background image

warning signals

warning signals

warning signals

ATTENTION

: Installation must be carried out by an electrician in

                      compliance with the latest codes and regulations.

ATTENTION

: Disconnect from power source before 

    installation or service to prevent electric shock.

ATTENTION

: On strobe beacons allow a minimum of 2 minutes

    for hazardous high voltage to discharge from unit.

 

Header Pin settings

for flashing modes.

A

B

C

A

B

C

A

B

C

A

B

C

1Hz Flash (60FPM)

1.5Hz Flash (90FPM)

Double Strike Flash Pattern

CPR FILE DRAWING

No modification permitted 

without reference to

"VdS"

~L

~N

Volume

Control

Tone Selection

(See Table)

AC CIRCUIT

S2

SWITCH

+

-

DC CIRCUIT

800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000

544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32-001

800/1000 Hz @ 7 Hz Sweeping
2400/2900 Hz 50 Hz Sweeping

1
2
3
4
5
6
7
8
9

Sawtooth 1200/500 Hz @ 1 Hz - DIN / PFEER P.T.A.P

10

Tone Description

Stage 1

Tone 1

Tone 2

Tone 3

Tone 4

Tone 5

Tone 6

Tone 7

Tone 8*

Tone 9*

Tone 10*

*To set tones 8, 9 & 10 

as a first stage

connect terminal 'S2' to 

'-' terminal.

800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000

544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32-001
Simulated Bell Sound
Sweeping 800/1000 Hz @ 7 Hz Sweeping
500-1200 Hz 3.75 sec / 0.25 sec Australian Evacuation
Continuous 1000 Hz - PFEER toxic gas
Continuous 554 Hz
420 Hz @ 0.625 sec Australian Alert

1
2
3
4
5
6
7
8
9

Sawtooth 1200/500 Hz @ 1 Hz - DIN / PFEER P.T.A.P

10

8

8

8

1

1

9

10

Tone Description

Stage 1

Stage 2

-
-
-

12V DC and 24V DC Tone Table

115V AC and 230V AC Tone Table

Simulated Bell Sound

Continuous 1000 Hz - PFEER toxic gas

420 Hz @ 0.625 sec Australian Alert
500-1200 Hz 3.75 sec / 0.25 sec Australian Evacuation

99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
95dB(A) @1m
99dB(A) @1m
100dB(A) @1m
100dB(A) @1m
97dB(A) @1m
97dB(A) @1m

SONF1 dB@ 1m

99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
100dB(A) @1m
95dB(A) @1m
99dB(A) @1m
100dB(A) @1m
97dB(A) @1m
100dB(A) @1m

Sonora

SONFL1X

 

Dimensions : 172 x 86 x 83mm

1.5mm² terminals

Cable entry: 1-off M20 x 1.5mm 

Temp: -25 C to +55 C

Unit weight: 0.46Kg 

B

A

Tel : +44 (0)2 8743 8880   Fax : +44 (0)20 8740 4200

mail : [email protected]     web : www.e2s.com

D176-00-501-IS-SC-CPR_SHT1_ISSUE_D

C

NOTE: Please check factory settings and ensure the correct alarm tone is selected for your country or application

Tone Selection / Header Pin Setting - Header pin settings are shown in the tone selection table. The links covered by the jumper 

are shown with a black rectangle.
Only tones 1, 2, 3, 4, 8 & 9 have been tested to EN54-3 and are compliant with the Construction Products Regulation 305/2011.

No liability is accepted for any consequences of the use of this document. The technical specification of

this unit is subject to change without notice due to our policy of continual product development. All dimensions/weights 

are approximate. This unit is sold subject to our standard conditions of sale, a copy of which is available on request.

SONFL1X Combined Sounder Xenon Beacon

10 Selectable Tones & 2 Stages

5J Xenon Flash Tube

Three Modes: Flashing 1Hz (AC & DC Units),

Flashing 1.5Hz (DC Units Only),

Double Strike (DC Units Only).

Note: Only 1Hz Flashing mode is CPR/VdS approved.

Only 24V dc Version is CPR/VdS Approved.

CE     

IP Rating: IP66  

                                                                                          Sounder

                                           Voltage                Nominal      Current       Beacon

Order code                         Range                  Voltage      @Tone 2     Current

SONFL1XDC012[X]/[Y]     10-14V dc             12 V dc        25mA         500mA    

SONFL1XDC024[X]/[Y]     20-28V dc             24 V dc       25mA         250mA  

SONFL1XAC024[X]/[Y]     24V ± 10% V ac    24 V ac       40mA         300mA     

SONFL1XAC115[X]/[Y]     115 ± 10% V ac    115 V ac     13mA          70mA

SONFL1XAC230[X]/[Y]     230 ± 10% V ac    230 V acv   13mA          35mA

[X] Denotes Body Colour,

[Y] Denotes Lens Colour: Note CPR Approved units

only available in C = Clear

Add '-UL' Suffix for UL Approved Units

(Type 4 / 4X / 3R / 13, IP66) 

S2 Denotes Stage 2. Stage switches