

Upload All and Download All Buttons:

The current Mode and Setpoints will not be changed 
by the LX USB Programmer.
Vacation and Holiday settings will not be changed by 
the LX USB Programmer.

Note:

LED Codes

Solid RED and/or 4 

GREEN  

= Data has been 

sent successfully.  

NOTE: 

Even if data has been sent from 

the USB Programmer, the thermostat will not accept data 
programmed for a different model thermostat.

 

Flashes 

2 Flashes RED 

= USB Programmer not programmed.  

5 Flashes RED 

= All data has not been sent successfully.  

LED Not Lit when connected to thermostat 

= Batteries

dead or not installed.
   

Remedy: Use the LX USB Programmer Application 
Software to program the USB Programmer.

Remedy: Check cable connections and resend data.

Remedy: Check/install new batteries.

Text cannot be downloaded into or removed from the 
thermostat by the LX USB Programmer.  The LX USB 
Programmer computer application must be used to 
change or reset text messages.  Text messages may
also be removed by resetting the thermostat back to
factory default settings.