P/N 88-810 Rev. 2
S1-LXPROG
USB PROGRAMMER
After the USB Programmer has been properly connected and recognized by the thermostat, choose
from the following options:
Upload text only:
Press the Upload Text button to upload service information
and thermostat messages to the thermostat. Only text will
be copied to the thermostat when this button is pressed.
This is the only button that will upload text.
Upload time only:
Press the Upload Clock button to upload time and day
information to the thermostat. Only the time and day will
be copied to the thermostat when this button is pressed.
Upload all settings:
Press the Upload All button to upload time and day
and
all
information listed in the
Data Transfer Table
below, to the
thermostat.
This button will not upload text.
Download all settings:
Press the Download All button to copy time and day
and
all
information listed in the
Data Transfer Table
below, to the
USB Programmer. This function may be used to copy data
from one thermostat to another.
This button will not download text.
4. Uploading settings and text to the thermostat (cont.):
(B)
Upload Clock
Button
Upload Text
Button
Upload All
Button
Download All
Button
LED
Do not disconnect the USB Programmer
from the thermostat during data transmission.
Important:
OVERRIDE
Thermostat
Accessory
Port
Thermostat
Accessory
Cable
Description
Time of day
Day of week
F or C readout
Cycles per hour
Compressor minimum
off minutes
Scrolling method
Language
Control temp source
Aux Heat lockout temp
Security level
Setpoint limits
Program mode
Available modes
Backlight
Time schedule
Minimum Heat/Cool
setpoint difference
Service Alerts
Deadband Settings
Fan off delay
Filter runtime set
UV runtime set
Humidity runtime set
Cool to Dehum
Max Dehum Overcool
Preoccupancy purge
Data Transfer Table, by Thermostat Model
S1-THSU21P1 S1-THSU32P7
S1-TBSU22HN S1-TBSU32P7 S1-TBSU32HP7
Programmable Fan
Fan on w/Hum
Reheat w/Cool to
Dehum
S1-THSU32HP7
Upload All and Download All Buttons:
The current Mode and Setpoints will not be changed
by the LX USB Programmer.
Vacation and Holiday settings will not be changed by
the LX USB Programmer.
Note:
LED Codes
Solid RED and/or 4
GREEN
= Data has been
sent successfully.
NOTE:
Even if data has been sent from
the USB Programmer, the thermostat will not accept data
programmed for a different model thermostat.
Flashes
2 Flashes RED
= USB Programmer not programmed.
5 Flashes RED
= All data has not been sent successfully.
LED Not Lit when connected to thermostat
= Batteries
dead or not installed.
Remedy: Use the LX USB Programmer Application
Software to program the USB Programmer.
Remedy: Check cable connections and resend data.
Remedy: Check/install new batteries.
Text cannot be downloaded into or removed from the
thermostat by the LX USB Programmer. The LX USB
Programmer computer application must be used to
change or reset text messages. Text messages may
also be removed by resetting the thermostat back to
factory default settings.