2. Common use menu explanation

3. Uncommon use menu explanation

TC4

TC9

TC7

16

S S R

O U T 1

17

-

+

14

S S R

O U T 1

13

-

+

TC6

Note:

17

S S R

O U T 1

18

-

+

Model with “M”, ssr output terminal

TC8

17

S S R

O U T 1

18

-

+

Model with “M”, ssr output terminal

Note:

13

S S R

O U T 1

11

-

+

NC

7

6

4

5

Lock function; 001: SV value can not be modified, 
010:menu setting value only can be checked ,cannot modified. 
033: If set it as 033 ,it can enter to uncommon menu . 
123: reset to factory defalut setting

Control type,0:ON/OFF control; related pararmeter: DB

1:PID heating control , related parameter: P , I , D, OVS, CP, ST, SPD

 2:compressor cooling , parameter: DB , PT 

 3:PID heating & cooling control . related parameters: P, I, D, OVS,DB,

 CP, CP1, PC, ST, SPD

0

999

0

8

9

10

11

12

13

14

15

16

17

18

K

CU100

0

3

K

1

0

999

30

0 ~ 999

120

0 ~ 999

30

0 ~ 999

5

0

100

5

1

200

20

4

200

20

1

100

10

Description

1

2

3

4

5

6

7

FL

FH

0

100

0

12

FL

FH

0

100

0

6

-199

999

10 

1

3

5

1

4

0

No. symbol

1st alarm value, note: the minus is dealed as absolute value when it is

as a deviation value .

Set range

Factory setting

1st alarm hystersis

1st alarm mode . Note: when 1st alarm is used as OUT2 , should set
 as  0. When setting as 0, it close alarm function. When set value 

6

 should set AD2 as 0. (refer to alarm output logic diagram on page 6)

2nd alarm value,note:the minus is dealed as absolute value when it is as

a deviation value .

2nd alarm hystersis

2nd alarm mode. Note: When AD1

6, should set this value as 0 to 

close the alarm function.(refer to alarm output logic diagram on page 6)

Amend value,display value=actual measured value+ amend value

Optional input measured signal type:refer to input signal parameters 
table.Note:it need to change the relevant parameters after changing.

Proportional band,the lower of setting value,the faster of system heating .

Increase proportional band can reduce vibration,but it may increase control 

bias.Reduce proportional band  reduce control bias, may cause vibration

Integral time the lower of the value,the stronger of integral action,the more 

tendency to eliminate and deviation of set value.If integral action is too weak,

it may not eliminate the deviation. Unit: Second
Differential time,reduce effect of differential time to proper value,which prevent 
system oscillation.The higher value,the stronger function of differential.Unit:s

Overshoot limit,in the process of PID control,when PV>SV+OVS,it force off 

output; The lower value,the lower PID adjusted range,the worse control 

stability;please set a proper value according actual state.

On-off control backlash(nagetive backlash on-off control) or cooling control 
and compressor cooling control dead zone. please change value according  
to decimal position,when you change input sigal type type.

OUT1 heating control cycle,   1:SSR control output,  
                                                4-200: relay control output.        (Unit:second)

OUT2 control cycle,cooling relay output cycle.Unit:second

OUT2 cooling proportionality coefficient,the higher of value,the stronger of 

cooling

19

20

21

22

0

1

0

1

0

0

N

999

-50

0

10

0

999

180

0

5

0

6

0

0

5

0

1

0

23

24

25

26

27

28

29

30

31

0.0~2.0

1.0

V1.0

0~255

℃、

AT

Control output : 0: relay output  1: single SSR output

Power on auto-tuning setting. 0: normal control after power on   

to exit the auto-tuning.

Control speed fine tuning,optional 0(N)no function,1(slow),2(ss)medium slow,
3

SSS

very slow

4

F

fast

5

FF

 medium fast

6

FFF

express

Compressor starting delay ,unit:s

1st alarm extended function

2nd alarm extended function

Measure range low limit, setting value must be less than measure 

range high limit

Measure range high limit, setting value must be more than measure

 range low limit.

Decimal point setting

 filter coefficient ,the higher of value,the stronger of filter function

Temperature unit

PV fuzzy tracking value,it can get stable control display value in some status.
 Note:when the alarm setting value is equal with SV setting value after setting 
the DTR value,operation of alarm output is subject to actual measured value.
Setting 0 to close the function.     

Software version

cannot modified

refer to input signal table

refer to input signal table

1: meter enter into pid auto-tuning status after power on. long press

Key function operation

 1. Run/stop operation
    1

Under the measure mode,press “    ” into monitoring mode;and on the SV window display “STP” . Long Press “    ” to exit.

    2

It can modify SV value and shift mode operation even if displaying STP.

    3

Under the monitoring mode, main control output will stop

2. PID Parameter confirmation and auto-tuning operation:
    1

Factory default PID may not be suitable to usage occasion;please use auto-tuning function to get suitable PID setting.

    2

The meter will make control output after power on a short period. User can set the meter to monitor mode to make sure

         auto-tuning effect, or switch off the power of control output load at temporary . No matter how to operate, it should guarantee
         the set value is larger than  the present measured value, it is better if much larger.
   3

In order to avoid the effect of alarm output,please set the proper alarm value,or remove the alarm effect.

   4

Set proper SV value .

   5

Set OT as 1 (PID control).

   6

Under the condition of PV value at normal room temperature, exit the monitoring mode or switch on load power,and 

         long press  “        ” to enter auto-tuning mode, and AT indication light will flashing.
   7

Auto-tuning need a period, to ensure the auto-tuning result,please don`t modify parameters or power-off during auto tuning.

   8

When AT light is off , it will exit the auto-tuning. PID will update automatcially, and can get good control result.

   9

During  auto-tuning, long press “        ” key, measure beyond the range,display abnormally, shift to “STP” status,power-off 

         ect will stop the auto-tuning.
  10

Experienced users can set a proper PID parameter according to their experience.

3. PID & Cooling control operation (suitable for injection molding machine ,  extruding machine ect)
   1)  Please set OT parameter as 3
   2

PID control act on main control output OUT1

Cooling control act on OUT2.

   3

AL1 alarm relay will be used as OUT2 control output.

   4

Please set the cooling start offset DB to a value bigger than 5,to ensure the cooling would not affect the PID control impact.

   5

Please set cooling control cycle CP1 to a proper value,and modify the cooling proportional coefficient to a a proper value.

   6

When PV value > SV+DB value,the cooling control start to effect;the bigger value of PV,the longer output time of OUT2

R/S 

R/S 

AT

AT

Wire Connection

Model with “M”, ssr output terminal

Model with “M”, ssr output terminal

Model with “M”, ssr output terminal

Note:

Note:

Note:

Display

LLLL/HHHH

Methods

Check whether the input disconnection, check the FH and FL value,  Check working 

environment temperature , Check whether input signal is selected correctly.

Simple TroubleShooting Method 

1

Alarm parameters and output logic diagram:

Symbol description

” means alarm hystersis 

 

“▲” means alarm value

“   ” means SV value

No.

Type

High limit absolute value alarm

1

2

3

4

5

6

High limit deviation value alarm

Low limit deviation value alarm

High/low limit deviation value alarm

High/low limit interval value alarm

Low limit absolute value alarm

Alarm output

AL1

AL2 is independent of each other

Image

the hatched section means the alarm action

SV+AL

SV+AL

SV-AL

SV

SV

SV-AL SV

SV+AL

SV-AL

AL

AL

When the alarm value with deviation alarm set to a negative number,it will deal with it as an absolute value.

7

8

9

10

11

12

High/low limit absolute value alarm

High/low limit deviation value alarm

High/low absolute value alarm

High/low limit deviation alarm

Alarm between high limit absolute

value and low limit deviation value .

Alarm between high limit deviation

value and low limit absolute value.

The following two group of alarm parameters(AL1

AL2) used in 

combination,AL1 alarm output , AD2 must set to 0

SV

SV

SV

SV

SV

SV

SV-AL1

SV-AL1

SV-AL1

SV+AL2

SV+AL2

SV+AL2

AL2

AL2

AL2

AL1

AL1

AL1

No.

Type

2

Alarm extension function table

0
1
2

5

3
4

AE1/AE2 value

Alarm handling mode when show HHHH/LLLL

Forced alarm output
Forced alarm close

Forced alarm output
Forced alarm close

Remark

The state when alarm keep HHH/LLL in previous time

The state when alarm keep HHH/LLL in previous time

Power on alarm,  alarm does not inhibit

(As long as meet the requirement

 of alarm , make alarm output)

Power on alarm , alarm inhibits.

(Before PV value reach the set value at the 

first time ,the alarm does not output)

Alarm function logic diagram