RE-3P-105 

3-Phase Panel Mount 105kW 

Issue Number: 7.0 

Date of Issue: 02/01/2018 

 

 

Four Elms Road 

 Edenbridge 

Kent 

 TN8 6AB 

 UK 

 

 

 

SAFETY REQUIRMENTS & ADVICE SHEET (continued) 

 
 Adherence to BS 7671, Chapter 42 (Protection Against Thermal Effects), and in particular; 
 

 

420.3 – General Requirements, 

 

421 – Protection Against Fire Caused by Electrical Equipment 

o

 

421.1 

o

 

412.2 

 

422 – Precautions Where Particular Risks of Fire Exist 

o

 

422.1.2 

o

 

422.1.3 

 
should be undertaken, and as a minimum, a mains isolation switch, a load-breaker switch and a contact breaker should be installed in the electric 
heater battery controller supply. The supply to the contactor coil should be interrupted by an over-temperature (hi-limit) thermostat located in the 
heater battery and also upon detection of airflow loss (fan proving), via an air flow switch, air DP switch across the fan or fan current switch in the 
fan supply. 
 
Additionally, EN 61508-1:2010 (Functional safety of electrical/electronic/ programmable electronic safety-related systems. General requirements) 
stipulates the general requirements for electrical, electronic and programmable electronic safety devices, and covers the safety systems of electrical 
equipment and their components that could have an impact on the safety of people and the environment if they fail. BS EN 61508-1 also applies to 
protection and control systems, and helps organisations to identify hazards to improve overall equipment safety in the workplace. 
 
Failure to incorporate these safety interlocks may result in the invalidation of fire insurance, building and contents insurance, and in extreme cases 
may result in the disconnection of the electrical supply by the distributor. 
 
 

Operation, Installation & Configuration

 

 
The RE-3P-105 has been designed to control electric heating loads in proportion to the incoming, selectable analogue signal. Control of the load is 
facilitated by the use of solid-state semiconductor devices and feature zero crossing point switching of the AC load which virtually eliminates RFI 
problems. 
 
Caution 
In normal operation the heat sink surface can exceed 90°C. 
Dangerous voltages exist on the PCB and particular care should be taken. The RE-3P-105 must be installed in accordance with the relevant 
statutory regulations and installation must be carried out by an experienced and fully qualified engineer. 
 
Ventilation / Location 
Install power controller with heatsink fins in the vertical plane. Allow a minimum of 100mm clearance top and bottom, and 25mm horizontally. 
Control panels should have sufficient ventilation (grills or louvres as required) to maintain the ambient temperature through the thyristor unit to 
below 40C°C to run unit to specified kW rating. 
 
Over Temperature Monitoring 
The RE-3P-105 is provided with an electronic thermal cut-out fitted to the heat sink to protect against over temperature. The unit will switch off the 
load if the heat sink temperature exceeds 95°C and will automatically reconnect the load once the heat sink temperature has dropped below 85°C. 
Upon switching, the alarm output from the control PCB will change from 24V to 0V. 
 
The heat sink temperature will not reach 95°C under normal operating conditions. However, this might occur if the ambient temperature exceeds 
40°C. 
 

Installation must be carried out by a suitably trained electrician, and in accordance with the relevant statutory regulations. 

 
Load Supply and Back-up Protection 
High speed fuses or miniature circuit breakers should be utilised to provide back-up protection to the switching devices. It is recommended that a 
load disconnect switch and a contactor are installed in the load supply. The supply to the contactor coil should be interrupted by an over-
temperature thermostat located in the heater battery and also upon detection of airflow loss. 
 
Control Supply 
There is a transformer fitted to the unit removing the requirement for a 24V supply (see wiring for details).  
The control supply common is linked to the 0-10V Input Signal common. Screened cable should be used for connections to BMS Controllers, where 
possible the cable screen should be connected to a functional earth and at one end only to avoid earth loops. 
 
Maximum Heating Load 
The power rating of the units are given as a guide. The maximum current (which is dependent on the actual supply voltage and heating load) must 
not be exceeded. 