Installation (continued): 

Installation heat calculator 

Sontay recommends mounting the calculator on the wall. Do not mount the device at the pipe or attach it directly on the flow sensor. 
 
The mounting adapter at the backside of the calculator can be used for DIN-rail mounting or “reverse” for wall mounting. 
 
For wall mounting attach the adapter with at least two screws to the wall and clip the calculator on it. 
 
For rail mounting lift the adapter a little bit, place the calculator on the rail and push the adapter back until it locks. 
  
  
  
  
 
  
  

DIN-rail 

mounting 

   Wall 

mounting 

Connection sensors 

The mounting of the temperature sensors should be done symmetrical with direct immersion. If immersion sleeves are used they have 
to be checked for conformity to MID and have to be marked accordingly. The installation of immersion sleeves has to be done 
according to DIN EN 1434-2. 
  

 

The sensor cables are marked with colours (red = supply, blue = return). Do not buckle, extend or shorten the wire. 

 

Do only use paired sensors with the same serial number on it. 

 

 

 

 

 

 

 

 

Supply and return sensors must be inserted into the immersion sleeves completely.   

 

 

 

 

Installation points in the flow sensor can be used for symmetrical installation of the temperature sensors. 

 

 

 

Seal temperature sensor after installation to prevent unauthorized demounting (seals included). 

 

 

 

Do not wrap or install wires along hot pipes. 

 

Connection flow sensor 

The total length of the wire between flow sensor and calculator should not exceed 2m. Mind the polarity at electronic flow sensors. 
  

Operation test 

Check the calculator for any error codes in the display after installation (see Page 5 for error codes). Most of the errors can be deleted 
by pressing the button. 
If the error appears permanently, it will be detected at the next measuring cycle and displayed again. Check whether the volume 
information is updated and the displayed temperatures correspond to the present ones while the system is running (measuring cycle 2 
minutes max.). 
When attaching the top cover on the housing pulses on the inputs can possibly be generated. Check readings of the inputs and correct 
if necessary. 
  

Sealing 

Seal the device with the included seals to prevent unauthorized opening. 
  

Maintenance 

Repairs or overhaul are only allowed by the manufacturer or companies authorized by the manufacturer. 

 

 

  

 
 
  

 
 

Содержание MW-U

Страница 1: ...the delay time measured this information is then transmitted to the calculator by the way of electronic pulses The calculator uses the latest innovative technology to calculate heat usage from heatin...

Страница 2: ...400m s TP 600m s M Bus Baud rate 2400 General Ambient range Temperature 5 to 55 C RH 95 non condensing Measurement accuracy Class 2 MID Annex MI 004 Conformity MID Annex B Annex D Protection IP54 The...

Страница 3: ...he device is maintenance free during the service life Repairs can only be made by the manufacturer Declaration of Conformity Sontay Ltd declares that this product with the number of the EC type examin...

Страница 4: ...re Do only use paired sensors with the same serial number on it Supply and return sensors must be inserted into the immersion sleeves completely Installation points in the flow sensor can be used for...

Страница 5: ...and outgoing of the M Bus wires L1 24 L2 25 The symbols in the table below show the meter s operational status The status messages only appear in the main display energy The temporary display of the...

Страница 6: ...5 40 60 Nominal Diameter DN mm 15 15 15 20 25 40 50 65 80 100 lnch 1 1 Inst Length without conn L mm 110 110 110 130 260 300 270 300 300 360 Thread meter G x B D1 lnch 1 1 2 Flange Flange Flange Flang...

Страница 7: ...erature difference Flow Maximum flow Instantaneous power Pulse value counter 1 Pulse value counter 2 Energy at SRD Date SRD SRD value external counter 1 SRD value external counter 2 Monthly values inp...

Страница 8: ...y value input 1 1st monthly value input 2 Sensor type installation point Pulse value Basic configuration Model number Date battery end Time Datum M Bus address Baud rate Input display Error status Sof...

Отзывы: