3 | Product description
12 / 36
Installation instructions sonnenProtect 1300
5
20
40
60
80
100
ON AL
Test
Reset
R
AL
kΩ
RCD
1
2 3
4
5
6
7
8
Illustration 4: Emergency operation
1 Plug outlet of the sonnenProtect
2 sonnenProtect
3 F1.P miniature circuit breaker
4 Storage system
5 Insulation monitor
6 AC miniature circuit breaker
7 Residual current device (RCD) - 30 mA
8 Public grid (electrical mains)
If a
grid outage
occurs, the connection to the public grid is disconnected in the storage
system. The plug outlet (1) is supplied with electrical power from the storage system
until the battery’s minimum charging status is achieved. The insulation monitor is ac-
tivated (‘ON’ LED lights up). This protects against indirect contact.
If an insulation fault occurs (R
E
< R
AL
), the insulation monitor terminates the connec-
tion to the plug outlet. The ‘AL’ LED lights up. When the insulation fault no longer ex-
ists, the connection to the plug outlet is automatically reestablished. The ‘AL’ LED
goes out.
The storage system switches back to grid operation with a delay after a grid outage.
This can take a few minutes. During this time the plug outlet is supplied with power in
emergency operation.
3.4 Type plate
The type plate is located on the outer surface of the sonnenProtect. The type plate
can be used to uniquely identify the sonnenProtect. The information on the type plate
is required for the safe use of the system and for service matters.
The following information is specified on the type plate:
• Item designation
• Item number