background image

 

Tel: +44 (0)1732 861200  -  E-mail: [email protected]  -  Web: www.sontay.com 

© 2017 Sontay Limited. All rights reserved 

Page 1 of 5 

 

GL-CO-RFG-361 

1-Channel Gas Leak Alarm System 

Issue Number: 7.0 

Date of Issue: 08/03/2017 

 

 

Four Elms Road 

 Edenbridge 

Kent 

 TN8 6AB 

 UK 

 

 

Features & Benefits 

 

 

Remote sensors for natural gas, LPG and CO 

 

1 x SPST relay outputs 

 

DIN-rail as standard, panel mounting kit 
available 

 

Adjustable alarm thresholds 

 

Self-diagnosis fault system 

 

Audio & visual alarms 

Technical Overview 

 
The CL-CO-RFG361 is a single channel gas leak alarm system, that is designed for the detection of gas leaks in spaces such as boiler plant rooms, 
workshops and other industrial gas installations, to provide safety alarm and shutdown facilities on detection of gas leakage.

 

Specification

 

 
Power supply 

 

230Vac ±10% @ 50/60Hz 

Power consumption   

3VA 

Radio disturbance   

VDE0875/0871 

Vibration test 

 

with 2g (DIN 40046) 

Relay output 

 

SPDT, 250V @ 5(1) A 

Housing dimensions  

115 x 53 x 70mm 

Housing materials: 
 

Cover 

 

ABS 

 

Base 

 

Nylon 

Housing protection   

IP30 

Sensor dimensions   

77 x 77 x 44 

Sensor material 

 

Nylon 

Sensor protection   

IP44 

Ambient: 
 

Storage temp. 

-25 to + 60°C  

 

Operating temp. 

0 to 45°C 

 

RH 

 

Class F Din 40040 

Country of origin 

 

Italy 

  
 
  
  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The products referred to in this data sheet meet the requirements of 
EU 2014/30/EU and 2014/35/EU 

Product Codes

 

 
Controller 
GL-CO-RFG-361 
 

1 Channel gas leak alarm system (DIN rail mount) 

  
Mounting option 
GL-CO-FMK3 
 

Panel mounting kit 

 
Sensors 
GL-CO-SRS-150 
 

Natural gas sensor 

  
GL-CO-SRS-250 
 

LPG, Propane sensor 

  
GL-CO-SR-S350 
 

Carbon Monoxide sensor 

WEEE Directive: 

At the end of the products useful life please 
dispose as per the local regulations. 
Do not dispose of with normal household waste. 
Do not burn. 

Содержание GL-CO-RFG-361

Страница 1: ...akage Specification Power supply 230Vac 10 50 60Hz Power consumption 3VA Radio disturbance VDE0875 0871 Vibration test with 2g DIN 40046 Relay output SPDT 250V 5 1 A Housing dimensions 115 x 53 x 70mm Housing materials Cover ABS Base Nylon Housing protection IP30 Sensor dimensions 77 x 77 x 44 Sensor material Nylon Sensor protection IP44 Ambient Storage temp 25 to 60 C Operating temp 0 to 45 C RH ...

Страница 2: ...t NOT be positioned Less than 1 to 2 metres from boilers or water heaters Less than 2 to 3 metres from kitchen ranges and ovens In spaces where air movement could be hindered e g in corners or enclosed spaces Near to doors or windows Near to air extractors In places where dust or dirt could contaminate the sensor and so render it ineffective In places subject to possible sprays of water particular...

Страница 3: ... sensors positioned up to a maximum distance of 75 meters 5 NB It is advised that no more than 2 cables be inserted into a single terminal Use external junction boxes if necessary 6 Select the link functions to adapt the detector to the desired type of operational control Fascia Wiring Basic operation Solenoid valve N C Links Warning when changing link functions ensure all power is disconnected fi...

Страница 4: ...s into account the concentration of the gas in the air and the exposure time For this reason the Sensitivity knob on the detector must not influence the sensor readout and even if there is only one carbon monoxide CO sensor it must be set in 0 position If the pre alarm threshold is exceeded this is indicated on the detector facia by the intermittent lighting of the ALARM LED for the sensor which h...

Страница 5: ...gas it is necessary to use small gas cylinders containing specific gases at preset concentrations releasing the gas as near as possible to the detecting sensor Only for sensors for detecting propane LPG can gas from a normal cigarette lighter be used When the gas concentration exceeds the pre alarm threshold the ALARM LED flashes With a delay about 20 seconds after exceeding the alarm threshold o ...

Отзывы: