by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that 

is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can 

correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If 

you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of 

FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The 

correction value starts from 00 6B. We take the first parameter as an example. The correction value is read 

and modified in the same way for multiple parameters. 

Device ID 

Function id 

Start Address 

Data Length 

CRC16 

01 

03 

00 6B 

00 01 

F5 D6 

        For the correct query command, the device will respond, for example the response data is: 01 03 02 

00 64 B9 AF, the format of which is as shown in the following table:  

Device ID 

Function id 

Data Length 

Data value 

CRC16 

01 

  03 

02 

00 64 

B9 AF 

        In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the 

first state quantity correction value register. If the device has multiple parameters, other parameters 

operate in this way. The same, the general temperature, humidity have this parameter, the light generally 

does not have this item. 

        (2)Change correction value 

        For example, the current state quantity is too small, we want to add 1 to its true value, and the current 

value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .   

Device ID 

Function id 

Start Address 

Destination 

CRC16 

01 

06 

00 6B 

00 64 

F9 FD 

        After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the 

parameters take effect immediately after successful change. 

        Disclaimer 

        This document provides all information about the product, does not grant any license to intellectual 

property, does not express or imply, and prohibits any other means of granting any intellectual property 

rights, such as the statement of sales terms and conditions of this product, other issues. No liability is 

assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use 

of this product, including the suitability for the specific use of the product, the marketability or the 

infringement liability for any patent, copyright or other intellectual property rights, etc. Product 

specifications and product descriptions may be modified at any time without notice.  

        Contact Us 

        Company: Shanghai Sonbest Industrial Co., Ltd   

        Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China  

        Web: http://www.sonbest.com  

        Web:    http://www.sonbus.com   

        SKYPE:  soobuu   

        Email: [email protected] 

        Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077 

 

Содержание SM1212B-12

Страница 1: ...parameter Parameter value Brand SONBEST Temperature measuring range 30 80 Temperature measuring accuracy 0 5 25 Support sensor SHT20 Channels 12 Input bus IIC Humidity measuring range 0 100 RH Humidity accuracy 3 RH 25 Communication Interface RS485 Default baud rate 9600 8 n 1 Power DC9 24V 1A Running temperature 40 80 C Wiring instructions Any incorrect wiring can cause irreversible damage to the...

Страница 2: ...ification is 100 the actual value is 121 100 1 21 Others and so on 2 Data Address Table Address Start Address Description Data type Value range 40001 00 00 1 temperatureregister Read only 0 65535 40002 00 01 2 humidityregister Read only 0 65535 40003 00 02 3 temperatureregister Read only 0 65535 40004 00 03 4 humidityregister Read only 0 65535 40005 00 04 5 temperatureregister Read only 0 65535 40...

Страница 3: ...4 Read and Modify Baud Rate 1 Read baud rate The device default factory baud rate is 9600 If you need to change it you can change it according to the following table and the corresponding communication protocol For example read the current device s baud rate ID the command is 01 03 00 67 00 01 35 D5 its format is parsed as follows Device ID Function id Start Address Data Length CRC16 01 03 00 67 0...

Страница 4: ... the general temperature humidity have this parameter the light generally does not have this item 2 Change correction value For example the current state quantity is too small we want to add 1 to its true value and the current value plus 100 correction operation command is 01 06 00 6B 00 64 F9 FD Device ID Function id Start Address Destination CRC16 01 06 00 6B 00 64 F9 FD After the operation is s...

Отзывы: