background image

 

EVSE-01 

– USER MANUAL 

10 

5.3 

Control signal CP 

 

Connect the oscilloscope to the CP socket, in order to obtain information about the Pulse-Width 

Modulation (PWM) of the control signal. The signal has a frequency of 1 kHz. Signal duty cycle indi-
cates the status of the charging station or the maximum current that the station can supply. The cur-
rent value can be determined based on the following table, contained in EN 61851-1 standard. 
 

 

 
 
 

 

NOTE! 

 

 

Test CP signal in relation to the PE line.  

 

We  recommend  using  a  battery-powered  portable oscilloscopes  with  isolated  input 
and differential probes that ensure galvanic isolation of the oscilloscope. 

 

If  the  ground  wire  of  the  oscilloscope  is  not  isolated  from  its  casing,  then  before 
connecting  the  oscilloscope,  make  sure  that  the  PE  line  of  the  charging  station  is 
free from dangerous voltage!  

 
 

Содержание EVSE-01

Страница 1: ...4...

Страница 2: ...4...

Страница 3: ...USER MANUAL ADAPTER FOR TESTING VEHICLE CHARGING STATIONS EVSE 01 FOR MPI METERS SONEL S A Wokulskiego 11 58 100 widnica Poland Version 1 03 10 07 2020...

Страница 4: ...ings 5 5 Measurements 6 5 1 Automatic measurements 6 5 2 Manual measurements 8 5 3 Control signal CP 10 6 Cleaning and maintenance 11 7 Storage 11 8 Dismantling and utilisation 11 9 Technical data 11...

Страница 5: ...health and safety regula tions and with other relevant fire regulations required during the performance of a particular type of work The adapter must not be used for networks and devices in areas with...

Страница 6: ...vidual measurements Perform measurements for all required com binations of settings CP C or D with these settings you can measure the fault loop impedance and test residual current circuit breakers CP...

Страница 7: ...ing etc EVSE 01 provides a simulation of situations when the charged object is connected to the charging source via a ca ble with a pre set maximum current PP and the charging cycle is in a mode set o...

Страница 8: ...of the meter Select the test required for your meas urements Enter the settings required during the tests For test ZL N ZL L ZL PE RCD protection of phases L1 L2 L3 supplying the charger method for ca...

Страница 9: ...work Set CP C or D RCD results from the safety device of the charger Set CP C or D RISO results from the basic insulation of the charger Set CP B After completion of the measurement a summary is displ...

Страница 10: ...e test Connect EVSE 01 to the meter If you test 3 phase chargers use banana socket cables If you test 1 phase charger use banana socket cables or WS adapter If you use the WS adapter for testing a 3 p...

Страница 11: ...If you test RCD you need to measure L1 PE L2 PE L3 PE If you test RISO you need to measure L1 PE L2 PE L3 PE N PE or L1 L2 L3 N PE Enter settings to EVSE 01 and start the measurement Before and during...

Страница 12: ...ation can supply The cur rent value can be determined based on the following table contained in EN 61851 1 standard NOTE Test CP signal in relation to the PE line We recommend using a battery powered...

Страница 13: ...onic equipment should be gathered selectively i e it must not be placed with waste of another kind Worn out electronic equipment should be sent to a collection point in accordance with the law of wast...

Страница 14: ...tion state E error CP short to PE i socket types measuring sockets L1 L2 L3 N PE 1 phase socket CP signal socket PWM communication j test lead length EVSE 1 m MPI 0 5 m k operating temperature 5 45 C...

Страница 15: ...I 530 MPI 525 MPI 520 MPI 502 Auto measurements Automatic three phase measurement via multiplug Visual inspection Fault loop ZL PE ZL N parameters measure ment 6 mA RCD test RCD test AC A F B B EV AC...

Страница 16: ...EVSE 01 USER MANUAL 14...

Отзывы: