DECLARATION OF CONFORMITY

We declare that the LED floodlight is designed to be used in potentially explosive atmospheres
described below:

SOPEX Explosion Proof LED Floodlight

Types: SXF8011W/8011N/8012W/8012N/8013W/8013N

Ex II 2 G    Ex db eb op is IIC T6/T5/T4 Gb

Ex II 2 D    Ex tb op is IIIC T80°C / T100°C / T135°C Db

satisfies:

- the provisions of Directive 2014/34/EU
- standards:

EN 60079-0:2012+A11:2013
EN 60079-1:2014
EN 60079-7:2015
EN 60079-28:2015
EN 60079-31:2014

- the provisions of IEC 60533 (electromagnetic compatibility)
- the type and its variants have received the EC examination certification type:

EPS 18 ATEX 1 191 X  /  IECEx EPS 18.0097X

Subject to use for the purpose for which it is designed and installation in accordance with standards
in force and with recommendations of the manufacturer.

The certification body is EPS - Bureau Veritas Consumer Products Services Germany GmbH.

Symptom 

Solution

Floodlight does not turn on 

Check for proper cable termination and good connection

Verify the power supplied has the right voltage

If connected to external controls, ensure the control is working 
properly 

Floodlight is rocking

Ensure the position locking mechanism is properly secured 

Check the mounting screws are firmly tightened 

TROUBLESHOOTING

Use AISI 316 stainless steel screws to secure / mount the floodlight.

The LED floodlight can be turned on or restarted instantly with full brightness. No warm-up time is
required.

Other than the junction box, no other parts of the floodlight should be opened for installation,
modification or maintenance.

To ensure the junction box is waterproof and maintain the

floodlight’s

warranty:

a) Check the compatibility of the cable gland size with the power cable diameter. Tightening of

the cable gland seal on the cable sheath must by steady.

b) Check the base of the cable gland is firmly screwed into the junction box and does not turn

loosely.

c) Ensure the gasket of the junction box is correctly positioned. Periodically check the gasket.

If the gasket is in poor condition, replace it immediately.

All repair works and spare parts must be sourced from SOPEX Innovations Pte Ltd.