36
Settings
6.4 Tmax
S2
6.5 Tmax
S3
6.6 Tmax
S4
Switch-off temperature at sensor 2
If this value is exceeded at sensor 2 and the other conditions are also met, then the
controller switches the associated pump and/or valve off. If sensor 2 falls below this
value again and the other conditions are also met, then the controller switches the
pump and/or valve on again.
Setting range: from 0°C to 99°C/default setting: 60°C (in pool variants locked to 30°C)
Switch-off temperature at sensor 3
If this value is exceeded at sensor 3 and the other conditions are also met, then the
controller switches the associated pump and/or valve off. If sensor 3 falls below this
value again and the other conditions are also met, then the controller switches the
pump and/or valve on again.
Setting range: from 0°C to 99°C/default setting: 60°C (in hydraulic variants without S3
default: Off)
Switch-off temperature at sensor 4
If this value is exceeded at sensor 4 and the other conditions are also met, then the
controller switches the associated pump and/or valve off. If sensor 4 falls below this
value again and the other conditions are also met, then the controller switches the
pump and/or valve on again.
Setting range: from 0°C to 99°C/default setting: 60°C (in hydraulic variants without S3
default: Off, in variants with pool: 30°C)
Danger
Danger
Danger
Temperature values which are set too high can lead to scalding or dam-
age to the system. Scalding protection must be provided by the cus-
tomer!
Temperature values which are set too high can lead to scalding or dam-
age to the system. Scalding protection must be provided by the cus-
tomer!
Temperature values which are set too high can lead to scalding or dam-
age to the system. Scalding protection must be provided by the cus-
tomer!