![Sontay GS-S-CO-W Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/sontay/gs-s-co-w/gs-s-co-w_quick-start-manual_1322772003.webp)
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.
Page 3 of 3
UK Sales Tel: 0845 345 7253
International Tel: +44 1732 861225
For the latest information and product updates, register at www.sontay.com
GS-S-CO-W
Issue: 5.0
Date Of Issue: 19/12/2011
© 2011 Sontay Limited. All rights reserved.
Trend Scaling
IQ1xx and early IQ2x series (without type 5, characterise)
0-10Vdc 4-20mA
(0 to 100ppm)
Brange:
-100
Brange:
-150
Trange:
100
Trange:
100
Upper:
100
Upper:
100
Lower:
0 Lower:
0
Exponent: 3 Exponent: 3
(0 to 1000ppm)
Brange:
-1000
Brange:
-15000
Trange:
1000
Trange:
1000
Upper:
1000
Upper:
1000
Lower:
0 Lower:
0
Exponent: 4 Exponent: 4
Later IQ2x series and IQ3 (with type 5, characterise)
0-10Vdc 4-20mA
(0 to 100ppm)
Upper:
100
Upper:
100
Lower:
0 Lower:
0
Exponent: 4 Exponent: 4
Points Used:
2
Points Used:
2
I1:
0 I1:
4
O1:
0 O1:
0
I2:
10
I2:
20
O2:
100
O2:
100
0-10Vdc 4-20mA
(0 to 1000ppm)
Upper:
1000
Upper:
1000
Lower:
0 Lower:
0
Exponent: 4 Exponent: 4
Points Used:
2
Points Used:
2
I1:
0 I1:
4
O1:
0 O1:
0
I2:
10
I2:
20
O2:
1000
O2:
1000