S-36 VLF
– USER MANUAL
18
[Enter]
[Enter]
Data recording (option - not installed on all devic-
es). Select whether the test data should be record-
ed and stored in the built in memory of the device
or not.
Measurement configuration of phases of the
measured object. E.g.:
L1 » L2 L3 E
means insulation test of phase L1
against Ground, L2 and L3 grounded,
L1 L2 L3 » E
means insulation test of all 3 phas-
es against Ground,
*S L1 » E
means sheath test, cable shield of L1
against Ground.
Display of selected test parameters. Acknowledge
parameters with
[Enter]
or correct with
[Cancel]
.
The green illumination pushbutton
[HV On]
signals
readiness for switch on.
Operate button
[HV On]
. The high-voltage is connected, the discharge switch opens. The red il-
luminated pushbutton
[HV Off]
illuminates and signals „High voltage is on“. At the same time,
the green illuminated pushbutton extinguishes.
Start with:
[HV On]
VLF Test
Frequency: 0.1 Hz
Voltage: 36.0 kV
Test time: 60 min
Test between:
► 1) L1 » L2 L3 E ◄
2) L2 » L1 L3 E
3) L3 » L1 L2 E
4) L1 L2 L3 » E
5) L1 L2 » L3 E
6) L1 L3 » L2 E
7) L2 L3 » L1 E
8) *S L1 » E
9) *S L2 » E
10) *S L3 » E
11) *S L1 L2 L3 » E
DATA RECORDING:
►1) Yes ◄
2) No