Operation and Maintenance Documentation 

 

 

 

 

 

 

 
 

 

 

SONNIGER Polska Sp. z o.o. Sp.K.

 

ul. 

Ś

l

ą

ska 35/37, 81-310 Gdynia, Poland, 

infolinia 801 055 155

, tel. + 48 58 785 34 80, www.sonniger.com

 

 

S

ą

d Rejonowy Gda

ń

sk-Pó

ł

noc, VIII Wydzia

ł

 Gospodarczy Krajowego Rejestru S

ą

dowego, KRS 0000

504509

NIP 586 227 35 14,Regon 22154369 kapita

ł

 zak

ł

adowy: 1.655.000 PLN

 

 

 

Содержание GUARDPR0 150E

Страница 1: ... o Sp K ul Śląska 35 37 81 310 Gdynia Poland infolinia 801 055 155 tel 48 58 785 34 80 www sonniger com Sąd Rejonowy Gdańsk Północ VIII Wydział Gospodarczy Krajowego Rejestru Sądowego KRS 0000504509 NIP 586 227 35 14 Regon 22154369 kapitał zakładowy 1 655 000 PLN ...

Страница 2: ... which is possible due to the airstream suitably directed that protects the entrance of cold air into a heated space In summers the curtains may be used as cooling devices preventing the entry of hot air from outside as well as air pollutants The GUARD PRO industrial air curtains are designed to protect against heat losses in the gateways of buildings of medium and high capacity especially such as...

Страница 3: ...electric heaters Main advantages of PTC electric heaters No current on coil surface Lower temperaturę on coil surface in comparison to old type of electric heaters for ex electric wires long life solution Large space of PTC coil enhanced energy exchange between coil and air Fully automated regulation of heat capacity depending on air flow No risk of system overheat thanks to self colling option co...

Страница 4: ...he power When the air curtain is connected directly to the cable please make sure there is a splitter protecting against any undesired disconnecting Pay special attention while transporting the device not to damage the casing When the device is being operated ensure the safety rules in accordance with the labor standards relating to the operation of any electrical devices Do not place any objects ...

Страница 5: ...e that maintenance work is possible to be conducted On both connection nozzles manual shut off valves should be installed in case of the necessity of disconnecting the unit The hot water medium supply must be connected in accordance with the marking on the casing inlet outlet When pipes being screwed to the heat exchanger make sure you secure the inlet connection of the heater to protect it agains...

Страница 6: ...t stop at the moment of opening gate Possibility to connect SPEEDER S2 speed regulator for two GUARD PRO curtains Possibility to connect SPEEDER S3 speed regulator for three GUARD PRO curtains Delivery does not include main maintenance switch To mount the curtain vertically make sure the air outlet of the curtain is as close as possible to the doorway and air gap is at the height of the upper edge...

Страница 7: ...t be conducted in accordance with the applicable building regulations and standards The connection of the unit to the power supply must be conducted by a qualified specialist who is familiar with the Manual Fan s motor is equipped with internal thermal protection against overheating Power cable and a main switch are not included in the set Also the DOORSTOP door contact switch can be installed it ...

Страница 8: ...RICAL SUPPLY OF CONTROL BOX POLARITY L N CONNECTION MUST BE KEPT AS PRESENTED ON ABOVE SCHEME L N CONNECTION CANNOT BE MIXED CONNECTED IN OPPOSITE WAY A dashed line indicates factory mounted jumpers that enables the operation of CONTROLBOX S3 without SPEEDER speed regulator When installing the SPEEDER controller jumpers must be taken out Required main priotection fuse C16 A Required electrical sup...

Страница 9: ...er and techncial manual GUARDPRO are equipped with singe phase fans 1 230 V 50 Hz it is required to use additional protection for overload and shor circuit It is not allowed to start up GUARDPRO without grounded line 7 3 Connection scheme for GUARDPRO E electric heater with a switch and power board carried out by an installer NOTICE Supply of electrical heaters 3 x 400V 50 Hz GUARDPRO 150E supply ...

Страница 10: ...ation and Maintenance Documentation of GUARD PRO air curtains v201708 www sonniger com 10 7 4 Connection scheme for GUARDPRO E electric heater with CONTROLBOX S3 and SPEEDER S2 or SPEEDER S3 speed regulator ...

Страница 11: ...Operation and Maintenance Documentation of GUARD PRO air curtains v201708 www sonniger com 11 8 DIMENSIONS GUARD PRO 150W GUARD PRO 150C GUARD PRO 150E GUARD PRO 200W GUARD PRO 200C GUARD PRO 200E ...

Страница 12: ...e goes below 0 C If the device is to operate in a room where the temperature goes below 0 C anti freeze liquid must be added to the water circulation system Anti freeze liquid must be appropriate for the material the exchanger is made of copper as well as other elements of the hydraulic system circulation The liquid must be diluted with water accordingly to the manufacturer s recommendation NOTICE...

Страница 13: ...ystem but have not been delivered by the Seller and whose inappropriate functioning has a negative impact on the device s functioning Defects caused by connecting spare parts to the components that are not original parts Defects incurred by reselling of the product by the first buyer user to another buyer who dismantles installs the device that was previously installed and operated in a specific b...

Страница 14: ...ice 6 The repair service including the replacement of the parts shall be done free of charge only if the representative of the installing contractor or the Service claims that the defect or malfunctioning of the device is caused by fault of the producer 7 Any and all costs cost of repair travel and exchanged components incurred due to the unjustified complaint especially in the situation when the ...

Страница 15: ...l Serial number Date of purchase Start date Details of installation company Person activating the device Name of company Address Telephone Signature of a person who has started the device Installation works check ups inspections repairs Date The scope of installation works inspections repairs Signature and installation company stamp ...