                SM1212B-12    Us er Ma nual                   

http://www.sonbus.com/ 

Sha nghai Son

best Industrial Co., Ltd                                                                             Page1

 

 

 

SM1212B-12 

 

 

User Manual   

 

File Version: V21.4.24

   

        SM1212B-12 using the standard    RS485 bus MODBUS-RTU protocol,easy access to PLC

DCS and 

other instruments or systems for monitoring temperature,humidity@12 state quantities.The internal use of 

high-precision sensing core and related devices to ensure high reliability and excellent long-term 

stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and 

other output methods. 

        Technical Parameters 

Technical parameter 

Parameter value 

Brand 

SONBEST 

Temperature measuring range 

-30

~80

 

Temperature measuring accuracy 

±

0.5

  @25

 

Support sensor 

SHT20 

Channels 

12 

Input bus 

IIC 

Humidity measuring range 

0~100%RH 

Humidity accuracy 

±

3%RH @25

 

Communication Interface 

RS485 

Default baud rate 

9600 8 n 1 

Power 

DC9~24V 1A 

Running temperature 

-40~80° C 

        Wiring instructions 

        Any incorrect wiring can cause irreversible damage to the product. Pleas e carefully wire the cable as 

follows in the case of power failure, and then connect the cable to confirm the correctness and then use it 

again.   

ID 

Core color 

Identification 

Note 

Red 

V+ 

Power + 

Green 

V- 

Power - 

Yellow 

A+ 

RS485 A+ 

Blue 

B- 

RS485 B- 

                                     

        In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the 

Содержание SM1212B-12

Страница 1: ...parameter Parameter value Brand SONBEST Temperature measuring range 30 80 Temperature measuring accuracy 0 5 25 Support sensor SHT20 Channels 12 Input bus IIC Humidity measuring range 0 100 RH Humidity accuracy 3 RH 25 Communication Interface RS485 Default baud rate 9600 8 n 1 Power DC9 24V 1A Running temperature 40 80 C Wiring instructions Any incorrect wiring can cause irreversible damage to the...

Страница 2: ...ification is 100 the actual value is 121 100 1 21 Others and so on 2 Data Address Table Address Start Address Description Data type Value range 40001 00 00 1 temperatureregister Read only 0 65535 40002 00 01 2 humidityregister Read only 0 65535 40003 00 02 3 temperatureregister Read only 0 65535 40004 00 03 4 humidityregister Read only 0 65535 40005 00 04 5 temperatureregister Read only 0 65535 40...

Страница 3: ...4 Read and Modify Baud Rate 1 Read baud rate The device default factory baud rate is 9600 If you need to change it you can change it according to the following table and the corresponding communication protocol For example read the current device s baud rate ID the command is 01 03 00 67 00 01 35 D5 its format is parsed as follows Device ID Function id Start Address Data Length CRC16 01 03 00 67 0...

Страница 4: ... the general temperature humidity have this parameter the light generally does not have this item 2 Change correction value For example the current state quantity is too small we want to add 1 to its true value and the current value plus 100 correction operation command is 01 06 00 6B 00 64 F9 FD Device ID Function id Start Address Destination CRC16 01 06 00 6B 00 64 F9 FD After the operation is s...

Отзывы: