5.3 Mounting of the temperature sensors

The temperature sensor in the flow meter has no black frame marking on the label.

The temperature sensor with the black frame mark on the label indicates that the sensor must 

be mounted in the pipe “opposite” to the Superstatic 749.

Example: If the flow meter is installed on the warm side (Hot Pipe), the temperature sensor with 

the black frame mark will be mounted in the cold side (Cold Pipe).

The Superstatic 749 is delivered with temperature sensors having a cable length of 1.5 m. 

The temperature sensors form a sub-assembly with the calculator. The temperature sensor 

cables must be neither shortened nor lengthened.

The temperatures of use displayed on the label must be respected.

A temperature sensor may be fitted directly in the Superstatic 749 flow meter. The temperature 

sensors will preferably be fitted directly, in other words one temperature sensor will be fitted in 

the flow meter while the other sensor will be installed on the other side of the heat exchanging 

circuit. 

Note:

 The temperature sensors will be fixed with a plastic nut. This plastic nut consists of two 

half-nuts held together by a rubber band. If the rubber band is removed from the nut, the two 

nut halves will no longer be held together on the temperature sensor and one or both nut halves 

may separate from the temperature sensor.

1.   Remove the O-ring from the temperature sensor. Be careful not to remove the rubber band  

     (symbolized by the letter "E" on the drawing) from the nut as it may separate into two parts  

      and fall on the floor.

2.   Fit the O-ring on the mounting template pin.

3.   Insert the O-ring by rotating it using the fitting template in the position provided for the ball valve.

4.   Position the O-ring definitively with the other flat end of the fitting tem-plate.

5.   Insert the temperature sensor with the two half-nuts in the thread M10x1 of the ball valve  

      and screw down by hand as far as it will go (maximum tightening torque of 1 Nm).

Note: The mounting template pin is not included in the delivery and can be ordered separately 

(Article number: 0460P348).

When sensor pockets are employed, these must be used specifically for the two temperature 

sensors and must correspond to the list set out below. 

Asymmetrical mounting is also possible. In that case the temperature sensor having a cable 

marked with black frame will be fitted in the other side of the heat exchanging circuit in a sensor 

pocket defined according to the table set out below.

For applications with non-symmetrical integrated temperature sensor pair restricted rated

operating conditions are to be in accordance with the lower limit of the flow value and the lower 

limit of the temperature difference: qi ≥ 200 l/h at ∆Tmin = 3K or qi ≥ 60 l/h at ∆Tmin ≥ 6 K.

Make sure that the sensors are mounted until they stall with the bottom of the sensor pocket.

Содержание Superstatic 749

Страница 1: ...Instruction for Use Superstatic 749 ...

Страница 2: ... mounting of the calculator 11 5 3 Mounting of temperature sensors 12 5 4 Sensor pockets overview 13 5 5 Direct mounting in a T tube 13 5 6 Fitting temperature sensor for cooling application 14 6 Installation 14 6 1 Superstatic 749 14 6 2 Mounting of the for the pulse input function 14 6 3 Mounting cable for the pulse output function 14 7 Commissioning 15 7 1 Commissioning from the storage mode 15...

Страница 3: ...erstatic 749 will be explained as a note in the current manual s different sections 1 2 Target groups This documentation is intended for the system operator and the installer 1 3 Storage of the document The system operator must ensure that this documentation is accessible to the responsible persons at all times If the original document is lost you can download an up to date version of this documen...

Страница 4: ...ning the non observance of which may result in damage to property Reference Information that is important for a specific topic or goal but not relevant to security Documentation Reference to documentation Help Help in case of problems Visual check Check that the item is in order CE and UKCA Marking The device meets the requirements of the European directives and of the UK Conformity Assessment Dis...

Страница 5: ...ergy meter Superstatic 749 is a precision measuring instrument approved for individual metering of heating systems and must be handled with care The Superstatic 749 is available in a heating or cooling or heating cooling version and determines the thermal and or cold energy exchanged by a heat bearing fluid in a heat exchanger circuit The Superstatic 749 complies with the requirements of the Europ...

Страница 6: ...erating fluids n Action must be taken to ensure that no condensation water can penetrate inside the calculator n If there is any risk of vibrations the calculator must be installed separately on the wall n If the temperature of the fluid within the flow meter regularly reaches 90 C the calculator must be installed separately from the flow meter n It is advisable to drain the installation before fi...

Страница 7: ...7 Instruction for use Superstatic 749 3 Scope of delivery Transport Storage Cleaning ...

Страница 8: ... Superstatic 749 4 Superstatic 749 thermal energy meter 4 1 Dimension qp0 6 m3 h L 110 mm 86 8 110 2 L 52 78 D 105 87 5 35 5 53 57 2 L 86 8 89 110 2 78 D 110 5 35 5 57 2 53 54 49 90 4 2 Dimension qp1 5 m3 h L 130 or 190 mm ...

Страница 9: ...9 Instruction for use Superstatic 749 4 Superstatic 749 thermal energy meter 4 3 Dimension qp2 5 m3 h L 130 or 190 mm L D 108 35 5 89 78 110 2 54 6 55 6 52 87 5 ...

Страница 10: ...y interfering influence Waterproof will be checked at the various mounting points The heat conveying liquid must be equivalent to water without any additives according to standard FW510 of the AGFW German District Heating Association If additives are added to the water the user must ensure the compatibility of the materials used in the thermal energy meter which are in contact with these additives...

Страница 11: ...rom the flow meter press laterally with one hand on the two locking buttons while pulling the calculator upwards Figure 2 Fix the calculator onto the wall fixing component taking care not to jam the cable which connects the calculator to the flow meter and stick the adhesive tab behind the wall component Secure the assembly to the wall Figure 3 Figure 1 Figure 2 Figure 3 To remove the calculator f...

Страница 12: ... nut halves may separate from the temperature sensor 1 Remove the O ring from the temperature sensor Be careful not to remove the rubber band symbolized by the letter E on the drawing from the nut as it may separate into two parts and fall on the floor 2 Fit the O ring on the mounting template pin 3 Insert the O ring by rotating it using the fitting template in the position provided for the ball v...

Страница 13: ...ng Ø 5 Pt1000 M10x1 SCTW4A1 Brass 0 100 C Ø 5 Pt1000 G3 8 SCTW4A2 Brass 0 100 C Ø 5 Pt1000 G1 2 SCTW4A3 Brass 0 100 C Ø 5 2 Pt1000 M10x1 SCTW4A4 Brass 0 100 C Ø 5 2 Pt1000 G3 8 SCTW4A5 Brass 0 100 C Ø 5 2 Pt1000 G1 2 SCTW4A6 Brass 0 100 C Ø 6 Pt1000 G1 2 SCTW1A1 Brass 0 100 C The temperature sensor is on the same level and perpendicular to the pipe axis DN15 DN20 5 4 Sensor pocket overview 5 5 Dir...

Страница 14: ...e sure that the gaskets are carefully positioned in relation to the water pipe and flow meter unions Tighten the fixing nuts firmly by hand Then tighten up to the mechanical end stop using a mounting tool Install the temperature sensor Turn the display into the desired position for reading Check the waterproof of the meter placed under pressure Seal the flow meter and the temperature sensors 6 2 M...

Страница 15: ...ngue PUSH CHANGE Long pression Automatic change 000000 01 MWh Short pression PUSH CHANGE Long pression Automatic change 000000 01 m3 Short pression PUSH CHANGE Long pression Automatic change Short pression Cold pipe Short pression 001234 56 MWh Energy Service Counting OFF Short pression Short Pression In the Config menu optionally available a long press will change the settings below Flow meter mo...

Страница 16: ...9 software via the optical interface 8 Error codes The Superstatic 749 calculator displays an error message with the 3 letters Err and a code If several errors occur at the same time the different codes are added together The error is displayed in the first position of the display menu It will still be possible to select all the other display menus by pressing the navigation button If the navigati...

Страница 17: ...Actual flow Aktuelle Leistung Puissance actuelle Actual power Segmenttest Test des segments Test LCD Identifikationsnummer Numéro d identification Identification number M Bus Adresse Adresse M Bus M Bus address Radio Adresse Adresse Radio Radio address Firmwareversion Version Firmware Firmware Version Energie Tariff 1 Monat 2 Energie Tariff 1 au mois 2 Energy Tariff 1 month 2 Letzter Monastwert En...

Страница 18: ...ng energy Whenever the smallest energy unit hot or and cold or volume displayed on the screen is incremented 1 pulse will be transmitted on the corresponding output cable S1 S2 Example for energy Display 12345678 kWh output pulse value for energy 1 kWh pulse Display 12345 678 MWh output pulse value for energy 0 001 MWh pulse Display 123456 78 GJ output pulse value for energy 0 01 GJ pulse Example ...

Страница 19: ... transfer data according to the wM Bus EN13757 4 radio communication protocol and in compliance with the OMS Open Metering System Release V4 To have this interface provided in the Superstatic 749 it is necessary to specify when ordering The Wireless M bus module will be installed and configured at the factory A specific notice will be added to the standard documentation Technical data Unidirection...

Страница 20: ...col compliant with standard EN 1434 3 free potential interfacing without polarity the voltage measured on the last device must exceed 36VDC transmission speed 300 2400 Baud variable data structure A M bus device is seen as two M Bus charges by the Master Type of cable recommended telephone cable JYStY N 2 0 8 mm2 11 Security seals As sealing varies from country to country local regulations must be...

Страница 21: ...0 130 Brass 16 3 0 15 10 yes 1 4 3 4 0 20 1 5 1 20 190 Brass 16 3 0 15 10 yes 1 6 3 4 0 20 2 5 1 20 130 Brass 16 5 0 25 17 yes 1 4 5 7 0 19 2 5 1 20 190 Brass 16 5 0 25 17 yes 1 6 5 7 0 19 16 bar 1 6 MPa Mounting The Superstatic 749 should not be mounted on the side where the continuous operating temperature of the liquid exceeds 90 C or is below 5 C Length of straight section fitted upstream down...

Страница 22: ...ume or pulses C K Power supply 3 VDC Lithium Battery 6 1 or 12 1 years Radio communication Sontex Radio Frequency Communication Protocol Encryption Transmission power Transmission interval wM Bus Frequency Communication Protocol Encryption Transmission power Transmission interval LoRaWAN Frequency Communication Protocol Encryption Transmission power Transmission interval Uplink Downlink 433 82 MHz...

Страница 23: ...ic 749 13 Declaration of Conformity Sontex hereby declares that the Superstatic 749 complies with MID 2014 32 EU and RED 2014 53EU and with the UK Conformity Assessment The Declaration of Conformity are available at the following link ...

Страница 24: ...1 32 488 30 00 sontex sontex ch www sontex ch 22 12 Technical support For technical support contact your local Sontex agent or Sontex SA directly Hotline Sontex support sontex ch 41 32 488 30 04 Technical modifications subject to change without notice ...

Отзывы: