Fresh Water Controller FWC3
Installation and operating instructions
Read carefully before installation, commissioning and operation
Страница 1: ...Fresh Water Controller FWC3 Installation and operating instructions Read carefully before installation commissioning and operation...
Страница 2: ...s 16 2 1 Operating hours HW 16 2 2 Operating hours circ 16 2 3 Heat output 16 2 4 Graphic overview 16 2 5 Error messages 16 2 6 Reset clear 16 3 Display mode 17 3 1 Schematic 17 3 2 Overview 17 3 3 Al...
Страница 3: ...eneral instructions It is essential that you read this These installation and operating instructions contain basic instructions and important information regarding safety installation commissioning ma...
Страница 4: ...accessories Use of the device for other than its intended purpose Operation above or below the limit values listed in the specifications Force majeure Changes additions to or conversion of the unit ar...
Страница 5: ...nsport storage no moisture condensation permitted Other specifications and dimensions Housing design 2 part ABS plastic Installation methods Wall installation optionally panel installation Overall dim...
Страница 6: ...system by means of statistical graphics etc Extensive setting menus with explanations Menu block can be activated to prevent unintentional setting changes Resetting to previously selected values or fa...
Страница 7: ...active This temperature is measured at sensor 4 If the water is very calcareous and the temperature of flow could be very high over 70 C for not creating limescale in the secondary side of exchanger...
Страница 8: ...s when doing so 4 Hold the lower part of the housing up to the selected position and mark the 3 mounting holes Make sure that the wall surface is as even as possible so that the housing does not becom...
Страница 9: ...pped by more than 55mm and the cable jacket must reach into the housing just to the other side of the strain relief Relay R1 is only suitable for standard pumps 20 120VA which are speed con trolled vi...
Страница 10: ...r pump N R2 Not used N Not used The PE protective conductor must be connected to the PE metal termi nal block Low voltage max 12VAC DC connection in the left hand terminal compartment Terminal Connect...
Страница 11: ...sh water pump L N Fresh water pump N R2 Circulation pump L N Circulation pump N The PE protective conductor must be connected to the PE metal termi nal block Low voltage max 12VAC DC connection in the...
Страница 12: ...n entry or to exit a menu If applicable there will be a request for confirmation as to whether the changes which have been made should be saved The function of each of the other three keys 4 is shown...
Страница 13: ...gs in the following sequence Menu 6 Special functions clock Menu 5 Settings complete Finally menu 4 2 under operating mode Manual should be used to test the switch outputs with the consumers connected...
Страница 14: ...main menu The following menu items are then available for selection there Current temperature values with explanations Function control of the system with operating hours etc Select graphics mode or...
Страница 15: ...tead of the measurement value then there may be a defective or incorrect temperature sensor Caution If the cables are too long or the sensors are not placed optimally the result may be small deviation...
Страница 16: ...ion Statistics 2 1 Operating hours HW Display of operating hours of the hot water pump connected to the controller 2 2 Operating hours circ Display of operating hours of the circulation pump connected...
Страница 17: ...ssing esc or selecting Exit display mode 3 1 Schematic In graphics mode the selected hydraulic systems are depicted with the measured temperatures and operating states of the connected consumers 3 2 O...
Страница 18: ...ual isactivated thecurrenttemperaturesandtheselected parameters are no longer considered There is a danger of scalding or serious dam age to the system The operating mode Manual may only be used by sp...
Страница 19: ...tings range 30 C to 90 C Default 45 C Danger Temperature values which are set too high can lead to scalding or damage to the system Scalding protection must be provided by the customer 5 2 Tmax Maximu...
Страница 20: ...iods Default Request When mode Periods or Request is active additional menu items are available in the Settings menu Caution Settings 5 5 Circ purging time Operating time of the circulation pump The c...
Страница 21: ...exceeds this value because water is being drai ned from the system the circulation pump is switched off Settings range 1 l min to 50 l min Default 15 l min Settings 5 10 Circulation period Period whe...
Страница 22: ...specialist Incorrect measurement values can lead to unpredictable errors Other than the time all settings may only be made by a specialist 6 3 Commissioning Starting the commissioning help guides you...
Страница 23: ...gh temperatures which can lead to scalding and damage to the system Caution This anti Legionella function does not provide complete protection against Legionella because the controller is dependent on...
Страница 24: ...g the pump runs at the specified speed and the flow rate can be determined Setting range 70 to 100 Default 100 6 6 2 Min speed The minimum speed of the pump at relay R1 is specified here During the se...
Страница 25: ...it menu lock The menus listed below remain completely accessible despite the menu lock being activated and can be used to make adjustments if necessary 1 Measurement values 2 Analysis 3 Display mode 8...
Страница 26: ...ed for remote diagnosis by a specialist or the manufacturer in the event of an error etc Caution Enter the values at the time when the error occurs e g in the table Themenucanbeclosedatanytimebypressi...
Страница 27: ...elect the language for the menu guidance This is queried automatically during initial commissioning The choice of languages may differ however depend ing on the device design Language selection is not...
Страница 28: ...he sensor the sensor input at the controller or the connecting cable is was defective Resistance table on page 5 This display appears automatically after a mains failure because the time date have to...
Страница 29: ...rnal source of the error e g pump and ex change it Then first recommission the controller and check the function of the switch outputs in manual mode as described under 9 2 Repairs and maintenance may...
Страница 30: ...list and have the settings optimised if necessary Caution Performing maintenance Check the date and time see 11 1 Assess check plausibility of analyses see 7 Check the error memory see 7 5 Verify chec...
Страница 31: ...31 Notes...
Страница 32: ...ityofincorrectorincompleteinformationcannotbeexcluded Subject as a basic principle to errors and technical changes Notes Hydraulic variant set Commissioned on Commissioned by Manufacturer SOREL GmbH M...