
Wall Installation
1. Unscrew cover screw completely.
2. Carefully pull upper part of housing
from lower part. During the removal,
the brackets are released as well.
3. Set upper part of housing aside Do not
touch the electronics.
4. Hold the lower part of the housing up
to the selected position and mark the
three mounting holes. Make sure that
the wall surface is as even as possible
so that the housing does not become
distorted when screwed on.
5. Using a drill and size 6 bit, drill three
holes at the points marked on the wall
and push in the plugs.
6. Insert the upper screw and screw it in
slightly.
7. Fit the upper part of the housing and
insert the other two screws.
8. Align the housing and tighten the three
screws.
1. open terminal cover.
2. Strip lines a max. of 55 mm, assemble
the strain reliefs, strip wire ends 8-9
mm (figure 1)
3. Open clamps with a fitting screwdriver
(figure 2) and connect electrical system
to the controller.
4. Suspend clip room cover again and
close with the screw.
5. Turn on mains supply and operate the
controller.
Electrical Connection
Before working on the unit, switch off the power supply and secure it against being switched on again! Check that there
is no power flowing! Electrical connections may only be made by a specialist and in compliance with the applicable
regulations. The unit may not be put into operation if there is visible damage to the housing, e.g. cracks.
The unit may not be accessible from behind.
Low-voltage cables such as temperature sensor cables must be routed separately from mains voltage cables. Feed
temperature sensor cables only into the left-hand side of the unit, and mains voltage cables only into the right-hand
side.
The customer must provide an all-pole disconnecting device, e.g. an emergency heating switch.
The cables being connected to the unit must not be stripped by more than 55 mm, and the cable jacket must reach into
the housing just to the other side of the strain relief.
10